Honeywell MS-9600LSE user manual

User manual for the device Honeywell MS-9600LSE

Device: Honeywell MS-9600LSE
Category: Smoke Alarm
Manufacturer: Honeywell
Size: 2.85 MB
Added : 5/24/2014
Number of pages: 208
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Honeywell MS-9600LSE. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Honeywell MS-9600LSE.

For your convenience

If looking through the Honeywell MS-9600LSE user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Honeywell MS-9600LSE on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Honeywell MS-9600LSE to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Honeywell MS-9600LSE User manual - Online PDF
Advertisement
« Page 1 of 208 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Honeywell MS-9600LSE but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Honeywell MS-9600LSE. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 3

Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be Like all solid state electronic devices, this system may connected to the fire alarm control panel. Disconnect all operate erratically or can be damaged when subjected to light- sources of power before servicing. Control unit and associ- ning induced transients. Although no system is completely ated equipment may be damaged

Summary of the content on the page No. 4

Software Downloads In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for

Summary of the content on the page No. 5

Table of Contents Section 1: Product Description .............................................................................................13 1.1: Inventory......................................................................................................................................................13 1.2: Features and Options ...................................................................................................................................13 1.3: Specifications.....

Summary of the content on the page No. 6

Table of Contents Section 3: Programming ........................................................................................................ 61 3.1: Programming Data Entry .............................................................................................................................61 3.2: User Programming .......................................................................................................................................62 3.3: Initial Power-up..............

Summary of the content on the page No. 7

Table of Contents Section 4: Operating Instructions .......................................................................................150 4.1: Panel Control Buttons................................................................................................................................150 4.1.1: Acknowledge/Step...........................................................................................................................150 4.1.2: Alarm Silence ............................

Summary of the content on the page No. 8

Table of Contents 5.4.2: Selecting and Locating Batteries .....................................................................................................177 Appendix A: Software Zones............................................................................................... 178 A.1: Correlations...............................................................................................................................................178 Appendix B: Default Programming ...............

Summary of the content on the page No. 9

It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies: • Underwriters Laboratories Standards • NFPA 72 National Fire Alarm Code • CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems Before proceeding, the installer should be familiar with the following documents. NFPA Standards NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Cod

Summary of the content on the page No. 10

10 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010 Notification Appliance Circuits Special Application Power Basic System Connections Power-limited, supervised circuits NAC #1 & #2 Sytle Z (Class A) 3.0 amps max per circuit EIA-232 to printer or JP8 configured for Class A personal computer using NACKEY card Special Application Power Power-limited (See Style Y illustrated 13 12 11 10 9 8 7 6 5 4 3 2 1 2 Programmable Relays & DC Power Outputs (24 VDC) for EDP-listed equipment 25

Summary of the content on the page No. 11

Peripheral Devices and Their Documents: Audio Control for ACC-25/50(ZS/T) Audio-Command-Center Doc. #51889 ANN-(R)LED ANN-I/O LED Display ANN-80 ANN-S/PG LED Driver Doc. #53032 Text Annunciator ANN-RLY Printer Driver Doc. #151416 Doc. #52749 Form-C Relay Card Doc. #151417 Doc. #53033 IPDACT ANN (EIA-485) TB6 Internet Communicator Doc. # 53109 DACT-UD2 Communicator J2 Connector Doc. # 53037 4XTMF Reverse Polarity module J10, J11 Connectors SLC Loop Addressable Devices and SLC Wiring Doc.

Summary of the content on the page No. 12

Notes 12 MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Summary of the content on the page No. 13

Section 1: Product Description The MS-9600LS and MS-9600UDLS are compact, cost effective, intelligent addressable FACPs (Fire Alarm Control Panels) with an extensive list of powerful features. The combination of Fire•Lite’s newer series devices and legacy 300 Series devices, along with the MS-9600LS or MS- 9600UDLS FACP, offer the latest in fire protection technology. The FLPS-7 power supply is a sep- arate board while all other electronics are contained on a single main circuit board. Both

Summary of the content on the page No. 14

Product Description Features and Options • Optional module for adding a second SLC loop which meets NFPA Style 4, 6 and 7 requirements • 318 addressable device capacity for each SLC loop (159 detectors and 159 control/monitor modules) • 99 software zones • Up to four onboard NACs (Notification Appliance Circuits): four Style Y (Class B) or two Style Z (Class A) • Additional NAC capability using control modules • 7.0 amps total power for NACs and 24 VDC auxiliary power outputs in alarm • Two pr

Summary of the content on the page No. 15

Specifications Product Description • Auto-program (learn mode) reduces installation time. Reports two devices set to the same address • Password and key-protected nonvolatile memory • User programmable password • Fully programmable from local keypad or keyboard or local PC • Compatible with Fire•Lite’s newer series addressable devices (LiteSpeed and CLIP Mode) - Refer to SLC Wiring Manual for listing of all compatible addressable devices • Compatible with legacy Fire•Lite’s 300 Series devices

