Honeywell IPGSM-4GC user manual

User manual for the device Honeywell IPGSM-4GC

Device: Honeywell IPGSM-4GC
Category: Smoke Alarm
Manufacturer: Honeywell
Size: 0.86 MB
Added : 9/25/2013
Number of pages: 24
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Honeywell IPGSM-4GC. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Honeywell IPGSM-4GC.

For your convenience

If looking through the Honeywell IPGSM-4GC user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Honeywell IPGSM-4GC on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Honeywell IPGSM-4GC to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Honeywell IPGSM-4GC User manual - Online PDF
Advertisement
« Page 1 of 24 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Honeywell IPGSM-4GC but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Honeywell IPGSM-4GC. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

LOW BATT
AC LOSS
AC ON
IPGSM-4GC Commercial Fire Communicator
RADIO TROUBLE


IPGSM-4GC
IPGSM-4GC
Commercial Fire Communicator
Commercial Fire Communicator


up Guide
IIn ns stta alllla attiio on n a an nd d S Se ettup Guide









800-12458 7/12 Rev. C

Summary of the content on the page No. 2

Contents General Information ..................................................................................................................... 1 Package Contents ..................................................................................................................... 1 Compatible Fire Panels.............................................................................................................. 1 Operation ...............................................................

Summary of the content on the page No. 3

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide General Information The IPGSM-4GC Commercial Fire Communicator (henceforth referred to as IPGSM-4GC) includes everything you need to upgrade a commercial fire system that previously reported by POTS to a system that uses the Internet as its primary reporting path, and uses a GSM cellular reporting path as a backup. In addition, the communicator’s power module (PowerBoost1) monitors and reports AC power loss, and low ba

Summary of the content on the page No. 4

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide STEP 1 – Setup the Customer Account The communicator requires a subscriber account (customer account) to be setup with AlarmNet Direct. This is accomplished by registering the communicator with AlarmNet. Registering, enables the fire panel to send reports. To setup the customer account you will need to contact the central monitoring station to get account information, and have access to the AlarmNet Direct website. T

Summary of the content on the page No. 5

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide 3. Temporarily wire the battery's negative [–] terminal to TB1–4 on the communicator, then wire the battery's plus [+] terminal to TB1–2 on the communicator. Wait about one minute for the communicator to initialize. 4. Position the assembly near a suitable mounting position and observe the RSSI display. 5. Look for a mounting position that yields at least 3 bars lit solid. For optimal performance 4 or 5 bars are bet

Summary of the content on the page No. 6

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide 11. Verify the PowerBoost1 DIP switches are configured as shown below. PowerBoost1 ON 15 2 3 4 ON (Switch handle = white) 15 2 3 4 12. Ensure the following:  LED Display board is fully seated.  All wiring terminals and connectors are tight.  All wiring has been completed and secured with cable ties. 13. Install the battery (not supplied). Apply power to the 1451-UL9 Wired Transformer, and attach the battery

Summary of the content on the page No. 7

Data Out IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide ANTENNA 1451-UL9 WIRED WIRES MUST BE TRANSFORMER RUN IN CONDUIT TO 24 HR NUT, BLU FACILITY POWER WASHER BLU 120VAC, 60Hz, 850mA 18 VAC GND 72 VA POST ANTENNA MOUNTING TO Cabinet Ground Post GND ADAPTER BLU TO PowerBoost1 BLU DO NOT REMOVE these knockouts. CABINET DOOR ON 15 2 3 4 RED GREEN Dialer Capture Module BATTERY TO Facility Ground TB 1 1 2 FUSE 3 4 PN: 100-02415 5 6 + 7 8 9 10 11 CONDUIT BATTERY 7AH (n

Summary of the content on the page No. 8

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide Wiring the 659EN Line Fault Monitor (Required for ULC) The IPGSM-4GC is compatible with Fire Panels when the model 659EN Line Fault Monitor, (also known as the HFS- 659EN), is installed. Note, the wire colors may vary. 1. Refer to the installation guide for the 659EN. 2. Mount the 659EN on the lower left side of the IPGSM-4GC cabinet. 3. DO NOT cut the 659EN’s BLACK Output Relay Jumper or the BLUE Voltage Trip Threshol

Summary of the content on the page No. 9

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide STEP 5 – Program the Communicator You must use the 7720P Programming tool to program the IPGSM-4GC. When using the 7720P Programming tool, the values given below are for most installations. Press the [#] key to accept the displayed default value (xxx) or enter the new value and press the [#] key for the next prompt. Use the [Space] key to scroll through a list of options. 1. (no display) Connect the 7720P. (Y

