Generac Power Systems 14 kW LP user manual

User manual for the device Generac Power Systems 14 kW LP

Device: Generac Power Systems 14 kW LP
Category: Portable Generator
Manufacturer: Generac Power Systems
Size: 19.43 MB
Added : 4/19/2014
Number of pages: 192
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Generac Power Systems 14 kW LP. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Generac Power Systems 14 kW LP.

For your convenience

If looking through the Generac Power Systems 14 kW LP user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Generac Power Systems 14 kW LP on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Generac Power Systems 14 kW LP to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Generac Power Systems 14 kW LP User manual - Online PDF
Advertisement
« Page 1 of 192 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Generac Power Systems 14 kW LP but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Generac Power Systems 14 kW LP. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

diagnostic
repair
manual
air- cooled Product
MODELS:
7 kW NG, 8 kW LP
9 kW NG, 10 kW LP
13 kW NG, 14 kW LP
16 kW NG, 17 kW LP
18 kW NG, 20 kW LP
automatic standby generators

Summary of the content on the page No. 2

ElEctrical formulas TO FIND KNOWN VALUES 1-PHASE 3-PHASE E x I E x I x 1.73 x PF KILOWATTS (kW) Volts, Current, Power Factor 1000 1000 E x I E x I x 1.73 KVA Volts, Current 1000 1000 kW x 1000 kW x 1000 AMPERES kW, Volts, Power Factor E E x 1.73 x PF WATTS Volts, Amps, Power Factor Volts x Amps E x I x 1.73 x PF 2 x 60 x Frequency 2 x 60 x Frequency NO. OF ROTOR POLES Frequency, RPM RPM RPM RPM x Poles RPM x Poles FREQUENCY RPM, No. of Rotor Poles 2 x 60 2 x 60 2 x 60 x Frequency 2 x 60 x Freque

Summary of the content on the page No. 3

contents 1.6 Engine-Generator Protective Devices ............. 25 General ............................................................25 specifications .......................................................... 4 Low Battery ......................................................25 Generator ................................................................ 4 Low Oil Pressure Shutdown .............................25 Engine ..................................................................... 5 High

Summary of the content on the page No. 4

Test 7 – Testing The Stator With A Vom Problem 11 – No Battery Charge (12-20 kW)...........................................44 (Pre-Packed Load Center) ...........................73 Test 8 – Test Brushless Stator..........................45 Problem 12 – No Battery Charge (RTSN & RTSE Transfer Switch) .................73 Test 9 – Check Capacitor .................................46 Problem 13 – No Battery Charge Test 10 – Test DPE Winding on (Gen-Ready Load Center) ...........................73

Summary of the content on the page No. 5

Part 4 - Dc coNtrol ......................................... 95 Test 68 – Check Fuel Solenoid ......................132 4.1 Description and Components .......................... 96 Test 69 – Check Choke Solenoid ...................132 General ............................................................96 Test 70 – Check for Ignition Spark .................134 Terminal Strip / Interconnection Terminal .........96 Test 71 – Check Spark Plugs .........................136 Circuit Board ............

Summary of the content on the page No. 6

sPEcificatioNs Generator Unit 8 kW 10 kW 12 kW 14 kW 16 kW 17 kW 20 kW Rated Max. Continuous 7,000 NG 9,000 NG 12,000 NG 13,000 NG 16,000 NG 16,000 NG 18,000 NG Power Capacity (Watts*) 8,000 LP 10,000 LP 12,000 LP 14,000 LP 16,000 LP 17,000 LP 20,000 LP Rated Voltage 120/240 Rated Voltage at No-Load (NG) 220-235 247-249 Rated Max. Continuous Load Current (Amps) 120 Volts** (NG/LP) 58.3/66.6 75.0/83.3 100.0/100.0 108.3/116.6 133.3/133.3 133.3/141.6 150.0/166.6 240 Volts (NG/LP) 29.2/33.3 37.5/4

Summary of the content on the page No. 7

SpecificationS nginee Model 8 kW 10 kW 12/14/16/17 kW 20 kW Type of Engine GH-410 GT-530 GT-990 GT-999 Number of Cylinders 1 2 2 2 Rated Horsepower @ 3,600 rpm 14.8 18 32 34 Displacement 407cc 530cc 992cc 999cc Cylinder Block Aluminum w/Cast Iron Sleeve Valve Arrangement Overhead Valves Ignition System Solid-state w/Magneto Recommended Spark Plug RC14YC BPR6HS RC14YCA RC12YC Spark Plug Gap 0.76 mm (0.030 inch) 0.76 mm (0.030 inch) 1.02 mm (0.040 inch) 1.02 mm (0.040 inch) Compression Ratio 9.4:1

