Summary of the content on the page No. 1
PACKAGE AIR CONDITIONERS
FORM NO. S11-933 REV. 2
Supersedes Form No. S11-933 Rev. 1
RSNA-B SUPER HIGH EFFICIENCY 13-SEER SERIES
NOMINAL SIZES 2-5 TONS [7.0-17.6 kW]
Summary of the content on the page No. 2
TABLE OF CONTENTS Unit Features & Benefits ..............................................................................3-4 Model Identification Options ..........................................................................5-6 General Data RSNA-B Series ........................................................................................7-9 General Data Notes ......................................................................................10 Performance Data RSNA-B Series ..........
Summary of the content on the page No. 3
UNIT FEATURES & BENEFITS—RSNA-B These quality features are included in the Rheem Package Air Conditioner 5 3
Summary of the content on the page No. 4
UNIT FEATURES & BENEFITS—RSNA-B SERIES [ ] Designates Metric Conversions Features Below Correspond to Photos on Page 3 ® ® 1. All models feature Copeland Scroll compressors for maxi- 8. Refrigerant connections are conveniently located for easy mum efficiency and quiet operation. service diagnostics. 2. Louvered condenser compartment for protecting the coil 9. Condenser and evaporator coils feature enhanced fins against yard hazards and/or weather extremes. for better heat transfer and rifled co
Summary of the content on the page No. 5
MODEL IDENTIFICATION—RSNA-B SERIES R S N A — B 036 J K 010 X X Factory Installed Options (See Next Page) Heating Capacity (Factory Installed) 000 = No Resistance Heat 005 = 05 KW Resistance Heat (018-030) 010 = 10 KW Resistance Heat (024-048) 015 = 15 KW Resistance Heat (036-048) Drive Package K = Direct Drive Electrical Designation J = 208-230V—1PH—60 Hz C= 208-230V—3PH—60 Hz Cooling Capacity (BTUH) [kW] 024 = 24,000 [7.03] 030 = 30,000 [8.79] 036 = 36,000 [10.55] 042 = 42,000 [12.31] 048 = 48
Summary of the content on the page No. 6
OPTIONS—RSNA-B SERIES Instructions for Factory Installed Option(s) Selection Note: Two characters following the model number will be utilized to designate a factory-installed option or com- bination of options. If no factory option(s) is required, nothing follows the model number. Step 1. After a basic rooftop model is selected, choose a two-character option code from the FACTORY INSTALLED OPTION SELECTION TABLE. FACTORY INSTALLED OPTION CODES Option Side Flow Code AA No Option AK x Example: RSN
Summary of the content on the page No. 7
GENERAL DATA—RSNA-B SERIES NOMINAL SIZES 2-5 TONS [7.0-17.6 kW] Model RSNA-B Series B024JK B030JK B036CK B036JK 1 Cooling Performance CONTINUED Gross Cooling Capacity Btu [kW] 24,800 [7.27] 31,200 [9.14] 37,400 [10.96] 37,400 [10.96] 2 EER/SEER 11.8/13 11.1/13 11.7/13 11.7/13 Nominal CFM/ARI Rated CFM [L/s] 800/800 [378/378] 1000/1000 [472/472] 1200/1200 [566/566] 1200/1200 [566/566] ARI Net Cooling Capacity Btu [kW] 24,000 [7.03] 30,000 [8.79] 36,000 [10.55] 36,000 [10.55] Net Sensible Capacity