Summary of the content on the page No. 16

Product Description Specifications Maximum signaling current per circuit: 3.00 amps (see Figure 1.1 on page 17) End-of-Line Resistor: 4.7 k , ½ watt (P/N 71252 UL listed) for NACs Refer to Device Compatibility Document for listed compatible devices Two Programmable and One Fixed Output Relay - TB1 & TB5 Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive) Form-C relays Refer to Figure 2.5 on page 47 for information on power-limited wiring for relay circuits Four-Wire Res

Summary of the content on the page No. 17

Controls and Indicators Product Description 1.3.1 Current Availability The following figure illustrates the maximum current that is possible for each panel circuit and the total current available from the FACP power supply. TB3 Resettable Special 1.5 amps max Application Power per circuit for 4-wire smoke detectors Resettable Special Standby 1.5 amps max Application Power 1.5 Amps Max* per circuit Power #1 per panel Resettable Special 1.5 amps max Application Power per circuit Power #2 Alarm

Summary of the content on the page No. 18

Product Description Circuits • Maintenance/presignal (yellow) • Alarm Silenced signals (yellow) • Disabled (yellow) • Battery fault (yellow) • Ground fault (yellow) Key Panel Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad. Function keys: • Acknowledge/Step • Alarm Silence • Dril

Summary of the content on the page No. 19

Components Product Description NAC (Notification Appliance Circuits) Up to four NACs are provided with various programmable features: • four Style Y (Class B) NACs OR • two Style Z (Class A) NACs Relays One fixed and two fully programmable Form-C dry contact relays are provided. The fixed fail-safe relay monitors system trouble and the two programmable relays are factory default programmed for system alarm and system supervisory. Contacts are rated 2.0 amps @ 30 VDC (resisti

Summary of the content on the page No. 20

Product Description Components the BB-26 can be used for housing the batteries. The CHG-120F can be used for charging 26 to 120 AH batteries and the BB-55F can be used for housing the batteries. Batteries must be ordered sep- arately. 1.6.1 Intelligent Addressable Detectors: Newer Series Intelligent, addressable detectors provide information to the control panel on an SLC Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on device installation, wir- ing and oper

Summary of the content on the page No. 1

Addressable Fire Alarm Control Panel
MS-9600LS/MS-9600LSE
MS-9600UDLS/MS-9600UDLSE
MS-9600LSC
Manual
Document 52646
2/12/2010 Rev:B2
P/N 52646:B2 ECN 10-098

Summary of the content on the page No. 2

Fire Alarm System Limitations While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance! An automatic fire alarm system—typically made up of Heat detectors do not sense particles of combustion and smoke detectors, heat detectors, manual pull stations, audible alarm only when heat on their sensors increases at a predeter- warning devices, and a fire alarm control panel with remote mined rate or reaches a predetermined level. Rate-of-rise notification capabi


Alternative user manuals
# User manual Category Download
1 Honeywell DUCT-MOUNT AND OUTDOOR-MOUNT H7625B User manual Smoke Alarm 11
2 Honeywell DUCT-MOUNT AND OUTDOOR-MOUNT H7635B User manual Smoke Alarm 3
3 Honeywell DUCT-MOUNT AND OUTDOOR-MOUNT H7655B User manual Smoke Alarm 3
4 Honeywell DUCT-MOUNT AND OUTDOOR-MOUNT H7635C User manual Smoke Alarm 6
5 Honeywell 25/50ZS User manual Smoke Alarm 12
6 Honeywell 25/50ZST User manual Smoke Alarm 1
7 Honeywell EXCEL ADT-HRSI User manual Smoke Alarm 7
8 Honeywell ANN-RLY User manual Smoke Alarm 2
9 Honeywell 50ZST User manual Smoke Alarm 0
10 Honeywell C User manual Smoke Alarm 1
11 Honeywell C7015A User manual Smoke Alarm 14
12 Honeywell C7021F User manual Smoke Alarm 0
13 Honeywell C7021B User manual Smoke Alarm 1
14 Honeywell C7021D User manual Smoke Alarm 1
15 Honeywell C7021K User manual Smoke Alarm 0
16 Adobe CS3 User manual Smoke Alarm 1
17 ADT Security Services ADT-LCD40 User manual Smoke Alarm 6
18 ADT Security Services Safewatch Pro 2000 User manual Smoke Alarm 5
19 ADT Security Services SAVS20ADT-1 User manual Smoke Alarm 3
20 ADT Security Services Unimode 9600 User manual Smoke Alarm 7