Summary of the content on the page No. 8

sPEcificatioNs mountinG dimenSionS AIR INTAKE 457.2 299 MINIMUM DISTANCE [18.0] [11.8] 914 [36.0] MINIMUM OPEN AREA 1079.5 ON SIDES AND FRONT [42.5] 698 [27.5] AIR OUTLET AIR INTAKE 997 [39.3] 747 [29.4] 250.0 575.3 207 [9.8] [22.7] 454 [8.2] [17.9] 508 [20.0] TRANSFER Ø30.2 [Ø1.2] LIFTING HOLES 4 CORNERS TRANSFER SWITCH 530.0 SWITCH HOLE LOCATIONS FOR 8KW - 17KW [20.9] OPTIONAL MOUNTING TO 20KW (IF SUPPLIED) A CONCRETE PAD (IF SUPPLIED) 446.6 378.7 44.8 [17.6] [14.9] [1.8] "DO NOT LIFT BY ROO

Summary of the content on the page No. 9

sPEcificatioNs mountinG dimenSionS AIR INTAKE 457.2 299 MINIMUM DISTANCE [18.0] [11.8] 914 [36.0] MINIMUM OPEN AREA 1079.5 ON SIDES AND FRONT [42.5] 698 [27.5] AIR OUTLET AIR INTAKE 997 [39.3] 747 [29.4] 250.0 575.3 207 [9.8] [22.7] 454 [8.2] [17.9] 508 [20.0] TRANSFER Ø30.2 [Ø1.2] LIFTING HOLES 4 CORNERS TRANSFER SWITCH 530.0 SWITCH HOLE LOCATIONS FOR 8KW - 17KW [20.9] OPTIONAL MOUNTING TO 20KW (IF SUPPLIED) A CONCRETE PAD (IF SUPPLIED) 446.6 378.7 44.8 [17.6] [14.9] [1.8] "DO NOT LIFT BY ROO

Summary of the content on the page No. 10

sPEcificatioNs major FeatureS 8kW, Single Cylinder, GH-410 Engine 10kW, V-twin, GT-530 Engine (door removed) (door removed) Circuit Oil Data Label Control Breaker Oil Data Label Control Dipstick (see sample) Panel Dipstick (see sample) Panel Circuit Breaker Exhaust Exhaust Enclosure Enclosure Air Air Filter Filter Fuel Inlet Fuel Inlet (back) (back) Fuel Fuel Regulator Regulator Composite Base Oil Filter Battery Compartment Composite Base Oil Filter Battery Compartment Figure 1.3 – 12, 14, 16,

Summary of the content on the page No. 11

t aBlE of coNtENts Part titlE PaGE 1.1 Generator identification 10 1.2 installation Basics 11 Part 1 1.3 Non-Prepackaged 14 interconnections GENEral 1.3 Preparation Before use 16 1.4 t esting, cleaning and Drying 18 iNformatioN 1.5 Engine-Generator Protective 25 Devices 1.6 operating instructions 27 1.7 automatic operating 29 Parameters air-cooled, a utomatic standby Generators 1.1 Generator Identification ................................... 10 Measuring Resistance ........................

Summary of the content on the page No. 12

sEctioN 1.1 GENERAL INFORMATION Part 1 GENErator iDENtificatioN It is not our intent to provide detailed disassembly and introduction reassemble instructions in this manual. It is our intent This Diagnostic Repair Manual has been prepared to (a) provide the service technician with an under- especially for the purpose of familiarizing service per- standing of how the various assemblies and systems sonnel with the testing, troubleshooting and repair of work, (b) assist the technician in finding

Summary of the content on the page No. 13

sEctioN 1.2 GENERAL INFORMATION Part 1 iNstallatioN B asics LP (propane) gas is usually supplied as a liquid in introduction pressure tanks. Both the air-cooled and the liquid Information in this section is provided so that the cooled units require a “vapor withdrawal” type of fuel service technician will have a basic knowledge of supply system when LP (propane) gas is used. The installation requirements for home standby systems. vapor withdrawal system utilizes the gaseous fuel Problems

Summary of the content on the page No. 14

sEctioN 1.2 GENERAL INFORMATION Part 1 iNstallatioN B asics Figure 1. Typical Installation Page 12

