Trane GSSD user manual

User manual for the device Trane GSSD

Device: Trane GSSD
Category: Heat Pump
Manufacturer: Trane
Size: 1.69 MB
Added : 9/4/2013
Number of pages: 18
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Trane GSSD. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Trane GSSD.

For your convenience

If looking through the Trane GSSD user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Trane GSSD on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Trane GSSD to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Trane GSSD User manual - Online PDF
Advertisement
« Page 1 of 18 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Trane GSSD but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Trane GSSD. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

WSHPC-IOM-2
Installation
72-9041-02
Operation &
Maintenance
Library Service Literature
Product Section Unitary
Product Water Source Heat Pump
Model GSSD
Literature Type Installation, Operation and Maintenance
Sequence 2
Date June 1999
File No. SL-UN-WSHP-GSSD-IOM-2-6-99
Supersedes WSHPC-IOM-2 / 72-9041-01 (Jan 98)
Water Source Heat
Pump Residential
Split Configuration
HVAC System
Since American Standard Inc. has a policy of continuous product improvement, it reserves the right to change specific

Summary of the content on the page No. 2

Table of Contents Model Number 3 Installation (Water Loop).. 15 Descriptions..................... General 4 Refrigeration Charge........ 16 Information...................... Receiving and 6 Refrigeration System....... 17 Handling.......................... Installation 7 Accessories................... 18 Drawings......................... Installation (Water 10 Connections).................... Installation 11 (Electrical)................. Diagram.................... 14 Notice The Trane Compa

Summary of the content on the page No. 3

Model Number Description GS S D 036 1 0 C 0 0 1 2 0 T 5 10 15 DIGITS 1 & 2 - PRODUCT TYPE DIGIT 14 - FREEZE PROTEC- TION GS = Ground Source Heat Pump 1 = 35 Degree Freezestat 2 = 20 Degree Freezestat DIGIT 3 - PRODUCT CONFIGU- RATION S = Split System DIGIT 15 - OPEN 0 = Open DIGIT 4 - DEVELOPMENT SE- QUENCE D DIGIT 16 - BRAND C = Command Aire DIGITS 5,6 & 7 - UNIT NOMINAL T = Trane CAPACITY (MBH) 024 = 24.1 030 = 29.6 036 = 36.4 042 = 41.1 048 = 48.7 060 = 59.2 072 = 65.6 DIGIT 8 - VOLTAGE/HERT

Summary of the content on the page No. 4

General Information The GSSD split unit has been ARI rat- ature-out of the hot water heater. The Brass Loop Water ed with the Trane TWE air handlers desuperheater is disable until the com- Connections with ICM 2 variable speed motors to pressor discharge line reaches 145 de- create a complete split system for res- grees F. The desuperheater pump will Two 1-inch brass swivel connectors idential applications. The GSSD automatically shut off if the tempera- on the units help eliminate the need

Summary of the content on the page No. 5

General Information The refrigerant circuit, including the Optional extended warranties are Warranty compressor, expansion device, revers- available through the local distributor. ing valve (less solenoid coil), and all The unit is warranted by the manufac- Note: heat exchangers in contact with refrig- turer against any defects in material erants are warranted for an additional and factory workmanship for one year If any safety device is bypassed or four years (parts only). after installat

Summary of the content on the page No. 6

Receiving and Handling The GSSD is packaged in clear stretch remove the (4) four shipping brackets ! Inspect the overall quality and appearance of the unit wrap to allow immediate visual in- from the lower corners of the unit spection. A careful inspection should along with the shipping skid. be made for shipping damage. All or- Note: ders are free on board (FOB) facto- ry, therefore claims must be made Before installing the unit: with the delivering carrier. ! Verify nameplate and model numb

Summary of the content on the page No. 7

Installation-Location Considerations Unit Size 024 Unit Weight Unit Size (lbs.) 024 163 23-5/16” 23” 6-7/16” LOW VOLTAGE 5-1/2” 1-1/8” DIA. TOP VIEW 3-15/16” PUMP CONTROL 1-7/16” 1-1/8” DIA. HI VOLTAGE WATER REG (SCHRADER PORT) SUCTION/DISCH 1-1/8” DIA. 3/4” O.D. LIQUID LINE DESUPER OUT 1/2” O.D. 1/2” NPT WATER OUT 1” NPTI DESUPER IN 24-5/16” 1/2” NPT LOW PSI SCHRADER HI PSI SCHRADER 8-7/16” 24-13/16” 13-1/4” WATER IN-1” NPTI FRONT VIEW SIDE VIEW 7 10-7/16” 7-3/16” 2-1/16” 13” 13-15/16” 14-3/4”

