Toshiba RAV-SM562UT-E user manual

User manual for the device Toshiba RAV-SM562UT-E

Device: Toshiba RAV-SM562UT-E
Category: Air Conditioner
Manufacturer: Toshiba
Size: 5.63 MB
Added : 11/22/2014
Number of pages: 196
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Toshiba RAV-SM562UT-E. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Toshiba RAV-SM562UT-E.

For your convenience

If looking through the Toshiba RAV-SM562UT-E user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Toshiba RAV-SM562UT-E on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Toshiba RAV-SM562UT-E to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Toshiba RAV-SM562UT-E User manual - Online PDF
Advertisement
« Page 1 of 196 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Toshiba RAV-SM562UT-E but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Toshiba RAV-SM562UT-E. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

FILE NO. A05-018
Revised : Nov. 2006
SERVICE MANUAL/INTEGRATION
AIR-CONDITIONER
SPLIT TYPE
INDOOR UNIT

RAV-SM562UT-E RAV-SM562BT-E RAV-SM562CT-E
RAV-SM802UT-E RAV-SM802BT-E RAV-SM802CT-E
RAV-SM1102UT-E RAV-SM1102BT-E RAV-SM1102CT-E
RAV-SM1402UT-E RAV-SM1402BT-E RAV-SM1402CT-E

RAV-SP1102UT-E
• Service Manual for RAV-SM[[[KRT and RAV-SM[[[XT contact the Sales company or Dealer.
OUTDOOR UNIT

RAV-SM562AT-E RAV-SM802AT-E RAV-SM1102AT-E RA

Summary of the content on the page No. 2

ADOPTION OF NEW REFRIGERANT This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer. WARNING Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to have a service person do it. Do not attempt it yourself. The cleaning diagram for the air filter is there for the service person, and not for the customer. NOTE A direct curre

Summary of the content on the page No. 3

7. REFRIGERANT R410A ............................................................................ 51 7-1. Safety During Installation/Servicing ............................................................... 51 7-2. Refrigerant Piping Installation....................................................................... 51 7-3. Tools .................................................................................................................. 55 7-4. Recharging of Refrigerant..................

Summary of the content on the page No. 4

SAFETY CAUTION The important contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents (Indications/Illustrated marks), and keep them. [Explanation of indications] Indication Explanation Indicates contents assumed that an imminent danger causing a death or serious injury of DANGER the repair engineers and the third parties when an incorrect work ha

Summary of the content on the page No. 5

WARNING Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs. If the earth wire is not correctly connected, contact an electric engineer for rework. Check earth wires. Do not modify the products. Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury. Prohibition of modification. For spare parts, use those specified (∗ ∗ ∗ ∗ ∗). If unspecifi

Summary of the content on the page No. 6

WARNING After the work has finished, be sure to use an insulation tester set (500V mugger) to check the resistance is 2MΩΩΩΩΩ or more between the charge section and the non-charge metal section (Earth position). If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s Insulator check side. When the refrigerant gas leaks during work, execute ventilation. If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigeran

Summary of the content on the page No. 7

 New Refrigerant (R410A) This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer. 1. Safety Caution Concerned to New Refrigerant The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner w

Summary of the content on the page No. 8

4. Tools 1. Required Tools for R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types. 1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22)) 2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22) 3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below show

Summary of the content on the page No. 9

1. SPECIFICATIONS 1-1. Indoor Unit 1-1-1. 4-Way Air Discharge Cassette Type Indoor unit RAV- SM562UT-E SM802UT-E SM1102UT-E SM1402UT-E Model Outdoor unit RAV- SM562AT-E SM802AT-E SM1102AT-E SM1402AT-E Cooling capacity (kW) 5.3 7.1 10.0 12.3 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 8.42 – 7.72 11.32 – 10.37 16.30 – 16.00 19.20 – 17.60 Power consumption (kW) 1.76 2.34 3.52 4.09 Power factor (%) 95 94 98 97 Cooling E

Summary of the content on the page No. 10

Indoor unit RAV- SM562UT-E SM802UT-E SM1102UT-E SM1402UT-E Model Outdoor unit RAV- SP562AT-E SP802AT-E SP1102AT-E SP1402AT-E Cooling capacity (kW) 5.3 7.1 10.0 12.5 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 7.17 – 6.57 8.95 – 8.21 11.24 – 10.31 16.51 – 15.14 Power consumption (kW) 1.53 1.93 2.40 3.56 Power factor (%) 97 98 97 98 Cooling EER (W/W) 3.46 3.68 4.17 3.51 Energy efficiency class * AA AA Energy ratin