Summary of the content on the page No. 15

sEctioN 1.2 GENERAL INFORMATION Part 1 iNstallatioN B asics po Wer Source and load lineS SyStem control interconnectionS The utility power supply lines, the standby (genera- Home standby generators are equipped with a termi- tor) supply lines, and electrical load lines must all be nal board identified with the following terminals: (a) connected to the proper terminal lugs in the transfer UTILITY 1, (b) UTILITY 2, (c) 23, and (d) 15B. Load switch. The following rules apply: In 1-phase systems c

Summary of the content on the page No. 16

Section 1.3 General information Part 1 non-PreP ackaged interconnectionS Discussion: 3. Using the following diagram and UL approved wire nuts on the current model air-cooled generators Wire 194 connect the following wires together. Wire 0 will not be was changed to 15B. Wire 15B is still utilized for posi- utilized for this setup. tive voltage for the transfer relay and Wire 23 is still the CONTROL WIRES FROM control ground for transferring the generator. By follow- TRANSFER SWITCH ing the p

Summary of the content on the page No. 17

sEctioN 1.3 GENERAL INFORMATION Part 1 NoN-PrEP acKa GED iNtErcoNNEctioNs connect a 2008 and later load center SWitch CONTROL WIRES FROM to a pre-2008 air-cooled Generator. ENGINE GENERATOR PROCEDURE: N1 (BLU) N1 (YEL) 1. Follow all instructions located in the Installation Manual that was supplied with the unit regarding mounting of the N2 (YEL) N2 (YEL) switch, junction box, and generator. note: When installing a standalone pre-2008 gen- 23 (BRN) 23 (WHT) erator, the battery charger will b

Summary of the content on the page No. 18

sEctioN 1.4 GENERAL INFORMATION Part 1 PrEP aratioN BEforE usE All installed gaseous fuel piping must be purged and General leak tested prior to initial start-up in accordance with The installer must ensure that the home standby gen- local codes, standards and regulations. erator has been properly installed. The system must be inspected carefully following installation. All appli- cable codes, standards and regulations pertaining to Fuel conSumption such installations must be strictly complie

Summary of the content on the page No. 19

sEctioN 1.4 GENERAL INFORMATION Part 1 PrEP aratioN BEforE usE in the selector knob and pull out to overcome spring pressure and then twist clockwise 90 degrees and allow the selector to return in once aligned with the LP (Liquid Propane) position. FUEL SELECTION LEVER - 6. Save this tool with the Owner's Manual. “OUT” POSITION FOR 7. Install the battery, door and close the roof. LIQUID PROPANE (VAPOR) FUEL 8. Reverse the procedure to convert back to natural gas. Figure 3. 10 kW, GT-530 (I

Summary of the content on the page No. 20

sEctioN 1.4 GENERAL INFORMATION Part 1 PrEP aratioN BEforE usE enGine oil recommendationS All oil should meet minimum American Petroleum FUEL SELECTION Institute (API) Service Class SJ, SL or better. Use LEVER - no special additives. Select the oil's viscosity grade “OUT” POSITION FOR according to the expected operating temperature. LIQUID PROPANE • SAE 30 è Above 32° F (VAPOR) FUEL • 10W -30 è Between 40° F and -10° F • Synthetic 5W -30 è 10° F and below Engine crankcase oil capacities


Alternative user manuals
# User manual Category Download
1 Generac Power Systems 004373-6 User manual Portable Generator 6
2 Generac Power Systems 0043734 User manual Portable Generator 3
3 Generac Power Systems 0043735 User manual Portable Generator 3
4 Generac Power Systems 0043733 User manual Portable Generator 2
5 Generac Power Systems 004371-2 User manual Portable Generator 0
6 Generac Power Systems 004626-5 User manual Portable Generator 0
7 Generac Power Systems 0046263 User manual Portable Generator 0
8 Generac Power Systems 004270-1 User manual Portable Generator 0
9 Generac Power Systems 004474-1 User manual Portable Generator 0
10 Generac Power Systems 004701-0 User manual Portable Generator 0
11 Generac Power Systems 004709-0 User manual Portable Generator 1
12 Generac Power Systems 004988-2 User manual Portable Generator 1
13 Generac Power Systems 004917-4 User manual Portable Generator 1
14 Generac Power Systems 004987-2, 005396-0 User manual Portable Generator 2
15 Generac Power Systems 004917-3 User manual Portable Generator 0
16 ACDelco AC-G0005 User manual Portable Generator 1
17 ACDelco AC-G0002 User manual Portable Generator 0
18 ACDelco AC-G0004 User manual Portable Generator 3
19 AEG 2.33 2 User manual Portable Generator 3
20 ACDelco AC-G0003 User manual Portable Generator 0