Summary of the content on the page No. 1
Installation
Instructions
Models:
Cinch Pipe & Termination Cap System
These instructions are replacing VP (for Heatilator) and DV (for Heat-N-Glo) pipe assembly
instructions. See the appliance installation instructions for confi guration of vent assembly
and clearances to pipe.
If you need assistance during installation, contact your local dealer or the Technical Serices Dept., Hearth & Home Technologies
Inc., phone 1-800-927-6841 or 1-888-427-3973.
If DVP-AD adapters are used off the to
Summary of the content on the page No. 2
Parts and Descriptions 1 1 DVP-TV Vertical termination cap. Includes storm collar and fastener pack. DVP-TB1 Basement/window well termination cap. Includes fas- tener pack. DVP-TRAP1 Horizontal termination cap with 1-3/4 in. telescoping fl ue. Includes DVP-WS wall shield with heat shield and one fastener pack. DVP-TRAP2 Horizontal termination cap with 4 in. telescoping fl ue. Includes DVP-WS wall shield with heat shield and one fastener pack. DVP-TRAPK1 Vent kit containing DVP90ST 90° elbow
Summary of the content on the page No. 3
DVP-TRAPFL DVP-TRAP1 or DVP-TRAP2 termination DVP-TRAPFL Flashing cap rain fl ashing DVP-TRAP1 DVP-TRAP2 Termination Cap COOL ADD Cap shield DRC-RADIUS Cap shield Components Description DRC-RADIUS Cap Shield COOL-ADDM Cap Shield - pack of six DVP-TV Vertical Termination Cap DVP45 45° Elbow DVP90ST 90° Elbow RF6M Roof Flashing (vertical termination for 0/12 to 6/12 pitch) - pack of four RF12M Steep Pitch Roof Flashing (for 7/12 to 12/12 pitch) - pack of six DVP4 4 in. length Vent Pipe DVP6 6 in
Summary of the content on the page No. 4
V ent depth is measured from the back of the appliance to the outer edge of the exterior wall. See Table 1 and Figure 1. TRAP CAP SPECIFICATION CHART DVP-TRAPK1 DVP-TRAP1 DVP-TRAPK2 DVP-TRAP2 Top Vent Rear Vent Top Vent Rear Vent Appliance Depth Depth Depth Depth Novus 4-1/2 in. to 6-1/4 in. 3-1/2 in. to 4-3/4 in. 7 in. to 11 in. 5-1/2 in. to 9-1/2 in. NXT 4-1/8 in. to 5-7/8 in. 4-5/8 in. to 6-3/8 in. 6-1/2 in. to 10-1/2 in. 7-1/4 in. to 11-1/4 in. Caliber 4-1/8 in. to 5-7/8 in. 3-5/8 in. to 5-
Summary of the content on the page No. 5
Installing Vent Pipe 2 Note: Heat shields MUST overlap by 1-1/2 in. min. for rear Note: For termination cap installations only, go directly to Sec- vented appliances. tion E. B. Penetrating a Wall A. Clearances for the Vent Sections Wherever a combustible wall is penetrated, the hole must • Top Vented Direct Vent Appliances be framed with an interior wall shield (DVP-WS) as shown in For all top vented, direct vent appliances, clearances to Figures 2.3-2.4. This shield maintains mini
Summary of the content on the page No. 6
C. Assemble Vent Sections WARNING Fire Risk Exhaust Fumes Risk • Overlap pipe slip sections at least 1-1/2 inches. • Use pilot holes for screws. • Screws must not exceed one inch long. • Pipe may separate if not properly joined. Figure 2.5 Lances Attaching Vent to the Firebox Assembly To attach the fi rst pipe section to the collars, slide the male end of the inner vent of the pipe section over the inner collar on the fi rebox assembly. At the same time, slide the outer fl ue over the outer co
Summary of the content on the page No. 7
Assemble Minimum Installation (MI) Sections MI sections are non-unitized so that they can be cut to a specifi c length. Cut these sections to length from the non- expanded end (see Figure 2.9). They can then be attached by fi rst connecting the expanded end of the MI inner fl ue with the inner pipe from the adjacent pipe section and securing with three screws. The expanded portion of the MI inner fl ue must overlap completely with the unexpanded end of the adjacent pipe section. The outer fl u
Summary of the content on the page No. 8
Secure the Vent Sections Vertical sections of pipe must be supported every 8 ft after the 25 ft maximum unsupported rise. The vent support or plumber’s strap (spaced 120° apart) may be used to do this (see Figures 2.12 and 2.13). Horizontal sections of vent must be supported every 5 ft with a vent support or plumber’s strap. D. Disassemble Vent Sections To disassemble any two pieces of pipe, rotate either section (see Figure 2.14), so that the seams on both pipe sections are aligned (see F
Summary of the content on the page No. 9
E. Install the Heat Shield and Horizontal Termination Cap on the extended heat shield should rest on the top of the vent (pipe section) to properly space it from the pipe section. WARNING Install the Horizontal Termination Cap A 1-1/2 in. minimum overlap MUST be maintained on Vent termination must not be recessed in the wall. Siding the telescoping fl ue section of the cap. may be brought to the edge of the cap base. Caulk the outside edges of the cap. WARNING When installing a horizontal ter
Summary of the content on the page No. 10
F. Vertical Penetration Framing WARNING Fire Risk Keep loose materials or blown insulation from touching the vent pipe. • National building codes recommend using Attic Above attic shield to keep loose materials/blown insulation from contacting vent. 10 in. (254 mm) • Hearth & Home Technologies requires the use of an attic shield. Install the Firestop Spacer • Frame an opening 10 in. by 10 in. whenever the vent system penetrates a ceiling/fl oor (see Figure 2.17). • Frame the area with the sa
Summary of the content on the page No. 11
G. Install Roof Flashing and Vertical Termination Cap To install roof fl ashing see Figure 2.19. To attach the vertical termination cap, slide the inner collar of the cap into the inner fl ue of the pipe section and place For installation of vertical termination cap see minimum vent the outer collar of the cap over the outer fl ue of the pipe heights for various pitched roofs (Figure 2.19) . section. Horizontal Secure with three screws into the outer fl ue. Secure the cap overhang by driving
Summary of the content on the page No. 12
H. Assemble and Install Storm Collar CAUTION Sharp Edges! • Wear protective gloves and safety glasses during installation. Connect both halves of the storm collar with two screws (see Figure 2.21). Wrap the storm collar around the exposed pipe section and align brackets. Insert a bolt (provided) through the brackets and tighten nut to complete the storm collar assembly (see Figure 2.22). Make sure the collar is tight against the pipe section. Slide the assembled storm collar down the pipe