Summary of the content on the page No. 8

Installation-Location Considerations Unit Weight Unit Size Unit Size 030-042 (lbs.) 030 169 036 183 042 203 23-5/16” 23” 6-7/16” LOW VOLTAGE 5-1/2” 1-1/8” DIA. TOP VIEW 3-15/16” PUMP CONTROL 1-7/16” 1-1/8” DIA. HI VOLTAGE WATER REG (SCHRADER PORT) SUCTION/DISCH 1-1/8” DIA. 3/4” O.D. LIQUID LINE DESUPER OUT 1/2” O.D. 1/2” NPT WATER OUT 1” NPTI DESUPER IN 1/2” NPT 24-5/16” LO PSI SCHRADER HI PSI SCHRADER 8-7/16” 24-13/16” 11-1/2” WATER IN-1” NPTI FRONT VIEW SIDE VIEW 8 10-7/16” 7-3/16” 2-1/16” 13

Summary of the content on the page No. 9

Installation-Location Considerations Unit Weight Unit Size Unit Size 048-072 (lbs.) 048 214 060 244 072 277 23-5/16” 6-7/16” 23” 5-1/2” LOW VOLTAGE 3-15/16” 1-1/8” DIA. 1-7/16” TOP VIEW PUMP CONTROL HI VOLTAGE 1-1/8” DIA. 1-1/8” DIA. WATER REG LIQUID LINE (SCHRADER PORT) SUCTION/DISCH 1/2” O.D. 3/4” O.D. WATER OUT DESUPER OUT 1” NPTI 1/2” NPT DESUPER IN 1/2” NPT 24-5/16” LO PSI SCHRADER HI PSI SCHRADER 8-7/16” 24-13/16” 11-1/2” WATER IN-1” NPTI FRONT VIEW SIDE VIEW 9 10-7/16” 7-3/16” 2-1/16” 13

Summary of the content on the page No. 10

Installation-Water Connections Location Consideration ! Unit should be placed on a level surface in a indoor protected area. Units should not be installed or stored in an exterior environment. Remove these two ! There should be approximately 2 screws for internal unit to 3 feet of clearance available for maintenance. accessing the unit for service. Accessiblity into unit is made by re- moving (2) two screws at the base of the system. (See Figure 2). The top half of the cube then lifts off.

Summary of the content on the page No. 11

Installation- Electrical Field Wiring Connections GSSD 24V Field Wiring T-Stat (X13510588020) RF Y OC W W Power wiring to the unit should be in- 1 2 2 Manual changeover: -two-stage heat stalled per local electric codes by a -one-stage cool professional electrician. The wires can be run to the unit through the available knockouts and to the control box in the top half of the unit. TWE Control wiring to the unit is 24 volt. (Sizes 031-065) RG Y O B W W 1 2 The termination point identifications for

Summary of the content on the page No. 12

Installation- Electrical Electrical System 24VAC ENERGY LIMITING CLASS II LOCKOUT 75VA BREAKER TYPE TRANSFORMER RELAY; 24VAC The factory tested and installed control COMPRESSOR RUN CAPACITOR box contains all of the necessary de- 370V vices to control unit operation in both the heating and cooling mode. A re- COMPRESSOR CONTACTOR 3 POLE-24VAC mote wall thermostat is necessary for the control of the unit operation. See General Information for thermostat in- formation. The nameplate provides in

Summary of the content on the page No. 13

Installation- Electrical der low charge or catastrophic loss of The low pressure switch should be Pressure Switch charge situations. wired to activate at refrigerant A high pressure switch is provided to pressures of 35 psig when a 35 The low water temperature switch is protect the compressor against exces- degree F freezestat is used; 7 psig provided to protect the water-to-re- sive refrigeration pressure. The low frigerant heat exchanger from freez- when a 20 degree F freezestat is pre

