Summary of the content on the page No. 1
279104-YTG-B-0307
DESCRIPTION
The 10 SEER Series heat pumps is the outdoor part of a ver-
satile system of heat pumps. It is designed to be custom-
matched with one of UPG’s complete line of evaporator sec-
tions, with each serving a specific function. Matching Air Han-
dlers are available for upflow, downflow, or horizontal
applications to provide a complete system. Electric Heaters
are available, if required. Add-On coils are available for use
with upflow, downflow, or horizontal furnaces a
Summary of the content on the page No. 2
279104-YTG-B-0307 Physical and Electrical Data MODEL E1RA036S25 E2RA048S25 E1RA060S25 E1RA036S46 E2RA048S46 E1RA060S46 208/230-3-60 460 - 3 - 60 Unit Supply Voltage 1 187 to 252 432 to 504 Normal Voltage Range Minimum Circuit Ampacity 15.0 18.9 24.5 8.0 10.1 12.0 2 25 30 40 15 15 20 Max. Qvercurrent Device Amps 3 D C D C Inertia Inertia Compressor Type Scroll Scroll Scroll Scroll Compressor Amps Rated Load 10.9 14.1 18.6 5.8 7.0 9.0 Locked Rotor 78 125 128 40 55 63 Crankcase Heater Yes No No Y
Summary of the content on the page No. 3
279104-YTG-B-0307 Additional R-22 Charge / Orifice Size for Various Matched Systems Outdoor Unit E1RA036S(25,46) E1RA048S(25,46) E1RA060S(25,46) 1 71, 81 81, 84, 87 99 Unit Orifice (s) Factory R-22 Charge, lbs-oz 5 - 12 8 - 3 11 - 3 Indoor Coil System Orifice = Additional Charge, Oz FC/MC/PC35(B,C)3X 81 + 8 – – FC/MC/PC/UC36(A,B,C)3X 71 + 7 – – FC/MC/PC/UC42(B,C)3X 81 + 8 – – FC/MC/PC/UC48C3X – 87 + 6 – FC/MC/PC/UC48D3X – 87 + 6 – FC/MC/PC/UC60C3X – 84 + 4 99 + 0 FC/MC/PC/UC60D3X – 84 + 4 99 +
Summary of the content on the page No. 4
279104-YTG-B-0307 COOLING CAPACITY - With Air Handler Coils AIR HANDLER COOLING 1 COIL UNIT MODEL 2 NET MBH SEER RATED SEER ELECTRIC MODEL MODEL W EER 3 CFM W/O TXV HEAT KW WITH TXV TOTAL SENS. 3 PH 10 SEER HP WITH MA / MC / N-AH / G2FD MA12BN2,4 10 17 FC/MC35B3X 1250 34.4 25.3 10 – 8.95 MA12BN2,4 10 17 FC/MC36B3X 1250 34.4 25.3 10 – 8.95 E1RA036S(25,46) MA12BN2,4 10 17 FC/MC42B3X 1250 34.4 25.3 10 – 8.95 N1AHC1646 10, 15 21 G2FD042(S,H)21 1250 34.2 25.3 10 – 8.95 MA16CN4 10, 15 21 FC/MC48C3X 1
Summary of the content on the page No. 5
279104-YTG-B-0307 COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils FURNACE** COOLING COIL UNIT MODEL NET MBH 1 CFM RANGE RATED SEER SEER + TXV MODEL W EER (MIN.-MAX.) CFM W/O TXV + TDR* TOTAL SENS. 21,24 G1FA048S21 1250 34.4 24.7 10 – 9.05 17 G1NA036S17L 1250 35.0 26.2 10 – 9.00 21 G1NA048S21D 1250 35.0 26.2 10 – 8.95 21,24 G1UA048S21 1250 34.4 24.7 10 – 9.05 1100 E1RA036S(25,46 1400 21 G2FD042S21 1250 34.2 25.3 10 – 8.95 17,21 FC/MC/PC35*3X 1250 34.4 24.7 10 – 9.5 14,17,21
Summary of the content on the page No. 6
279104-YTG-B-0307 HEATING PERFORMANCE - With Air Handler 2 3 ARI HEATING OUTDOOR TEMP 1 UNIT COIL 47 °F17 °F HSPF -3 °F7 °F17 °F27 °F37 °F47 °F57 °F MODEL* MODEL MBH COP MBH COP STD MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW F2RP/F2FP036 34.0 3.00 20.4 2.16 7.2 15.5 2.40 15.6 2.54 20.4 2.80 24.9 3.03 29.9 3.20 34.0 3.32 38.5 3.50 E1RA036S(25,4 AHP36,42 34.0 3.00 20.4 2.16 7.2 15.5 2.40 15.6 2.54 20.4 2.80 24.9 3.03 29.9 3.20 34.0 3.32 38.5 3.50 F2FP048 37.0 3.08 31.4 2.32 7.5 20.8 3.64 26.
