256819-YTG-J-1208
DESCRIPTION
The Affinity Air Handler line offers the ultimate in comfort, sound
and application flexibility. The Affinity models utilize a whisper
quiet variable speed motor that provides humidity control and
the lowest operating cost in the industry. The AVY air handler is
shipped ready to be installed in all positions, upflow, downflow,
horizontal left or right, with minor adjustments. The SVY 48 &
60 models are upflow only models designed into a shorter cabi-
net, for those
Summary of the content on the page No. 2
256819-YTG-J-1208 DIMENSIONS F 10-3/8” J K TOP OUTLET CIRCUIT DIMENSIONS BREAKER PANEL 18-9/32” BLOWER E COMPARTMENT BOTTOM INLET A DIMENSIONS DRAIN CONNECTIONS FOR UPFLOW AND DOWNFLOW APPLICATIONS D REFRIGERANT CONNECTIONS 7-11/32” 1-1/2” C B FILTER DRAIN PAN CONNECTIONS ACCESS FOR HORIZONTALAPPLICATIONS DIMENSIONS 1 Refrigerant Dimensions (Inches) Wiring Knockouts Connections Models AB C JK Line Size DE F Height Width Depth Power Control Liquid Vapor AVY24B**H21 46 17.5 12-3/8 13-29/32 14-19/
Summary of the content on the page No. 3
256819-YTG-J-1208 COIL TECHNICAL DATA Refrig. Face Area Rows Fin Tube Tube Fin Models Application Coil Size TXV Conn. Types (Sq. Ft.) Deep Per In. Geometry Dia. Type AVY24B3XH21 None AVY24B2AH21 2A Cooling / AVY24B4EH21 Sweat 3.89 2 14 (2) 16 x 17.5 1 x 0.866 3/8 Enhanced 4E Heat Pump AVY24B4FH21 4F AVY24B4KH21 4K AVY36C3XH21 None AVY36C2AH21 2A AVY36C4EH21 4E AVY36C4FH21 4F Cooling / Sweat 4.86 3 12 (2) 20 x 17.5 1 x 0.866 3/8 Enhanced Heat Pump AVY36C4GH21 4G AVY36C4HH21 4H AVY36C4KH21 4K AV
Summary of the content on the page No. 4
256819-YTG-J-1208 Air Handler Air Flow Data HIGH / LOW SPEED COOLING AND HEAT PUMP AIRFLOW CFM JUMPER SETTINGS 24B 36C High Low High Low COOL Tap ADJ Tap 1088 707 1387 905 A B 830 542 1151 753 B B 948 617 1201 783 A A 716 465 1009 657 B A 854 556 1086 703 A C 612 462 953 622 C B 637 460 901 588 B C 531 460 754 493 D B 542 462 831 540 C A 462 462 657 460 D A 474 460 751 494 C C 461 464 588 461 D C 48D 60D JUMPER SETTINGS High Low High Low COOL Tap ADJ Tap 2138 1442 2364 1545 A B 1759
Summary of the content on the page No. 5
256819-YTG-J-1208 APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM 80% 90% Rated CFM 110% 120% % Of Rated Airflow 0.96 0.98 1.00 1.02 1.03 Capacity Factor PHYSICAL & ELECTRICAL DATA - COOLING ONLY (60 Hz) AVY48D**H21 AVY60D**H21 Models AVY24B**H21 AVY36C**H21 SVY48D**N21 SVY60D**N21 Blower - Diameter x Width 10 x 7 10 x 7 10 x 10 10 x 10 HP 1/3 1/2 3/4 1 Motor Nominal RPM 1200 1200 1200 1200 Voltage 230 Amps Full Load (230) 2.8 4.3 5.5 7.0 Type DISPOSABLE OR PERMANENT 1 Size 16 x 20 x1 20 x 20 x1
