Carrier SINGLE PACKAGE ROOFTOP 48HC user manual

User manual for the device Carrier SINGLE PACKAGE ROOFTOP 48HC

Device: Carrier SINGLE PACKAGE ROOFTOP 48HC
Category: Gas Heater
Manufacturer: Carrier
Size: 8.08 MB
Added : 8/8/2014
Number of pages: 52
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Carrier SINGLE PACKAGE ROOFTOP 48HC. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Carrier SINGLE PACKAGE ROOFTOP 48HC.

For your convenience

If looking through the Carrier SINGLE PACKAGE ROOFTOP 48HC user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Carrier SINGLE PACKAGE ROOFTOP 48HC on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Carrier SINGLE PACKAGE ROOFTOP 48HC to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Carrier SINGLE PACKAGE ROOFTOP 48HC User manual - Online PDF
Advertisement
« Page 1 of 52 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Carrier SINGLE PACKAGE ROOFTOP 48HC but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Carrier SINGLE PACKAGE ROOFTOP 48HC. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

48HC
SinglePackageRooftop
GasHeating/ElectricCoolingUnit
with Puronr(R---410A)Refrigerant
Sizes:17,20,24,28
InstallationInstructions
NOTE: Read the entire instruction manual before starting
the installation
TABLE OF CONTENTS
SAFETY CONSIDERATIONS .................... 2 Units without Thru--Base Connections ......... 22
Field Control Wiring ....................... 22
INSTALLATION ............................... 9
Thermostat ............................... 22
Jobsite Survey ........................

Summary of the content on the page No. 2

Field Connections .......................... 39 ! WARNING Space Temperature (SPT) Sensors ............ 40 Indoor Air Quality (CO )Sensor ............. 40 FIRE, EXPLOSION HAZARD 2 Outdoor Air Quality Sensor ................. 41 Failure to follow this warning could result in personal injury or death. Space Relative Humidity Sensor or Humidistat .. 41 Disconnect gas piping from unit when leak testing at Smoke Detector/Fire Shutdown (FSD) ......... 42 pressure greater than 0.5 psig (3450 Pa). Pressu

Summary of the content on the page No. 3

C10896 Fig. 1 -- Unit Dimensional Drawing – 17 Size Unit 3 48HC

Summary of the content on the page No. 4

C10897 Fig. 1 -- Unit Dimensional Drawing – 17 Size Unit (cont.) 4 48HC

Summary of the content on the page No. 5

C10892 Fig. 2 -- Unit Dimensional Drawing – 20 and 24 Size Units 5 48HC

Summary of the content on the page No. 6

C10893 Fig. 2 -- Unit Dimensional Drawing – 20 and 24 Size Units (cont.) 6 48HC

Summary of the content on the page No. 7

C10900 Fig. 3 -- Unit Dimensional Drawing – 28 Size Unit 7 48HC

Summary of the content on the page No. 8

C10901 Fig. 3 -- Unit Dimensional Drawing – 28 Size Unit (cont.) 8 48HC

Summary of the content on the page No. 9

INSTALLATION Jobsite Survey Be sure that the unit is installed such that snow will not block the combustion air intake or flute outlet. Complete the following checks before installation. Unit may be installed directly on wood flooring or on Class 1. Consult local building codes and the NEC (National A, B, or C roof- -covering material when roof curb is used. Electrical Code) ANSI/NFPA 70 for special installa- tion requirements. Do not install unit in an indoor location. Do not locate air 2. Dete

Summary of the content on the page No. 10

NOTE: The gasketing of the unit to the roof curb is critical Step 2 — Plan for Sequence of Unit Installation for a watertight seal. Install gasket supplied with the roof The support method used for this unit will dictate different curb as shown in Figs. 6, 7 and 8. Improperly applied gasket sequences for the steps of unit installation. For example, on can also result in air leaks and poor unit performance. curb- -mounted units, some accessories must be installed on the unit before the unit is pl

Summary of the content on the page No. 11

C10954 Fig. 6 -- Roof Curb Details – 17 Size Unit 11 48HC

Summary of the content on the page No. 12

C10955 Fig. 7 -- Roof Curb Details – 20 and 24 Size Units 12 48HC

Summary of the content on the page No. 13

C10956 Fig. 8 -- Roof Curb Details – 28 Size Unit 13 48HC

Summary of the content on the page No. 14

A minimum clearance is not required around ductwork. ! CAUTION C PROPERTY DAMAGE HAZARD Failure to follow this caution may result in damage to roofing materials. MAXIMUM ALLOWABLE A DIFFERENCE IN. (MM) Membrane roofs can be cut by sharp sheet metal B A-B B-C A-C edges. Be careful when placing any sheet metal parts 0.25” (6) 0.5” (12) 0.5” (12) on such roof. C10628 Fig. 9 -- Unit Leveling Tolerances Step 6 — Rig and Place Unit Step 5 — Field Fabricate Ductwork Keep unit upright and do not drop. S