Summary of the content on the page No. 14

Typical Wiring Diagram L1 L2 230V 6A MAX TO WATERSOURCE PUMP 5F3 5F2 5F1 4 2A 4S5 4S6 6H 6F 6E 6G DESUPER- HEATER PUMP 1K1 6A,C,D,E 7C A 6B1 L3 T3 R C 1C1 7A 2B1 S 1K1 A,C A 5C C L1 T1 5C G 1TB3-1 F,G 16 1K3 1TB3-5 1TB3-2 C2 C1 A C D,F 1K3-24 16 1K1 18 23 1K3 4S3 4S4 4S1 23 19A 21A A D 20A A 5 1TB3-7 1TB3-8 1K1-12,14 4S4 1TB3-6 A F 25 NOTES: LEGEND 1. UNLESS OTHERWISE NOTED. ALL SWITCHES ARE DEVICE DESCRIPTION SHOWN AT 77 DEGREES F AT ATMOSPHERIC PRESSURE. AT 50% RELATIVE HUMIDITY, WITH ALL UTIL

Summary of the content on the page No. 15

Installation - Water Loop apt to use one million gallons of Loop Water Applications Ground Water Applications water per year. It may be (Closed Loop) It should be noted that there is no me- necessary to install a recharge well chanical difference between geother- to return the water to the aquifer. Loop sizing should be done by a qual- mal (closed loop) and ground water In some soils, this may be difficult ified installer to insure maximized unit (open loop) GSSD units. Generally in perf

Summary of the content on the page No. 16

Refrigerant Charge 3. Charge the system unit until a GSSD Units Coupled with level of 10 degrees superheat is TWE Air Handlers Table 5: R22 requirement per foot of line achieved. To determine super- heat, an accurate suction line The GSSD IS coupled with the TWE- O.D. Tube Liquid Line Suction temperature needs to be taken Size (oz.) Line (oz.) E series. Table 4 may be used to deter- along with the suction pressure. mine the amount of charge necessary 1/4-inch 0.352 N/A 4. The sub-cooling

Summary of the content on the page No. 17

Refrigeration System loop applications and closed loop the unit is in the cooling mode and Refrigeration System applications without adequate de-energizes in the heating mode. ! Compressor: The unit includes a antifreeze. A 20 degree F ! Refrigerant Tubing: All refrigerant high efficiency scroll compressor freezestat may be used with closed tubing is constructed of copper. with and internal vibration isolator loop applications with antifreeze The low temperature refrigerant that absorb

Summary of the content on the page No. 18

Miscellaneous Equipment and the loop pump module. This necessary components for the Accessory Items isolation device is a much less installation, operation and Note: expensive and very effective maintenance of the water circuit of alternative. When the compressor a closed loop geothermal The following equipment may be pur- begins running, the valve will application. Standard pump chased through the nearest Trane dis- open, allowing water to flow module features include insulated tributor.


Alternative user manuals
# User manual Category Download
1 Trane 22-5202-03-3605 User manual Heat Pump 0
2 Trane 2TWB0-UM-2 User manual Heat Pump 0
3 Trane 4TWX6 User manual Heat Pump 1
4 Trane 2TWB-SVU01A-EN User manual Heat Pump 1
5 Trane 4TWX6036B User manual Heat Pump 2
6 Trane 4TWX6048B User manual Heat Pump 1
7 Trane 4TWX606OB User manual Heat Pump 0
8 Trane 4TWX6024B User manual Heat Pump 0
9 Trane 4YCY4024A User manual Heat Pump 5
10 Trane 4YCY4060A User manual Heat Pump 0
11 Trane EXWA User manual Heat Pump 7
12 Trane GETB User manual Heat Pump 2
13 Trane GEH User manual Heat Pump 27
14 Trane GEV User manual Heat Pump 3
15 Trane GSWD User manual Heat Pump 0
16 Edelbrock 15005 User manual Heat Pump 0
17 A.O. Smith AH User manual Heat Pump 2
18 ACS 882.00217.00 User manual Heat Pump 1
19 A.O. Smith AHD 290 User manual Heat Pump 3
20 AC International SELF-PRIMING CENTRIFUGAL PUMPS User manual Heat Pump 5