Summary of the content on the page No. 6
256819-YTG-J-1208 ELECTRICAL DATA - 208/230-1-60 1 kW Staging Total Heat Max. Min. Models Heat Kits* KW MBH W1 Only W2 Only W1 & W2 Static Speed Tap 208v 230v 208v 230v 208v 230v 208v 230v 208v 230v 4HK*6500206 0.5 Heat-D 1.9 2.5 6.4 8.5 1.9 2.5 1.9 2.5 1.9 2.5 4HK*6500506 0.5 Heat-D 3.6 4.8 12.3 16.4 3.6 4.8 3.6 4.8 3.6 4.8 AVY24B**H21 4HK*6500806 0.5 Heat-C 5.6 7.5 19.2 25.6 2.8 3.75 5.6 7.5 5.6 7.5 4HK*6501006 0.5 Heat-B 7.2 9.6 24.6 32.8 3.6 4.8 7.2 9.6 7.2 9.6 4HK165N1506 0.5 Heat-A 10.8 14
Summary of the content on the page No. 7
256819-YTG-J-1208 ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60 Field Wiring Heater Heat Kit - 1 Models Amps Min. Circuit Ampacity 75°C Wire Size - AWG Max. O.C.P. Amps/Type Single Phase* 240V 208V 230V 208V 230V 208V 230V 4HK*6500206 10.4 15.28 16.53 20 20 12 12 4HK*6500506 20.0 25.67 28.50 30 30 10 10 AVY24B**H21 4HK*6500806 31.3 37.85 42.63 45 45 8 8 4HK*6501006 40.0 47.33 53.50 50 60 8 6 4HK165N1506 60.0 69.00 78.50 70 90 4 3 4HK*6500506 20.0 27.54 30.38 30 35
Summary of the content on the page No. 8
256819-YTG-J-1208 ELECTRICAL DATA - 208/230-3-60 1 KW Staging Total Heat Min. Heat Kit - Max. Models Speed KW MBH W1 Only W2 Only W1 + W2 Three Phase Static Tap 208V 230V 208V 230V 208V 230V 208V 230V 208V 230V AVY24B**H21 4HK06501025 0.5 Heat-B 7.2 9.6 24.6 32.8 7.2 9.6 7.2 9.6 7.2 9.6 4HK06501025 0.5 Heat-C 7.2 9.6 24.6 32.8 7.2 9.6 7.2 9.6 7.2 9.6 AVY36C**H21 4HK06501525 0.5 Heat-C 10.8 14.4 36.9 49.1 10.8 14.4 10.8 14.4 10.8 14.4 4HK06501025 0.5 Heat-C 7.2 9.6 24.6 32.8 7.2 9.6 7.2 9.6 7.
Summary of the content on the page No. 9
256819-YTG-J-1208 ACCESSORIES LIMITATIONS Refer to Price Manual for specific model numbers where not These units must be wired and installed in accordance with all shown. national and local safety codes. Voltage limits are as follows: TXV Kits - TXV kits are available for “Flex-coil” applications and converting R-22 to R-410A or as a service replacement. All kits 1 Normal Operating are bolt-on and require no brazing to install. Air Handler Voltage Voltage code Voltage Range Electric Heaters -
Summary of the content on the page No. 10
TWO-STAGE COOLING WIRING CONTROL WIRING - Air Handler & New UPG HP Systems Two Stage H/P with York Guard VI Board & Copeland “Ultra Tech” Conventional Application - Not Hot Heat Pump 2 - STAGE SCROLL AIR HANDLER HEAT PUMP BOARD THERMOSTAT RR R GG Y2 Y2 Y/Y2 Y2 OUT Y1 Y1 Y1 W2 W2 OUT E W1 W1 OUT W W O O O * HUMIDISTAT HUM BS X/L X/L X/L C COM C * Optional dehumidification humidistat switch contacts open on humidity rise. NOTES: 1. “Y/Y2” Terminal on air handler control board must be connected for