Summary of the content on the page No. 11

1-1-2. Concealed Duct Type Indoor unit RAV- SM562BT-E SM802BT-E SM1102BT-E SM1402BT-E Model Outdoor unit RAV- SM562AT-E SM802AT-E SM1102AT-E SM1402AT-E Cooling capacity (kW) 5.0 7.1 10.0 12.5 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 8.99 – 8.24 12.23 – 11.21 16.50 – 15.10 20.70 – 19.00 Power consumption (kW) 1.78 2.53 3.56 4.42 Power factor (%) 90 94 98 97 Cooling EER (W/W) 2.81 2.81 2.81 2.83 Energy efficiency cla

Summary of the content on the page No. 12

Indoor unit RAV- SM562BT-E SM802BT-E SM1102BT-E SM1402BT-E Model Outdoor unit RAV- SP562AT-E SP802AT-E SP1102AT-E SP1402AT-E Cooling capacity (kW) 5.0 7.1 10.0 12.5 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 6.51 – 5.97 9.74 – 8.93 11.72 – 10.74 18.09 – 16.58 Power consumption (kW) 1.39 2.10 2.50 3.90 Power factor (%) 97 98 97 98 Cooling EER (W/W) 3.60 3.38 4.00 3.21 Energy efficiency class * AAA A Energy ratin

Summary of the content on the page No. 13

1-1-3. Under Ceiling Type Indoor unit RAV- SM562CT-E SM802CT-E SM1102CT-E SM1402CT-E Model Outdoor unit RAV- SM562AT-E SM802AT-E SM1102AT-E SM1402AT-E Cooling capacity (kW) 5.0 7.0 10.0 12.3 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 8.71 – 7.98 12.23 – 11.21 16.20 – 14.90 21.18 – 19.40 Power consumption (kW) 1.82 2.53 3.51 4.52 Power factor (%) 95 94 98 97 Cooling EER (W/W) 2.75 2.77 2.85 2.72 Energy efficiency clas

Summary of the content on the page No. 14

Indoor unit RAV- SM562CT-E SM802CT-E SM1102CT-E SM1402CT-E Model Outdoor unit RAV- SP562AT-E SP802AT-E SP1102AT-E SP1402AT-E Cooling capacity (kW) 5.0 7.1 10.0 12.5 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 6.61 – 6.06 9.47 – 8.93 11.24 – 10.31 18.09 – 16.58 Power consumption (kW) 1.41 2.10 2.40 3.90 Power factor (%) 97 98 97 98 Cooling EER (W/W) 3.55 3.38 4.17 3.21 Energy efficiency class * AAA A Energy ratin

Summary of the content on the page No. 15

1-1-4. Twin Type Type 4-Way Air Cassette Concealed Duct Under Ceiling Indoor unit 1 RAV- SM562UT-E SM802UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E Model Indoor unit 2 RAV- SM562UT-E SM802UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E Outdoor unit RAV- SM1102AT-E SM1402AT-E SM1102AT-E SM1402AT-E SM1102AT-E SM1402AT-E Cooling capacity (kW) 10.0 12.5 10.0 12.5 10.0 12.3 Heating capacity (kW) 11.2 14.0 11.2 14.0 11.2 14.0 Indoor unit Indoor unit Power supply 1 phase 230V (220 – 24

Summary of the content on the page No. 16

Type 4-Way Air Cassette Concealed Duct Under Ceiling Indoor unit 1 RAV- SM562UT-E SM802UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E Model Indoor unit 2 RAV- SM562UT-E SM802UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E Outdoor unit RAV- SP1102AT-E SP1402AT-E SP1102AT-E SP1402AT-E SP1102AT-E SP1402AT-E Cooling capacity (kW) 10.0 12.5 10.0 12.5 10.0 12.3 Heating capacity (kW) 11.2 14.0 11.2 14.0 11.2 14.0 Indoor unit Indoor unit Power supply 1 phase 230V (220 – 240V) 50Hz Ru

Summary of the content on the page No. 17

1-2. Outdoor Unit Model name RAV- SM562AT-E SM802AT-E SM1102AT-E SM1402AT-E 1 phase 230V (220 – 240V) Power supply 50Hz (Power exclusive to outdoor is required.) Type Hermetic compressor Compressor Motor (kW) 1.1 1.6 2.5 3.0 Pole 4444 Refrigerant charged (kg) 1.0 1.7 2.8 2.8 Refrigerant control Pulse motor valve Standard length (m) 7.5 7.5 7.5 7.5 Min. length (m) 5.0 5.0 5.0 5.0 Max. total length (m) 30 30 50 50 Inter connecting pipe Additional refrigerant charge 20g/m 40g/m 4

