Quadra-Fire QVI-30FB-S user manual

User manual for the device Quadra-Fire QVI-30FB-S

Device: Quadra-Fire QVI-30FB-S
Category: Indoor Fireplace
Manufacturer: Quadra-Fire
Size: 3.79 MB
Added : 7/12/2013
Number of pages: 41
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Quadra-Fire QVI-30FB-S. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Quadra-Fire QVI-30FB-S.

For your convenience

If looking through the Quadra-Fire QVI-30FB-S user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Quadra-Fire QVI-30FB-S on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Quadra-Fire QVI-30FB-S to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Quadra-Fire QVI-30FB-S User manual - Online PDF
Advertisement
« Page 1 of 41 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Quadra-Fire QVI-30FB-S but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Quadra-Fire QVI-30FB-S. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

DO NOT
DISCARD
R
Owner’s Manual
Installation and Operation
Model(s):
QVI-30FB-S
CAUTION
DO NOT DISCARD THIS MANUAL
• Important operating • Read, understand and follow
• Leave this manual with
and maintenance these instructions for safe party responsible for use
instructions included. installation and operation. and operation.
WARNING
WARNING: If the information in these
instructions is not followed exactly, a fi re HOT SURFACES!
Glass and other surfaces are hot during
or explosion may resul

Summary of the content on the page No. 2

Read this manual before installing or operating this appliance. Please retain this owner’s manual for future reference. Congratulations Congratulations on selecting a Quadra-Fire gas appliance This Owner’s Manual should be retained for future —an elegant and clean alternative to wood burning reference. We suggest that you keep it with your other important documents and product manuals. appliances. The Quadra-Fire gas appliance you have selected is designed to provide the utmost in safety, T

Summary of the content on the page No. 3

Table of Contents 1 Listing and Code Approvals 8 Gas Information A. Appliance Certifi cation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 A. Fuel Conversions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 B. BTU Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 B. Gas Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 C. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . . . . 4 C. Ga

Summary of the content on the page No. 4

Listing and Code Approvals 1 1 A. Appliance Certifi cation C. High Altitude Installations U.L. Listed gas appliances are tested and approved with- MODELS: QVI-30FB-S out requiring changes for elevations from 0 to 2000 feet in the U.S.A. and Canada. LABORATORY: Underwriters Laboratories, Inc. (UL) TYPE: Vented Gas Appliance Heaters When installing this appliance at an elevation above 2000 feet, it may be necessary to decrease the input rat- STANDARD: ANSI Z21.88-2002 • CSA2.33-2002 • UL30

Summary of the content on the page No. 5

Getting Started 2 2 A. Design and Installation Considerations C. Inspect Appliance and Components Quadra-Fire direct vent gas appliances are designed to operate with all combustion air siphoned from outside of WARNING the building and all exhaust gases expelled to the outside. Inspect appliance and components for damage. No additional outside air source is required. Damaged parts may impair safe operation. • Do NOT install damaged components. CAUTION • Do NOT install incomplete component

Summary of the content on the page No. 6

D. Inspect Firebox Surface cracking or crazing of fi rebrick material is normal and expected. The following types of cracks are acceptable and do not require replacement of the unit or the fi rebox: • Cracks that do not propagate entirely through the material. • Light fracture lines or “spider-webbing” on the surface of the material. • Cracks that are less than 1/32 in. wide and less than 3 in. long. • If cosmetically unacceptable, such cracks may be repaired with the SRV-PACK service kit.

Summary of the content on the page No. 7

Fireplace Size Requirements 3 3 • The metal fl oor of the solid fuel fi rebox may be removed to A. Minimum Fireplace Opening facilitate the installation of the insert. The appliance may Minimum fi replace opening requirements are shown in not be placed directly on the base of the outer wrap, a 1/4 Figure 5.1. inch airspace must be provided between the insert and WARNING! Risk of Fire or Burns! Provide adequate the fl oor of the outer wrap. Use the levelling legs to raise clearance aroun

Summary of the content on the page No. 8

B. Clearances INLET AIR 12 in. MAX. WARNING EXHAUST VENT PIPE VENT PIPE Fire Risk. MANTEL Odor Risk. • Clearance to combustible material under the insert is 1/4 inch (0.6 cm). • Use leveling legs to raise insert minimum 1/4 inch above combustible material or outer wrap of factory built fi rebox. 12 in. MIN. WARNING MEASUREMENTS FROM Fire Risk. TOP EDGE OF UNIT • Locate and install appliance to all clearance specifi cations in manual. Figure 3.2 Clearances to Mantels or other Combustibles abov

