Summary of the content on the page No. 1
HART XL
INSTALLATION
OPERATION &
COMMISSIONING
MANUAL
MANUAL NO. TM0042
Summary of the content on the page No. 2
Installation, Operation and Maintenance Manual FOREWORD This manual is intended to clearly and accurately reflect the High-Sensitivity Smoke Detector system with the Modular Control Equipment. This manual is to be used by trained distributors only. This publication describes the installation, operation and maintenance for the High-Sensitivity Smoke Detector system. TERMS AND ABBREVIATIONS AC/a.c.- Alternating Current AH Amperes per Hour CPU- Central Processing Unit DC/d.c.- Direct Current DIA-
Summary of the content on the page No. 3
Installation, Operation and Maintenance Manual TABLE OF CONTENTS Para Page 1 INTRODUCTION ........................................................................................................................ 1-1 1.1 Features ................................................................................................................................ 1-1 2 SYSTEM FUNCTIONAL DESCRIPTION ................................................................................... 2-1 2.1 General........
Summary of the content on the page No. 4
Installation, Operation and Maintenance Manual TABLE OF CONTENTS (Continued) Para Page 5 SYSTEM DESIGN ......................................................................................................................5-1 5.1 Introduction ............................................................................................................................5-1 5.2 Selecting the Correct Detector...............................................................................................5
Summary of the content on the page No. 5
Installation, Operation and Maintenance Manual TABLE OF CONTENTS (Continued) Para Page 7 ROUTINE MAINTENANCE ........................................................................................................7-1 7.1 Introduction............................................................................................................................7-1 7.2 Scheduled Maintenance........................................................................................................7-1 7.3 Ma
Summary of the content on the page No. 6
Installation, Operation and Maintenance Manual LIST OF ILLUSTRATIONS (continued) Figure Page 5.1 Anemometer................................................................................................................................5-3 5.2 Return Air Grill Sampling Method .............................................................................................5-12 5.3 Mini Sample Point Kit.....................................................................................................
Summary of the content on the page No. 7
Installation, Operation and Maintenance Manual SAFETY SUMMARY Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: Several different sources of power can be connected to this High Sensitivity Smoke Detection system. - Disconnect all sources of power before servicing. The High Sensitivity Smoke Detector (HSSD) system and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables wh
Summary of the content on the page No. 8
Summary of the content on the page No. 9
Installation, Operation and Maintenance Manual 1 INTRODUCTION This manual contains operation, installation, maintenance, trouble shooting and parts list information for the High Sensitivity Smoke Detection (HSSD) system. The HSSD system is designed to provide high sensitivity smoke detection for an area up to 2000 sq/m (20,000 sq/ft). Detection of smoke is achieved by using a fan to draw air from the protected area through sampling pipe network back to a Detector. The Detector will analyse the
Summary of the content on the page No. 10
Installation, Operation and Maintenance Manual Table 1.1 Detector Technical Specification DESCRIPTION SPECIFICATION Weight 3.4 kg (7.5 lbs) Finish Polycarbonate Light Grey Material Input Voltage 18 to 30 V DC (24 V DC nominal) Standard Detector Ultra Detector Detector Sensitivity Range 0.005%/m to 1%/m 0.001%/m to 0.1%/m (0.0015% to 0.3%/ft) (0.0003% to 0.03%/ft) Stand Alone With Display Module Input Current (With Standard Head) 315 mA 345/445 mA * Input Current (With Ultra Head) 395 mA 425/525
Summary of the content on the page No. 11
Installation, Operation and Maintenance Manual Figure 1.1 Detector Issue 1 Page 1-3 February 2001
Summary of the content on the page No. 12
Installation, Operation and Maintenance Manual This Page Intentionally Left Blank Page 1-4 Issue 1 February 2001
Summary of the content on the page No. 13
Installation, Operation and Maintenance Manual 2 SYSTEM FUNCTIONAL DESCRIPTION 2.1 General The following paragraphs provide a functional description of the overall operation of the system, as well as functional descriptions of the major components that together make up the High Sensitivity Smoke Detection (HSSD) system. 2.2 Overall Functional Description The High Sensitivity Smoke Detection system comprises a number of major components. Figures 2.1 to 2.2, show how these components are intercon
Summary of the content on the page No. 14
Installation, Operation and Maintenance Manual In addition to the detector, a sampling pipe network is required to carry the sampled air from the protected area to the detector. Overall performance of the High Sensitivity Smoke Detection system is dependent upon the layout of the air sampling pipe network. Use of the “SNIFF” computerised program balances the piping network to provide for an equal intake of air at each sampling hole. For a detailed description on how to design a pipe network r
Summary of the content on the page No. 15
Installation, Operation and Maintenance Manual Figure 2.1 Typical Stand Alone System Issue 1 Page 2-3 February 2001
Summary of the content on the page No. 16
Installation, Operation and Maintenance Manual Figure 2.2 Typical System with Stand Alone Intelligent Interface Module Page 2-4 Issue 1 February 2001
Summary of the content on the page No. 17
Installation, Operation and Maintenance Manual 2.3 Detector The Detector consists of a backbox with a removable cover, incorporated within the Detector are a detector head, termination board and a fan. These three items are the major elements of the Detector, refer to Figure 2.3 detailing the detector block diagram. The design of the Detector allows surface mounting, thus providing ease of installation and maintenance. Replacement of any of the detector’s main elements can be achieved without
Summary of the content on the page No. 18
Installation, Operation and Maintenance Manual Figure 2.3 Detector Block Diagram Page 2-6 Issue 1 February 2001
Summary of the content on the page No. 19
Installation, Operation and Maintenance Manual 2.3.1 Detector Head Located within the Detector, the detector head is a highly sensitive detector utilising a laser, focussed to a narrow beam. The laser beam exits a sample chamber into an attached beam dump area which monitors the laser intensity. A receive optics assembly is mounted on the sample chamber with its optical axis normal to the laser beam axis (see Figure 2.4). A particle-size discriminator inhibits the detector from responding to l
Summary of the content on the page No. 20
Installation, Operation and Maintenance Manual Figure 2.4 Detector Head Views Page 2-8 Issue 1 February 2001