Summary of the content on the page No. 15

(3 Positioning onCurb— Field- -supplied / - -inch) flanges should be attached to 4 horizontal duct openings (see Fig. 11) and all ductwork Position unit on roof curb so that the following clearances should be secured to the flanges. Insulate and weatherproof 1 are maintained: / in. (6 mm) clearance between the roof 4 all external ductwork, joints, and roof or building openings 1 curb and the base rail inside the right and left, / in. 2 with counter flashing and mastic in accordance with (12 mm)

Summary of the content on the page No. 16

To assemble the outside air hood: The combustion air hood is attached to the back of the burner access panel. Remove the two screws securing the 1. Remove hood top panel from shipping position on hood to the back of the burner access panel. Using the two unit end. screws, re--attach the hood to the front of the burner 2. Install four angles to the upper end panel using the access panel as shown in Fig. 16. screws provided. 3. Apply seal strip to mating flanges on the side plates of the hood (see

Summary of the content on the page No. 17

3 Table 2 – Typical / - -in NPT Field Supplied Piping Parts 4 4 5 3 2 6 1 Item Qty CPN Description 1 1 CA15RA201 90Deg StreetElbow 2 1 CA01CA226 5InchLong Nipple 7 3 1 CA85RA201 Ground---JointUnion 15 4 1 CA01CA218 3InchLong Nipple 8 5 1 CA05RA201 90Deg Elbow 9 6 1 CA01CA250 12InchLong Nipple 7 1 CA05RA201 90Deg Elbow 10 8 1 CA01CA218 3InchLong Nipple 11 9 1 CA20RA201 TEE 12 13 10 1 CA01CN222 4InchLong Nipple(SedimentTrap) 14 11 1 CA38RA201 Cap 1 12 1 CA01CA220 3 / InchLong Nipple 2 R 13 1 GB30

Summary of the content on the page No. 18

Factory--Option Thru--Base Connections — NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply Electrical Connections: Knockouts are located in the piping must be disconnected from the gas valve during the control box area. Remove the appropriate size knockout testing of the piping systems when test pressure is in for high voltage connection. Use the field supplied excess of 0.5 psig (3450 Pa). Pressure test the gas supply connector depen

Summary of the content on the page No. 19

Step 11 — Install External Condensate Trap and Step 12 — Make Electrical Connections Line ! 3 WARNING The unit has one / -in. condensate drain connection on 4 the end of the condensate pan (see Fig. 21). See Figs. 1, 2 ELECTRICAL SHOCK HAZARD and 3, item “E”, in the view labeled “BACK Failure to follow this warning could result in personal (HORIZONTAL DISCHARGE)” for the location of the injury or death. condensate drain connection. Do not use gas piping as an electrical ground. Unit cabinet must

Summary of the content on the page No. 20

! ! CAUTION WARNING FIRE HAZARD UNIT DAMAGE HAZARD Failure to follow this warning could result in Failure to follow this caution may result in equipment intermittent operation or unsatisfactory performance. damage. Do not connect aluminum wire between disconnect Operation on improper line voltage or excessive phase switch and air conditioning unit. Use only copper imbalance constitutes abuse and may cause damage to wire.(SeeFig.24.) electrical components. Such operation would invalidate any appl


Alternative user manuals
# User manual Category Download
1 Carrier 48SX User manual Gas Heater 10
2 Carrier 48SX024-060 User manual Gas Heater 2
3 Carrier 48TJ016-028 User manual Gas Heater 12
4 Carrier 48GX User manual Gas Heater 3
5 Carrier 48PG16 User manual Gas Heater 1
6 Carrier 58GP User manual Gas Heater 7
7 Carrier COMFORTLINK 48P2 User manual Gas Heater 3
8 Carrier 58DRC User manual Gas Heater 1
9 Carrier 48SS User manual Gas Heater 8
10 Carrier COMFORTLINK P3 User manual Gas Heater 38
11 Carrier COMFORTLINK P5030-100 User manual Gas Heater 0
12 Carrier COMFORTLINK P4 User manual Gas Heater 3
13 Carrier 58GSC User manual Gas Heater 2
14 Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48EJ User manual Gas Heater 2
15 Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING EK User manual Gas Heater 1
16 Allied Air Enterprises 506271-01 User manual Gas Heater 0
17 Blue Rhino ALL WEATHER WOVEN HEATER GWU9850F / 35554 User manual Gas Heater 2
18 Breckwell ECONOMY P22FSL User manual Gas Heater 0
19 Breckwell ECONOMY P22FSA User manual Gas Heater 0
20 Breckwell ECONOMY P22I User manual Gas Heater 1