Summary of the content on the page No. 9

Termination Locations 4 4 A. Vent Termination Minimum Clearances WARNING Figure 4.1 specifi es minimum vent heights for various pitched roofs. Fire Risk. Asphyxiation Risk. • Terminations MUST meet minimum clearances. HORIZONTAL • Exhaust gases are hot. OVERHANG • Nearby vents may draw fumes into house. 2 FT. 20 INCHES MIN. VERTICAL MIN. WALL LOWEST DISCHARGE OPENING GAS DIRECT VENT TERMINATION CAP X 12 ROOF PITCH IS X/ 12 H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENI

Summary of the content on the page No. 10

Vent Information and Diagrams 5 5 A. Vent Table Key WARNING The abbreviations listed in this vent table key are used in the vent diagrams. Fire Hazard. Explosion Risk. Symbol Description Asphyxiation Risk. V Minimum Vertical Run Length 14 ft. Do NOT connect this gas appliance to a MIN chimney fl ue serving a separate solid fuel or V Maximum Vertical Run Length 50 ft. MAX gas burning appliance. • May impair safe operation of this appliance B. Horizontal Venting or other appliances connecte

Summary of the content on the page No. 11

Installation Preparation 6 6 Prepare the existing solid fuel masonry or factory built E. Fireplace Conversion Notice non-combustible fi rebox for installation. Permanently attach the label with the following warning to the inside lower back of the fi replace fi rebox into which A. Flue Damper the insert is being installed. Silicone may be required to Fully lock the solid fuel fi replace’s fl ue damper in the open properly secure the label. position, OR completely remove it. B. Chimney WARNIN

Summary of the content on the page No. 12

Installing Vent Pipe and Appliance 7 7 A. Venting Components B. Connecting Vent Pipe Reference instructions in the termination kit. CAUTION • Install the 3-inch fl exible vent pipe(s) down through the chimney. Sharp Edges • Secure the exhaust fl exible vent pipe to the 3 foot section • Wear protective gloves and safety stainless steel flexible vent pipe using the factory- glasses during installation. installed 3-inch collar in the stainless steel section of pipe (see Figure 7.1). The verti

Summary of the content on the page No. 13

CUT AND BEND WARNING FLASHING AS NEEDED TO FIT CHIMNEY Fire Risk. Only an approved Hearth & Home Technologies surround may be used to cover integral grills on solid fuel burning fi replaces. • No other components such as shrouds, sheet- SEALANT metal plates, etc., may be used to seal off vents. ADHESIVE WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifi cally approved with this appliance may result in property damage or personal injury

Summary of the content on the page No. 14

D. Installing Adaptor and Termination Cap CAUTION For installation of termination cap see minimum vent heights for various pitched roofs (see Figure 7.3). Sharp Edges To install adaptor see Figure 7.4. • Wear protective gloves and safety glasses during installation. HORIZONTAL Damper Flashing Kit (Optional) OVERHANG For use with LINK-DV4-30B Liner Kit. 2 FT. Note: Damper may have to be removed to use this kit. 20 INCHES MIN. VERTICAL MIN. WALL • Run fl ex liners through 3” holes in damper fl

Summary of the content on the page No. 15

Gas Information 8 8 A. Fuel Conversions C. Gas Connection Before making gas connections ensure that appliance be- Note: Have the gas supply line installed in accordance ing installed is compatible with the available gas type. with local building codes, if any. If not, follow ANSI Any natural or propane gas conversions necessary to 223.1. Installation should be done by a qualifi ed installer meet the appliance and locality needs must be made by approved and/or licensed as required by the

Summary of the content on the page No. 16

HIGH ALTITUDE INSTALLATIONS WARNING U.L. Listed gas appliances are tested and approved without Fire or Explosion Hazard requiring changes for elevations from 0 to 2000 feet in the • Gas buildup during line purge may ignite. U.S.A. and Canada. • Purge should be performed by qualifi ed technician. When installing this appliance at an elevation above 2000 feet, • Ensure adequate ventilation. it may be necessary to decrease the input rating by changing • Ensure there are no ignition sources such

