Carrier 50TFQ008-012 user manual

User manual for the device Carrier 50TFQ008-012

Device: Carrier 50TFQ008-012
Category: Heat Pump
Manufacturer: Carrier
Size: 1.85 MB
Added : 6/6/2014
Number of pages: 56
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Carrier 50TFQ008-012. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Carrier 50TFQ008-012.

For your convenience

If looking through the Carrier 50TFQ008-012 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Carrier 50TFQ008-012 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Carrier 50TFQ008-012 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Carrier 50TFQ008-012 User manual - Online PDF
Advertisement
« Page 1 of 56 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Carrier 50TFQ008-012 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Carrier 50TFQ008-012. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

50TFQ008-012
Single-Package Rooftop
Heat Pump Units
Installation, Start-Up and
Service Instructions
CONTENTS Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
Page
fire extinguisher available for all brazing operations.
SAFETY CONSIDERATIONS .........................1
INSTALLATION ...................................1-43
Step 1— Provide Unit Support.......................1
 ROOF CURB
Before performing service or maintenance operation

Summary of the content on the page No. 2

Fig. 1 — Roof Curb Details 2

Summary of the content on the page No. 3

1 pitch the line away from the unit at / -in. per ft of run. Do not 4 use a pipe size smaller than the unit connection. See Fig. 4. Step 4 — Rig and Place Unit — Inspect the unit for transportation damage. File any claim with the transportation agency. Keep the unit upright and do not drop it. Spreader bars are not required if top crating is left on the unit. Rollers may be used to move the unit across a roof. Level by using the unit MAXIMUM ALLOWABLE frame as a reference. See Table 1 and Fig. 5

Summary of the content on the page No. 4

NOTES: 1. Dimension in ( ) is in millimeters. 2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit. WEIGHT A B C 50TFQ 3. Unit weights do not include economizer. See Table 1 for economizer Lb Kg in. mm in. mm in. mm weights. 008 940 426 77.42 1966.5 41.5 1054 42.12 1070 009 965 438 77.42 1966.5 41.5 1054 42.12 1070 012 1015 460

Summary of the content on the page No. 5

Table 1 — Physical Data UNIT SIZE 50TFQ 008 009 012 1 1 NOMINAL CAPACITY (tons) 7 / 8 / 10 2 2 OPERATING WEIGHT (lb) Unit 940 965 1015 Economizer EconoMi$er IV 75 75 75 Roof Curb* 143 143 143 COMPRESSOR (Hermetic) Reciprocating Scroll Quantity 222 Oil (oz) 45 ea 54 ea 54 ea REFRIGERANT TYPE R-22 Operating Charge (lb-oz) Circuit 1 5-14 8- 6 7-14 Circuit 2 5-13 8-13 8- 3 OUTDOOR COIL Enhanced Copper Tubes, Aluminum Lanced Fins, Acutrol™ Feed Device Rows...Fins/in. 1...17 2...17 2...17 Total Face A

Summary of the content on the page No. 6

6 Fig. 6 — Base Unit Dimensions

Summary of the content on the page No. 7

When installing units, provide a disconnect per the NEC. Step 5 — Make Electrical Connections All field wiring must comply with the NEC and local re- quirements. In Canada, electrical connections must be made in accordance with CSA (Canadian Standards Association) C22.1 Unit cabinet must have an uninterrupted, unbroken electri- Canadian Electrical Code Part One. cal ground to minimize the possibility of personal injury if Install field wiring as follows: an electrical fault should occur. This gr

