Amtrol BoilerMate Top Down user manual

User manual for the device Amtrol BoilerMate Top Down

Device: Amtrol BoilerMate Top Down
Category: Water Heater
Manufacturer: Amtrol
Size: 5.72 MB
Added : 7/15/2014
Number of pages: 32
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Amtrol BoilerMate Top Down. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Amtrol BoilerMate Top Down.

For your convenience

If looking through the Amtrol BoilerMate Top Down user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Amtrol BoilerMate Top Down on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Amtrol BoilerMate Top Down to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Amtrol BoilerMate Top Down User manual - Online PDF
Advertisement
« Page 1 of 32 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Amtrol BoilerMate Top Down but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Amtrol BoilerMate Top Down. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

INSTALLATION, OPERATION
West Warwick, Rhode Island 02893 & MAINTENANCE
INSTRUCTIONS
®
BOILERMATE
INDIRECT-FIRED WATER HEATERS
MODELS CODES:
MODELS COVERED:

P: Packaged with circulator & Smart Control
• WH-7 & 9 Classic Series
™ ™
L: Less Circulator, with Smart Control
• Top Down TD Series
Z: Dial Aquastat
• RTR models
C: High-output commercial exchanger
• WHS Premier Series
DW: Double-wall heat exchanger
RTR: Pre-piped and wired
INSTALLER: LEAVE THIS MANUAL WITH THE OWNER
IMPORTANT G

Summary of the content on the page No. 2

1. TABLE OF CONTENTS 2. Pre-Installation Checklist .................................................2 10. Wiring All Ready-To-Run (RTR) Models ....................... 23 3. Required Components and Accessories Checklist .........3 11. Startup Procedure For All Models ................................ 25 4. WH-7 & 9 Classic Series Piping Installation ....................4 12. Setting the Smart Control™ .......................................... 26 5. Top Down™ TD-Series Piping Installation ........

Summary of the content on the page No. 3

3. REQUIRED COMPONENTS AND ACCESSORIES CHECKLIST SHUTOFF VACUUM RELIEF THERMAL EXPANSION MODEL CIRCULATOR ZONE VALVE* VALVE BREAKER VALVE TANK DRAIN Residential = 5GPM *If Circulator not used Required ® WH SERIES Commercial = 10GPM 3/4” Full Port 4 1 Included (See Therm-X-Trol Included Except “P” Models or 1” STD Sizing Guide) 5GPM *If Circulator not used Required ® TD SERIES Except “P” Models 3/4” Full Port 4 1 Included (See Therm-X-Trol Included or 1” STD Sizin

Summary of the content on the page No. 4

4. WH-7 & 9 CLASSIC SERIES PIPING INSTALLATION DOMESTIC WATER PIPING BOILER PIPING 3 1. Plumb the circulator or zone valve on the BOILER SUPPLY 1. Thread the included /4” brass tee onto the pipe marked line. If using a separate circulator, the pump flange COLD WATER. can be mounted directly to the threaded pipe marked BOILER SUPPLY. Alternately, the circulator can be placed 3 2. Screw the /4” drain valve into the opposite end of the brass anywhere on the boiler supply line. tee. 2. Pipe

Summary of the content on the page No. 5

PIPING USING SEPARATE CIRCULATOR PUMP (RECOMMENDED) PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR -5-

Summary of the content on the page No. 6

5. TOP DOWN™ TD-SERIES PIPING INSTALLATION can be mounted directly to the threaded pipe marked DOMESTIC WATER PIPING BOILER SUPPLY. Alternately, the circulator can be placed anywhere on the boiler supply line. 1. Connect the cold water supply to the pipe labeled COLD WATER 2. Pipe the BOILER RETURN connection to the boiler return line. 2. Connect the HOT WATER piping to the domestic hot water system. Be sure the return line is NOT plumbed to the suction side of any 3. Make an 8-inch “hea

Summary of the content on the page No. 7

PIPING USING SEPARATE CIRCULATOR PUMP (RECOMMENDED) PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR -7-

Summary of the content on the page No. 8

6. READY-TO-RUN RTR-SERIES PIPING INSTALLATION DOMESTIC WATER PIPING BOILER PIPING 1. Connect the cold water supply to the pipe labeled COLD 1. Plumb the BOILER SUPPLY line. The circulator and flow WATER. check are factory installed 2. Connect the HOT WATER piping to the domestic hot water 2. Pipe the BOILER RETURN connection to the boiler return system. line. Be sure the return line is NOT 3. Make an 8-inch “heat trap” on the HOT WATER outlet as plumbed to the suction side of any shown in

