Siemens pcs 7 user manual

User manual for the device Siemens pcs 7

Device: Siemens pcs 7
Category: Time Clock
Manufacturer: Siemens
Size: 13.47 MB
Added : 2/24/2014
Number of pages: 23
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Siemens pcs 7. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Siemens pcs 7.

For your convenience

If looking through the Siemens pcs 7 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Siemens pcs 7 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Siemens pcs 7 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Siemens pcs 7 User manual - Online PDF
Advertisement
« Page 1 of 23 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Siemens pcs 7 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Siemens pcs 7. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

Deckblatt

Model Predictive Control including
integral transfer functions
SIMATIC PCS 7
Application Example  April 2010
Applikationen & Tools
Answers for industry.

Summary of the content on the page No. 2

Summary of the content on the page No. 3

Industry Automation and Drives Technologies Service & Support Portal This article is taken from the Service Portal of Siemens AG, Industry Automation and Drives Technologies. The following link takes you directly to the download page of this document. http://support.automation.siemens.com/WW/view/en/42200753 If you have any questions concerning this document please e-mail us to the following address: online-support.automation@siemens.com MPC Level V 1.0, Beitrags-ID: 4220075

Summary of the content on the page No. 4

Warranty and Liability Warranty and Liability The Application Examples are not binding and do not claim to be complete Note regarding the circuits shown, equipping and any eventuality. The Application Examples do not represent customer-specific solutions. They are only intended to provide support for typical applications. You are responsible for ensuring that the described products are used correctly. These application examples do not relieve you of the responsibility to use safe pract

Summary of the content on the page No. 5

Table of Contents Table of Contents Warranty and Liability ................................................................................................. 4 1 Preface................................................................................................................ 6 2 Introduction........................................................................................................ 7 2.1 Basic Principles of Model Predictive Control........................................ 7

Summary of the content on the page No. 6

Preface 1 Preface Objective of the Application The area of application of the model predictive controller provided in SIMATIC PCS 7 (function block ModPreCon and MPC respectively) is restricted by the following fact: The control algorithm only works for stable processes with a step response settling to a constant value in a finite time horizon. If the process is not stable or shows an integral action (e.g. level control, position control), the respective sub transfer functions have t

Summary of the content on the page No. 7

Introduction 2 Introduction 2.1 Basic Principles of Model Predictive Control A general overview of model predictive control is provided by the White Paper “How to improve the Performance of your Plant using the appropriate tools of SIMATIC PCS 7 APC-Portfolio?” https://pcs.khe.siemens.com/efiles/pcs7/support/marktstudien/WP_PCS7_APC_EN .pdf The application note including the basic principles of the MPC can be found here: http://cache.automation.siemens.com/dnl/zI/zIzMzM1MwAA_37361208_To

Summary of the content on the page No. 8

Introduction Figure 2-1 Step response of a control loop with compensation (blue) and without compensation (red), i.e. with integral behaviour. S S S S S S St t t t t t tep ep ep ep ep ep ep R R R R R R Res es es es es es espons pons pons pons pons pons ponse e e e e e e 3 3 3 3 3 3 3 whithout whithout com comp pens ensa at ti ion, on, i.e i.e.. with with ohne ohne 2. 2. 2. 2. 2. 2. 2.5 5 5 5 5 5 5 integ integr ra al l Ausglei Ausgleic ch h with with mit mit beh beha aviou viour r c co om

Summary of the content on the page No. 9

Introduction 2.3 Examples of Unstable Control Loops 2.3.1 Level Control If the level of a tank with continuous feed is to be controlled via an adjustable drain as actuator (e.g. pump or valve with or without flow control), the control loop shows integrating behaviour. An equilibrium condition of the level only exists if the drain is exactly equal to the feed. The level permanently decreases until the tank is empty, if the drain is in- creased stepwise starting at this equilibrium conditi

Summary of the content on the page No. 10

Introduction feed water tanks. There are different objectives for level control according to the plant context [also see Related Literature /2./]:  Keep level constant (exactly at the set point) – important for levels directly in- fluencing the process; disturbances are passed through to the output (drain).  Keep level as small as possible – if “dead volume” and inventory are undesir- able.  Keep level inside specified limits while using the tank as buffer – changes in level are tol

Summary of the content on the page No. 11

Introduction 2.3.3 Position Control The control loop shows integrating behaviour if the position of mechanical parts is controlled and the speed of the actuator is available as manipulated variable. An "equilibrium condition" without move in the position only exists for a speed equal to zero. The valve actuator is a common example for position control in process plants. However, the valve position controllers are mostly integrated in the corre- sponding actuators and hence not an issue fo