Summary of the content on the page No. 8
GENERAL DATA—RSNA-B SERIES NOMINAL SIZES 2-5 TONS [7.0-17.6 kW] Model RSNA-B Series B042CK B042JK B048CK B048JK 1 CONTINUED Cooling Performance Gross Cooling Capacity Btu [kW] 42,500 [12.45] 42,500 [12.45] 50,500 [14.8] 50,500 [14.8] 2 EER/SEER 11.5/13 11.5/13 11.6/13 11.6/13 Nominal CFM/ARI Rated CFM [L/s] 1400/1350 [661/637] 1400/1350 [661/637] 1600/1600 [755/755] 1600/1600 [755/755] ARI Net Cooling Capacity Btu [kW] 41,000 [12.01] 41,000 [12.01] 48,500 [14.21] 48,500 [14.21] Net Sensible Capa
Summary of the content on the page No. 9
GENERAL DATA—RSNA-B SERIES NOMINAL SIZES 2-5 TONS [7.0-17.6 kW] Model RSNA-B Series B060CK B060JK 1 Cooling Performance Gross Cooling Capacity Btu [kW] 60,000 [17.58] 60,000 [17.58] 2 EER/SEER 11.1/13 11.1/13 Nominal CFM/ARI Rated CFM [L/s] 2000/1850 [897/873] 2000/1850 [897/873] ARI Net Cooling Capacity Btu [kW] 58,000 [16.99] 58,000 [16.99] Net Sensible Capacity Btu [kW] 40,561 [11.88] 40,561 [11.88] Net Latent Capacity Btu [kW] 17,439 [5.11] 17,439 [5.11] Net System Power kW 5.2 5.2 Compresso
Summary of the content on the page No. 10
GENERAL DATA—RSNA-B SERIES NOTES: 1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360. 2. EER and/or SEER are rated at ARI c
Summary of the content on the page No. 11
SYSTEMS PERFORMANCE—RSNA-B SERIES GROSS SYSTEMS PERFORMANCE DATA—RSNA-B024 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 880 [415] 800 [378] 680 [321] 880 [415] 800 [378] 680 [321] 880 [415] 800 [378] 680 [321] DR ➀ .21 .20 .18 .21 .20 .18 .21 .20 .18 Total BTUH [kW] 28.9 [8.47] 28.4 [8.32] 27.6 [8.09] 27.3 [8.00] 26.8 [7.85] 26.1 [7.65] 25.0 [7.33] 24.6 [7.21] 23.9 [7.00] 75 Sens BTUH [kW] 16.2 [4.75] 15.4 [4.51] 14.4 [4.22] 19.5 [5.71] 18.6 [
Summary of the content on the page No. 12
SYSTEMS PERFORMANCE—RSNA-B SERIES GROSS SYSTEMS PERFORMANCE DATA—RSNA-B036 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 1320 [623] 1200 [566] 1020 [481] 1320 [623] 1200 [566] 1020 [481] 1320 [623] 1200 [566] 1020 [481] DR ➀ .21 .20 .17 .21 .20 .17 .21 .20 .17 Total BTUH [kW] 44.4 [13.01] 43.6 [12.78] 42.4 [12.43] 41.3 [12.10] 40.6 [11.90] 39.5 [11.58] 39.6 [11.61] 38.9 [11.40] 37.8 [11.08] 75 Sens BTUH [kW] 25.5 [7.47] 24.4 [7.15] 22.7 [
Summary of the content on the page No. 13
SYSTEMS PERFORMANCE—RSNA-B SERIES GROSS SYSTEMS PERFORMANCE DATA—RSNA-B048 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 1760 [831] 1600 [755] 1360 [642] 1760 [831] 1600 [755] 1360 [642] 1760 [831] 1600 [755] 1360 [642] DR ➀ .20 .19 .17 .20 .19 .17 .20 .19 .17 Total BTUH [kW] 60.8 [17.82] 59.7 [17.50] 58.1 [17.03] 56.4 [16.53] 55.4 [16.24] 53.9 [15.80] 53.1 [15.56] 52.2 [15.30] 50.8 [14.89] 75 Sens BTUH [kW] 36.3 [10.64] 34.7 [10.17] 32.3 [9.