Summary of the content on the page No. 9

PIPING MODELS WITH PRE-INSTALLED CIRCULATOR W/INTEGRAL FLOW CHECK -9-

Summary of the content on the page No. 10

7. WHS PREMIER SERIES PIPING INSTALLATION DOMESTIC WATER PIPING BOILER PIPING 1. Thread the included brass tee onto the pipe marked COLD 1. Plumb the circulator or zone valve on the BOILER SUPPLY WATER. line. If using a separate circulator, the pump flange can be mounted directly to the threaded pipe marked 2. Screw the drain valve into the opposite end of the brass BOILER SUPPLY. Alternately, the circulator can be placed tee anywhere on the boiler supply line. 3. Connect the cold water su

Summary of the content on the page No. 11

PIPING USING SEPARATE CIRCULATOR PUMP (RECOMMENDED) PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR -11-

Summary of the content on the page No. 12

™ 8. WIRING ALL SMART CONTROL MODELS The Smart Control™ incorporates all the switching and temperature control functions necessary to control the BoilerMate™. The diagram below shows internal wiring and the associated functions. After wiring is complete, insert the white thermistor (sensor) plug into the receptacle at the base of the Smart Control™. Select the plug marked CIRCULATOR or ZONE VALVE based on the application. Zone valves can be slow actuating. Therefore, the zone valve sensor co

Summary of the content on the page No. 13

® BOILERMATE L1 L2 JUNCTION BOX ORANGE ORANGE BLUE L8124 A & C BLUE VIOLET 1 2 T T VIOLET WHITE BLACK (PLACE A WIRE NUT OVER EACH WIRE NOT USED) ® BOILERMATE B2 B1 CIRCULATOR ZR C2 C1 ZC HONEYWELL L8124 A & C L8124 B & D ® T BOILERMATE T JUNCTION BOX ORANGE HIGH LOW LIMIT/ CIRCULATOR LIMIT ORANGE W BLUE B R BLUE B VIOLET R VIOLET B2 C1 B1 WHITE BLACK C2 1 2 (PLACE A WIRE NUT OVER EACH WIRE NOT USED) ® BOILERMATE CIRCULATOR HONEYWELL L8124 B & D L1 L2 L1 L2

Summary of the content on the page No. 14

® BOILERMATE JUNCTION BOX L8148J ORANGE T W TV ORANGE TP Z BLUE BLUE HI B LIMIT VIOLET R VIOLET WHITE BLACK C1 C2 (PLACE A WIRE NUT OVER B2 B3 B1 L1 L2 EACH WIRE NOT USED) ® BOILERMATE CIRCULATOR L1 L2 HONEYWELL L8148 J WITH MILLIVOLT GAS VALVE ® BOILERMATE JUNCTION BOX L8148J ORANGE W TV T ORANGE Z TP BLUE BLUE HI B LIMIT VIOLET R VIOLET WHITE BLACK C1 C2 (PLACE A WIRE NUT OVER B1 B2 B3 L1 L2 EACH WIRE NOT USED) ® BOILERMATE CIRCULATOR L1 L2 HONEYWELL

Summary of the content on the page No. 15

® BOILERMATE JUNCTION BOX 8J48A ORANGE TV W T ORANGE Z B TP BLUE BLUE C1 C2 VIOLET L1 B1 B2 B3 L2 VIOLET WHITE BLACK (PLACE A WIRE NUT OVER EACH WIRE NOT USED) WHITE - RODGERS 8J48A WITH SELF-GENERATING GAS VALVE ® L1 L2 BOILERMATE JUNCTION BOX ORANGE ORANGE BLUE L8124 A & C BLUE VIOLET 1 2 T T VIOLET WHITE BLACK B2 B1 ZR ZC C2 C1 ® BOILERMATE CIRCULATOR PRIORITY WIRING HEATING CIRCULATOR HONEYWELL L8124 A & C L8124 B & D ® T T BOILERMATE JUNCTION BOX HIGH