Summary of the content on the page No. 7
279104-YTG-B-0307 Room Thermostats - A wide selection of matching thermo- ACCESSORIES stats is available to provide features required for any installa- Refer to Price Manual for specific model numbers. tion. Start Assist Kit (2SA067*) 2H/1C, manual changeover electronic non-programmable Blower Time Delay - Available to increase efficiency when thermostat. installed. Installs on indoor section and maintains blower for 3H/2C, non-programmable digital thermostat. approximately one minute after coo
Summary of the content on the page No. 8
279104-YTG-B-0307 TYPICAL FIELD WIRING - 3 PH (036 - 060) ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES THERMOSTAT INDOOR UNIT OUTDOOR UNIT 3,4 LOW VOLTAGE TERMINAL BLOCK DEFROST IN AIR HANDLER WITH ELECTRIC HEAT CONTROL CONTACTOR RED R R R BLK BorC BorC C T3 T2 T1 YEL Y Y Y M ORG O GND. O O L3 L2 L1 SCREW BRN W2 W W PUR LorX X WHT G G W1/66 1 5 2 FIELD GRY T W1 CC INSTALLED 2 E JUMPER 1 JUMPER TERMINALS E AND W TOHEAT POWER WIRING ON FIRST STAGE DURING EMERGEN
Summary of the content on the page No. 9
279104-YTG-B-0307 COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. E1RA036S(25,46) INDOOR COIL MODEL NO. F2RP/F2FP036 ID CFM 1000 1250 1400 CONDENSER ENTERING AIR ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70 TEMPERATURE ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57 T.C. 38.1 35.0 32.5 29.4 38.6 35.5 32.9 29.9 38.8 35.7 33.2 30.2 75 S.C. 22.9 22.9 22.1 23.6 24.1 24.2 23.4 24.8 24.9 24.9 24.1 25.5 KW 3.15 3.08 3.02 2.94 3.16 3.10 3.03 2.96 3.17 3.10 3.04 2.97 T.C. 37.6 34.6 32.0 28.9 38.1 35
Summary of the content on the page No. 10
279104-YTG-B-0307 COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. E2RA048S(25,46) INDOOR COIL MODEL NO. F2FP048 ID CFM 1300 1450 1550 CONDENSER ENTERING AIR ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70 TEMPERATURE ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57 T.C. 52.3 48.3 45.0 40.6 53.0 49.0 45.7 41.3 53.4 49.4 46.1 41.9 75 S.C. 32.5 32.8 31.7 33.5 34.0 34.3 33.2 35.1 35.0 35.2 34.1 36.3 KW 4.14 4.07 4.02 3.95 4.16 4.08 4.04 3.97 4.17 4.09 4.05 3.97 T.C. 50.9 47.0 43.7 39.4 51.5 47.6 44.
Summary of the content on the page No. 11
279104-YTG-B-0307 COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. E1RA060S(25,46 INDOOR COIL MODEL NO. G2FD060(S,H)24 ID CFM 1600 1800 2000 CONDENSER ENTERING AIR ID DB (°F) 85 80 75 85 80 75 85 80 75 TEMPERATURE ID WB (°F) 71 67 63 71 67 63 71 67 63 T.C. 63.0 61.1 60.7 62.9 60.9 61.1 62.9 60.6 61.4 65 S.C. 39.6 39.7 40.3 41.6 41.5 42.2 43.7 43.3 44.1 KW 3.71 3.66 3.68 3.71 3.66 3.67 3.71 3.67 3.67 T.C. 62.3 59.8 57.9 62.5 60.0 58.5 62.6 60.1 59.0 75 S.C. 39.6 39.3 39.1 41.8 41.3 41.1 43.9 4
Summary of the content on the page No. 12
279104-YTG-B-0307 HEATING PERFORMANCE DATA CONDENSING UNIT MODEL NO E1RA036S(25,46) EVAPORATOR COIL MODEL NO F2RP/F2FP036 AIR TEMP. AIR TEMP. ID CFM ENTERING ENTERING 1000 1250 1400 OUTDOOR INDOOR MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P. UNIT COIL 60 41.6 3.37 3.6242.03.303.7341.33.273.70 60 70 39.1 3.54 3.2440.23.493.3740.23.493.38 80 37.4 3.70 2.9739.13.673.1239.73.693.16 60 35.3 3.17 3.2635.73.153.3234.83.153.24 47 70 33.1 3.32 2.9334.03.323.0033.83.332.98 80 31.5 3.46 2.6732.73.482.7
Summary of the content on the page No. 13
279104-YTG-B-0307 HEATING PERFORMANCE DATA CONDENSING UNIT MODEL NO E2RA048S(25,46) EVAPORATOR COIL MODEL NO F2RP/F2FP048 AIR TEMP. AIR TEMP. ID CFM ENTERING ENTERING 1250 1400 1550 OUTDOOR INDOOR MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P. UNIT COIL 60 53.4 4.863.2352.94.723.2852.24.25 3.61 60 70 54.2 4.763.3454.14.613.4453.74.14 3.80 80 54.1 5.572.8554.45.392.9654.44.83 3.30 60 47.0 4.543.0346.64.453.0746.54.05 3.36 47 70 46.9 4.563.0247.04.473.0847.24.06 3.41 80 46.3 5.242.5946.95.132.6
Summary of the content on the page No. 14
279104-YTG-B-0307 HEATING PERFORMANCE DATA CONDENSING UNIT MODEL NO E1RA060S(25,46) EVAPORATOR COIL MODEL NO G2FD060(S,H)24 AIR TEMP. AIR TEMP. ID CFM ENTERING ENTERING 1600 1800 2000 OUTDOOR INDOOR MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P. UNIT COIL 60 63.6 5.09 3.6761.94.983.6460.14.873.62 60 70 64.8 5.33 3.5663.55.183.5962.25.043.62 80 65.9 5.60 3.4565.15.393.5464.25.203.62 60 56.9 4.15 4.0355.74.024.0654.43.904.10 47 70 58.3 4.62 3.7058.04.543.7556.34.353.80 80 59.7 5.19 3.3859.05.033
Summary of the content on the page No. 15
279104-YTG-B-0307 NOTES Unitary Products Group 15
Summary of the content on the page No. 16
NOTES Subject to change without notice. Printed in U.S.A. 279104-YTG-B-0307 Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 279104-YTG-A-1106 Unitary 5005 Norman Product York OK Group Drive 73069