Summary of the content on the page No. 14
AIRFLOW PERFORMANCE—RSNA-B SERIES 14 INDOOR AIRFLOW PERFORMANCE—208 VOLTS CFM [L/s] Air Delivery/RPM/Watts—208 Volts Motor Speed Nominal Blower Size/ Side Discharge—Wet Coil from Cooling Motor Motor Factory External Static Pressure—Inches W.C. [kPa] Capacity HP [W] & Speed Tons [kW] # of Speeds Cool Heat 0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] CFM 675 [319] 657 [310] 634 [299] 602 [284] 560 [264] 505 [238] 435 [205] High Low Low RPM 695 785 870 905 940 980 1020 9x7
Summary of the content on the page No. 15
AIRFLOW PERFORMANCE—RSNA-B SERIES 15 INDOOR AIRFLOW PERFORMANCE—230 VOLTS CFM [L/s] Air Delivery/RPM/Watts—230 Volts Motor Speed Nominal Blower Size/ Side Discharge—Wet Coil from Cooling Motor Motor Factory External Static Pressure—Inches W.C. [kPa] Capacity HP [W] & Speed Tons [kW] # of Speeds Cool Heat 0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17] CFM 771 [364] 751 [354] 725 [342] 691 [326] 645 [304] 584 [276] 546 [258] High Low Low RPM 825 870 910 950 985 1010 1030 9x7
Summary of the content on the page No. 16
ELECTRICAL DATA—RSNA-B SERIES ELECTRICAL DATA – RSNA-B SERIES -B024JK -B030JK -B036CK -B036JK -B042CK -B042JK -B048CK -B048JK -B060CK -B060JK Unit Operating 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 Voltage Range Minimum Circuit Ampacity 16/16 22/22 16/16 22/22 18/18 26/26 22/22 32/32 33/33 43/43 Minimum Overcurrent 20/20 25/25 20/20 30/30 20/20 30/30 25/25 40/40 40/40 50/50 Protection Device Size Maximum Overcurrent 25/25 35/35 25/25 35/35 25/25 40/40 30/30
Summary of the content on the page No. 17
ELECTRIC HEATER KITS—RSNA-B SERIES 17 208-240 VOLT, SINGLE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION Single Power Supply For Both Unit and Heater Kit Separate Power Supply For Both Unit and Heater Kit Heater Kit Unit Heater Kit Air Conditioner Unit Over Current Over Current Model RXQJ- No. of Rated Heater Heater Unit Min. Ckt. Min. Ckt. Max. Fuse Min. Circuit Protective Device Size Protective Device Size No. of No. Heater Kit Sequence Heater kW KBTU/Hr Amp. Amp
Summary of the content on the page No. 18
UNIT DIMENSIONS—RSNA-B SERIES UNIT DIMENSIONS PACKAGE AIR CONDITIONERS OUTDOOR FAN GRILLE AND COMPRESSOR ACCESS CONTROL FILTER ACCESS ACCESS PANEL PANEL (FOR UNIT MOUNTED FILTER ACCESSORY) 30% 2% LIQUID PRESSURE SERVICE PORT OUTDOOR COIL PROTECTIVE GRILLE TOP COVER 21% 2% SUCTION PRESSURE SERVICE PORT THREADED PVC CONDENSATE DRAIN CONNECTION N.P.T. THERMOSTAT WIRING 29% 2% ENTRANCE IMPORTANT: UNIT MUST BE LEVEL TO PREVENT WATER MIGRATION ELECTRICAL POWER ENTRANCE CORNER WEIGHTS % OF TOTA
Summary of the content on the page No. 19
UNIT DIMENSIONS—RSNA-B SERIES SIDE VIEW SIDE VIEW OUTDOOR COIL PROTECTIVE FILTER ACCESS PANEL (FOR UNIT GRILLE THERMOSTAT MOUNTED FILTER ACCESSORY WIRE ENTRANCE 1 1 /8" [28.6 mm] 5 25 /16" [643 mm] 3 10 /16" [259 mm] 1 5 /16" [129 mm] ELECTRICAL 7 52 /16" POWER ENTRANCE BLOWER/ 3 [1332 mm] 4 /4" EVAPORATOR [121 mm] ACCESS PANEL FRONT VIEW REAR VIEW CONTROL ACCESS PANEL 7 4 /8" SIDE SUPPLY [124 mm] DUCT OPENING 3 LIQUID 13 /4" [349 mm] PRESSURE SERVICE PORT 5 7 /16" 7 [186 mm] 5 /16" [138
Summary of the content on the page No. 20
TYPICAL INSTALLATIONS 20