Summary of the content on the page No. 17

Electrical Information 9 9 Appliance Requirements A. Wiring the Appliance • This appliance DOES NOT require 110-120 VAC to Note: Electrical wiring must be installed by a licensed operate. electrician. • It is recommended that a 110 VAC junction box be connected for use with fan or remote control. (See Figure Note: This appliance must be electrically wired and grounded 9.2 for junction box wiring). in accordance with local codes or, in the absence of local codes, with National Electric

Summary of the content on the page No. 18

B. Junction Box Installation C. Installation for Fan (Optional) On units already installed removal of decorative front, INSERT STRAIN RELIEF surround and gas insert is required. AROUND CORD IN THIS END FROM OUTSIDE OF UNIT FEED PLUG • Detach fl exible liner from back of unit if insert is installed. THROUGH HOLE SIDEWALL • Remove the four screws on the cover plate (see Figure 9.3). JUNCTION BOX SCREW PROVIDED Figure 9.2 Junction box installation COVER FAN PLATE Optional Accessories Connecting

Summary of the content on the page No. 19

VARIABLE SPEED CONTROL JUNCTION BOX BLK BLK BLOWER RECEPTACLE BLK BLK BLK BLK BLK WHT WHT BLK GROUND BLOWER TEMPERATURE GRN SENSOR SWITCH BLK WHT 110-120 VAC FAN JUNCTION BOX NOTE: IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, TEMPERATURE SENSOR SWITCH IT MUST BE REPLACED WITH TYPE 0 105 C RATED WIRE. SPEED CONTROL (RHEOSTAT) BEND GROUND WIRE UP TABS (ATTACH TO ANY METAL SURFACE) Figure 9.4 Fan Wiring Diagram Quadra-Fire • QVI-30FB-S • 2020-910 Rev. H •

Summary of the content on the page No. 20

Finishing 1 10 0 A. Mantel Projections LOCATING TABS Figure 10.1 shows the minimum vertical and corresponding maximum horizontal dimensions of appliance mantels or other combustible projections above the top front edge of the appliance, not the surround. INLET AIR 12 in. MAX. FIREBOX EXHAUST VENT PIPE VENT PIPE MANTEL 12 in. MIN. LOCATING SLOTS MEASUREMENTS FROM TOP EDGE OF UNIT Figure 10.1 Clearances to Mantels or other Combustibles above Appliance B. Installing Trim Surrounds Figure 1


Alternative user manuals
# User manual Category Download
1 Quadra-Fire 7046-137C User manual Indoor Fireplace 1
2 Quadra-Fire 810-03201 User manual Indoor Fireplace 1
3 Quadra-Fire 810-02901 User manual Indoor Fireplace 0
4 Quadra-Fire 5100I-GD-B User manual Indoor Fireplace 1
5 Quadra-Fire 5100I User manual Indoor Fireplace 0
6 Quadra-Fire CASTINS-CSB User manual Indoor Fireplace 0
7 Quadra-Fire CASTILEI-CE-MBK User manual Indoor Fireplace 0
8 Quadra-Fire Castile Pellet Insert CASTILEI-MBK User manual Indoor Fireplace 0
9 Quadra-Fire CUMBGAP-MBK User manual Indoor Fireplace 0
10 Quadra-Fire CASTINS-CWL User manual Indoor Fireplace 0
11 Quadra-Fire 5100I-NL-B User manual Indoor Fireplace 0
12 Quadra-Fire Direct Ven Room Heater DV400S User manual Indoor Fireplace 0
13 Quadra-Fire CUMPGAP-PMH User manual Indoor Fireplace 0
14 Quadra-Fire DV-40 User manual Indoor Fireplace 0
15 Quadra-Fire Gas Fireplace QV-ST User manual Indoor Fireplace 0
16 Aarrow Fires Becton 7 mk3 User manual Indoor Fireplace 1
17 AEG Royal Belmont G20 User manual Indoor Fireplace 3
18 Austro Flamm Gussofen G3 User manual Indoor Fireplace 1
19 Aarrow Fires Becton Bunny User manual Indoor Fireplace 12
20 Avalon Stoves Victorian Lace DVS Face Black 95200132 User manual Indoor Fireplace 1