Summary of the content on the page No. 18

Model name RAV- SP562AT-E SP802AT-E SP1102AT-E SP1402AT-E 1 phase 230V (220 – 240V) Power supply 50Hz (Power exclusive to outdoor is required.) Type Hermetic compressor Compressor Motor (kW) 2.0 2.0 3.75 3.75 Pole 4444 Refrigerant charged (kg) 1.5 2.1 2.95 2.95 Refrigerant control Pulse motor valve Standard length (m) 7.5 7.5 7.5 7.5 Min. length (m) 5.0 5.0 5.0 5.0 Max. total length (m) 50 50 70 70 Inter connecting pipe Additional refrigerant charge 20g/m 40g/m 40g/m 40g

Summary of the content on the page No. 19

1-3. Operation Characteristic Curve • Operation characteristic curve RAV-SM562AT-E, RAV-SM802AT-E 14 16 14 12 RAV-SM802AT-E RAV-SM802AT-E RAV-SM802AT-E RAV-SM802AT-E 12 10 10 8 8 6 RAV-SM562AT-E RAV-SM562AT-E 6 RAV-SM562AT-E RAV-SM562AT-E 4 4  Conditions  Conditions Indoor : DB27˚C/WB19˚C Indoor : DB20˚C Outdoor : DB35˚C Outdoor : DB7˚C/WB6˚C 2 2 Air flow : High Air flow : High Pipe length : 7.5m Pipe length : 7.5m 230V 230V 0 0 0 20 40 60708090 100 0 204

Summary of the content on the page No. 20

 Operation characteristic curve RAV-SP562AT-E, RAV-SP802AT-E 14 16 14 12 RAV-SP802AT-E RAV-SP802AT-E 12 RAV-SP802AT-E RAV-SP802AT-E 10 10 RAV-SP562AT-E RAV-SP562AT-E 8 8 6 6 RAV-SP562AT-E RAV-SP562AT-E 4 4  Conditions  Conditions Indoor : DB27˚C/WB19˚C Indoor : DB20˚C Outdoor : DB35˚C Outdoor : DB7˚C/WB6˚C 2 2 Air flow : High Air flow : High Pipe length : 7.5m Pipe length : 7.5m 230V 230V 0 0 0 20406 500 70 80 100 0 204060 70 8090 100 Compressor sp


Alternative user manuals
# User manual Category Download
1 Toshiba CARRIER RAS-15LAV-UL User manual Air Conditioner 228
2 Toshiba CARRIER RAS-17LAV-UL User manual Air Conditioner 25
3 Toshiba CARRIER RAS-17LKV-UL User manual Air Conditioner 79
4 Toshiba CARRIER RAS-22LKV-UL User manual Air Conditioner 53
5 Toshiba CARRIER RAV-SP180UT-UL User manual Air Conditioner 29
6 Toshiba CARRIER RAS-15LKV-UL User manual Air Conditioner 84
7 Toshiba CARRIER RAV-SP180CT-UL User manual Air Conditioner 10
8 Toshiba CARRIER RAV-SP240CT-UL User manual Air Conditioner 3
9 Toshiba CARRIER RAS-22LAV-UL User manual Air Conditioner 4
10 Toshiba CARRIER RAV-SP180AT2-UL User manual Air Conditioner 8
11 Toshiba CARRIER RAV-SP240AT2-UL User manual Air Conditioner 11
12 Toshiba CARRIER RAV-SP300AT2-UL User manual Air Conditioner 6
13 Toshiba CARRIER RAV-SP240UT-UL User manual Air Conditioner 3
14 Toshiba CARRIER RAV-SP300CT-UL User manual Air Conditioner 3
15 Toshiba CARRIER RAV-SP360AT2-UL User manual Air Conditioner 3
16 Sony SU-PW2 User manual Air Conditioner 12
17 Sony CV-P12PX User manual Air Conditioner 3
18 Sony MULTI CHANNEL AV RECEIVER STR-DG710 User manual Air Conditioner 31
19 Sony VGN-BX500 User manual Air Conditioner 1
20 Philips 190S5 User manual Air Conditioner 21