Summary of the content on the page No. 10

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide To exit the programming mode, press [N] in response to the "Review?" prompt. Then press [Y] to the "Exit Prog Mode?" prompt. Upon exiting, the root file is updated to log the changes made. A message is displayed telling the user that this step is being executed. When complete, the message "DONE" is displayed to indicate the file was successfully uploaded. Note: If critical configuration changes were made, such as th

Summary of the content on the page No. 11

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide Dialer Capture Module Information LED Indicator STATUS RED – Steady ON Messages exist in buffer. RED – Flashing No messages to be sent. Waiting for messages. GREEN – Steady ON Normal Indication. GREEN – Blinks every 2 sec. PowerBoost1 communication problem. GREEN – Blinks twice every sec. Connection with the Communicator is lost. GREEN – Blinks 10 times every sec. PowerBoost1 and Communicator connections are lost.

Summary of the content on the page No. 12

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide PowerBoost1 Information LED Indicator STATUS AC (green) AC power available. ACTIVE (green) Cyclical flashing – normal communications. Repetition of 3 flashes – loss of communications. LOW BATT (yellow) Missing or low battery. TROUBLE (yellow) One or more trouble conditions exist, such as; overload, output supervision, ground fault, or charger failure. Notes:  If AC power is lost and the battery voltage fa

Summary of the content on the page No. 13

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide Communicator Information ON – NOT registered with AlarmNet. Cellular Status LED GRN OFF – Registered with AlarmNet. Voice Session – FAST BLINK – Download session with Compass Short blink every second in progress. Data Session – SLOW BLINK – In unison with yellow LED, 7720P Short blink every 2 seconds registration in progress. Programmer Port Connected to Cell network –

Summary of the content on the page No. 14

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide RF Specifications Frequency Bands 2G GSM/GPRS/EDGE Quad Band, 850/900/1800/1900 MHz 3G/4G UMTS/HSPA+ Band V, Band II Output Power 2G GPRS +33dBm, GMSK modulation EDGE +27dBm, 8-PSK modulation 3G UMTS +24dBm, QPSK modulation WCDMA +24dBm, QPSK modulation 4G HSPA+ +24dBm, 64 QAM modulation WCDMA +24dBm, 64 QAM modulation Central Station Messages Alarm Condition Alarm Code Restore Code Power On / Reset E339

Summary of the content on the page No. 15

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide IPGSM-4GC Trouble Detection Information Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-4GC, and Telco 2 is used by the IPGSM- 4GC to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use Telco 2 to report events if there are no faults in the Communicator. Fault Condition Indication to Fire Panel PowerBoost1 fault Telco 2 is cut. Communicator fault 

Summary of the content on the page No. 16

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide NOTES – 14 –

Summary of the content on the page No. 17

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide NOTES – 15 –

Summary of the content on the page No. 18

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide NOTES – 16 –

Summary of the content on the page No. 19

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide NOTES – 17 –

Summary of the content on the page No. 20

IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide NOTES – 18 –


Alternative user manuals
# User manual Category Download
1 Honeywell DUCT-MOUNT AND OUTDOOR-MOUNT H7625B User manual Smoke Alarm 11
2 Honeywell DUCT-MOUNT AND OUTDOOR-MOUNT H7635B User manual Smoke Alarm 3
3 Honeywell DUCT-MOUNT AND OUTDOOR-MOUNT H7655B User manual Smoke Alarm 3
4 Honeywell DUCT-MOUNT AND OUTDOOR-MOUNT H7635C User manual Smoke Alarm 6
5 Honeywell 25/50ZS User manual Smoke Alarm 12
6 Honeywell 25/50ZST User manual Smoke Alarm 1
7 Honeywell EXCEL ADT-HRSI User manual Smoke Alarm 7
8 Honeywell ANN-RLY User manual Smoke Alarm 2
9 Honeywell 50ZST User manual Smoke Alarm 0
10 Honeywell C User manual Smoke Alarm 1
11 Honeywell C7015A User manual Smoke Alarm 14
12 Honeywell C7021F User manual Smoke Alarm 0
13 Honeywell C7021B User manual Smoke Alarm 1
14 Honeywell C7021D User manual Smoke Alarm 1
15 Honeywell C7021K User manual Smoke Alarm 0
16 Adobe CS3 User manual Smoke Alarm 1
17 ADT Security Services ADT-LCD40 User manual Smoke Alarm 6
18 ADT Security Services Safewatch Pro 2000 User manual Smoke Alarm 5
19 ADT Security Services SAVS20ADT-1 User manual Smoke Alarm 3
20 ADT Security Services Unimode 9600 User manual Smoke Alarm 7