Summary of the content on the page No. 16

L1 L2 ® BOILERMATE JUNCTION BOX L8148A ORANGE L1 L2 T T ORANGE BLUE HIGH 3 LIMIT BLUE VIOLET B VIOLET WHITE R BLACK C1 C2 B1 B2 ® PRIORITY WIRING BOILERMATE CIRCULATOR HONEYWELL L8148A L1 L2 ® BOILERMATE JUNCTION BOX ORANGE ORANGE L8148B BLUE BLUE L1 L2 T T VIOLET HIGH VIOLET LIMIT WHITE B BLACK R ® BOILERMATE C1 C2 B1 B2 CIRCULATOR PRIORITY WIRING HONEYWELL L8148B ® BOILERMATE JUNCTION BOX L8148J ORANGE T W TV ORANGE Z TP BLUE BLUE HI B LIMIT VIOLE

Summary of the content on the page No. 17

® BOILERMATE JUNCTION BOX L8148J ORANGE T W TV ORANGE Z TP BLUE BLUE HI B VIOLET LIMIT R VIOLET WHITE BLACK C1 C2 B1 B2 B3 L1 L2 PRIORITY WIRING ® BOILERMATE HONEYWELL L8148 J CIRCULATOR WITH MILLIVOLT GAS VALVE L1 L2 ® BOILERMATE JUNCTION BOX 8J48A ORANGE TV W T ORANGE HEATING TP Z B BLUE CIRCULATOR C1 BLUE C2 VIOLET L1 B3 B1 B2 L2 VIOLET WHITE BLACK (PLACE A WIRE NUT OVER EACH WIRE NOT USED) PRIORITY WIRING WHITE-RODGERS 8J48A ® BOILERMATE WITH 24VOL

Summary of the content on the page No. 18

Typical Multi-Zone Relay ORANGE Utilizing Post-Purge Feature ORANGE BLUE BLUE Thermostat Inputs VIOLET VIOLET Priority or DHW Zone BLACK WHITE Zone Outputs Smart Control™ X X L1 L2 (PLACE A WIRE NUT OVER EACH WIRE NOT USED) 120V Supply T T ® BoilerMate Boiler Aquastat Circulator Typical Multi-Zone Relay ORANGE 24V without Post-Purge Feature ORANGE BLUE BLUE Thermostat VIOLET Inputs VIOLET Priority or DHW Zone BLACK 24V Supply WHITE Zone Outputs Smart

Summary of the content on the page No. 19

WATER SENSOR INSTALLATION (IF EQUIPPED) The Smart Control™ features an error code designed to alert the user to the presence of water on the floor. This is useful to warn of a leaking boiler, water heater, etc., or to alert the owner to a leak in the basement. If equipped with the optional water sensor, follow the installation instructions below: Water Sensor Plug 1. If the sensor will be used to detect a water heater leak, the proper placement is in a drip pan as required in the warning se

Summary of the content on the page No. 20

9. WIRING ALL DIAL CONTROL MODELS (EXCEPT RTR MODELS) Dial Control models utilize a standard dry-contact aquastat with capillary temperature sensor. The dial control contains a make-and-break switch and is suitable for 24V or 120V, 25A Max. CAPILLARY TUBE SENSOR BULB SHAFT WIRE LEADS To wire Dial Control models, select the appropriate diagram from the following pages. If a suitable diagram is not available for your application, please contact AMTROL Tech Support at (401)535-1216. Always d


Alternative user manuals
# User manual Category Download
1 Amtrol WH-7 Classic Series User manual Water Heater 2
2 Amtrol Pre-Pressurized Water System Tanks WELL-X-TROL User manual Water Heater 7
3 Amtrol HYDROMAX HM-80L User manual Water Heater 4
4 Amtrol HYDROMAX HM-41L User manual Water Heater 1
5 Amtrol WH-9 Classic Series User manual Water Heater 1
6 Amtrol Therm-X-Trol User manual Water Heater 1
7 Amtrol HYDROMAX HM-80Z User manual Water Heater 0
8 Amtrol HYDROMAX HM-41Z User manual Water Heater 0
9 Amtrol BoilerMate RTR User manual Water Heater 0
10 A.O. Smith 000 User manual Water Heater 8
11 A.O. Smith 101 User manual Water Heater 3
12 A.O. Smith 12 40GPC T 100 User manual Water Heater 4
13 A.O. Smith 104 Series User manual Water Heater 3
14 A.O. Smith 104 - 110 User manual Water Heater 6
15 A.O. Smith 105 Series User manual Water Heater 1