Summary of the content on the page No. 12

Stabilization of Unstable Control Loops 3 Stabilization of Unstable Control Loops Regarding the stabilization of unstable control loops, integral processes and mono- tone unstable or oscillating unstable processes have to be distinguished. In general only an analysis in frequency domain is helpful for oscillating control loops. As an example, displacements of unstable poles to the stable domain can be examined using root locus analysis [also see Related Literature /3./]. These oscillat

Summary of the content on the page No. 13

Stabilization of Unstable Control Loops k i The behaviour of an integrating process g  s  can be described by i  s t s 1 1 two parameters:  The maximal gradient k of the response to a unit-step (of height one) i  The delay time t needed by the process to reach its maximal gradient after a 1 step in the manipulated variable (intersection point of the tangent with the base line in Figure 3-1) The transfer function of the closed loop including a proportional-only controller k s 

Summary of the content on the page No. 14

Stabilization of Unstable Control Loops 3.2 PID Tuner The PCS 7 PID tuner can be used for integral processes without problems if at least one stable controller parameterization is already available. The following hints are helpful for this:  Fix the check mark „With integral action in the process“  Excite the process with a step in the set point in closed loop in automatic mode  Chose the proportional only controller as controller type, at least, if you want to use this controller

Summary of the content on the page No. 15

Configuration of MPC with Slave Controller 4 Configuration of MPC with Slave Controller 4.1 Starting Point The starting point is the standard connection of the MPC with its actuators. The structure of the following example corresponds to the control of product quality (CV1) and level (CV2) in a reactor as mentioned in section 2.3.4. However, this ex- ample is not a realistic simulation of a real reactor. Figure 4-1 Original signal flow chart of an MPC with 2x2 process, where the main t

Summary of the content on the page No. 16

Configuration of MPC with Slave Controller Figure 4-2 Signal flow chart of MPC with subordinated stabilizing PID controller for the integral main transfer function g22 g11 CV1 g12 MV1 ModPreCon CV2 MV2 . g21 PI CV2 LIC CV2 g22 The slave controller stabilizes the control variable CV1 in general. The integral ef- fect of the main transfer function g22 is compensates as well as the integral effect of the coupling transfer function g21. The influence of MV2 on CV1 is also modified

Summary of the content on the page No. 17

Configuration of MPC with Slave Controller Figure 4-3 Connection of MPC and slave controller MPC Level V 1.0, Beitrags-ID: 42200753 17 Copyright  Siemens AG 2010 All rights reserved

Summary of the content on the page No. 18

Configuration of MPC with Slave Controller 4.3 Commissioning The parameterization of the controller and the commissioning is done „from interior to exterior” as in any cascade control. First the slave controller is tuned (see chap- ter 3) and switched to automatic mode. Afterwards the slave controller is switched to cascade mode and the master controller is parameterized. While tuning the mas- ter controller please consider that the whole inner closed control loop of the slave controlle

Summary of the content on the page No. 19

Simulation Example 5 Simulation Example The simulation example was generated from a copy of the plant section ModPre- Con of the APL_Example_EU, by introducing an additional integral block after the transfer function Proc662. Figure 5-1 Modified process simulation of the example project; the inserted integrator is marked in blue MPC Level V 1.0, Beitrags-ID: 42200753 19 Copyright  Siemens AG 2010 All rights reserved

Summary of the content on the page No. 20

Simulation Example Figure 5-2 OS picture of the example project Despite the interaction between both manipulated variables MV1 and MV2 and the integral action of MV2 on PV2, both control variables PV1 and PV2 of the master controller can be controlled to their given set points independently of each other, which is a success of the described control concept. A “crosstalk” between the in- teracting control loops can mostly be avoided, e.g. the level PV2 (dark green) is only moved min


Alternative user manuals
# User manual Category Download
1 Siemens Module B3 User manual Time Clock 3
2 Acroprint BOSS BP125-6 User manual Time Clock 10
3 Acroprint Green ATR20/20-2 User manual Time Clock 2
4 Acroprint ES1000 User manual Time Clock 5
5 Acroprint BOSS BP125-R6 User manual Time Clock 5
6 Acroprint ES900 User manual Time Clock 389
7 Acroprint ATR-120 User manual Time Clock 24
8 AMD ATHLON K User manual Time Clock 1
9 Acroprint Green ATR20/20-3 User manual Time Clock 0
10 Acroprint Green ATR20/20-4 User manual Time Clock 0
11 Acroprint Green ATR20/20-6 User manual Time Clock 0
12 Aiphone MC-D User manual Time Clock 2
13 Acroprint Green ATR20/20-1 User manual Time Clock 0
14 Acroprint ES700 User manual Time Clock 120
15 Acroprint Green ATR20/20-5 User manual Time Clock 0