Summary of the content on the page No. 8

Table 2 — Electric Heating Capacities ELECTRIC HEATER SINGLE POINT BOX 50TFQ UNIT VOLTAGE ACCESSORY PART NUMBER PACKAGE NO. UNIT SIZE (60 Hz) kW CRHEATER---A00 CRSINGLE---A00 7.8/ 9.6/10.4 017 007 12.0/14.7/16.0 010 007 208/230/240 18.6/22.8/24.8 011 009 (3 phase) 24.0/29.4/32.0 012 009 31.8/39.0/42.4* 012 and 017 013 12.8/13.9 016 006 008, 009 15.2/16.5 013 006 460/480 25.6/27.8 014 008 (3 phase) 30.4/33.0 015 008 38.4/41.7* 014 and 016 010 575 17.0 018 006 (3 phase) 34.0 019 006† 7.8/ 9.6/10.4

Summary of the content on the page No. 9

Table 3A — Electrical Data (Units Without Electrical Convenience Outlet) (cont) VOLTAGE COMPRESSOR DISCONNECT ELECTRIC HEAT* POWER SUPPLY RANGE (each) SIZE† 50TFQ NOMINAL IFM OFM IFM UNIT SIZE V-PH-Hz TYPE FLA FLA Nominal Min Max RLA LRA FLA MCA MOCP FLA LRA kW** — — 44.6/ 44.6 45/ 45†† 47/ 47 321/321 7.8/10.4 21.7/ 25.0 71.7/ 75.9 80/ 80 72/ 75 343/346 12.0/16.0 33.3/ 38.5 86.2/ 92.7 90/100 85/ 91 354/360*** STD 187 254 16.0 137.0 1.4 5.8 18.6/24.8 51.6/ 59.7 109.1/119.2 110/125 106/115 373/381

Summary of the content on the page No. 10

Table 3B — Electrical Data (Units With Electrical Convenience Outlet) VOLTAGE COMPRESSOR ELECTRIC DISCONNECT POWER SUPPLY RANGE (each) HEAT* SIZE† 50TFQ NOMINAL IFM OFM IFM UNIT SIZE V-PH-Hz TYPE FLA FLA Nominal Min Max RLA LRA FLA MCA MOCP FLA LRA kW** — — 43.6/ 43.6 45/ 45†† 46/ 46 234/234 7.8/10.4 21.7/ 25.0 70.7/ 74.8 80/ 80 71/ 75 256/259 12.0/16.0 33.3/ 38.5 85.2/ 91.7 90/100 85/ 91 267/272*** STD 187 254 13.4 91.0 1.4 5.8 18.6/24.8 51.6/ 59.7 108.1/118.2 110/125 106/115 285/294*** 24.0/32

Summary of the content on the page No. 11

Table 3B — Electrical Data (Units With Electrical Convenience Outlet) (cont) VOLTAGE COMPRESSOR ELECTRIC DISCONNECT POWER SUPPLY RANGE (each) HEAT* SIZE† 50TFQ NOMINAL IFM OFM IFM UNIT SIZE V-PH-Hz TYPE FLA FLA Nominal Min Max RLA LRA FLA MCA MOCP FLA LRA kW** — — 52.1/ 52.1 60/ 60†† 55/ 55 300/300 7.8/10.4 21.7/ 25.0 79.2/ 83.4 80/ 90 80/ 84 322/325*** 12.0/16.0 33.3/ 38.5 93.7/100.2 100/110 93/ 99 333/338*** STD 187 254 17.2 124.0 1.4 5.8 24.0/32.0 66.6/ 77.0 135.4/148.4 150/150 132/144 366/37

Summary of the content on the page No. 12

FIELD CONTROL WIRING — Install a Carrier-approved DEFROST BOARD — The defrost board timer cycle is set to accessory thermostat assembly according to the installation 30 minutes. To change the cycle time, turn off power to the instructions included with the accessory. Locate the thermostat unit and install lockout tag. Remove the wire from defrost assembly on a solid wall in the conditioned space to sense aver- board connected to the 30 minute quick-connect. See Fig. 10. age temperature in accord

Summary of the content on the page No. 13

Table 4 — Heat Anticipator Settings UNIT VOLTAGE 208/230 460 575 UNIT Configuration Configuration Configuration Heater Heater Heater 2-Stage 2-Stage 2-Stage kW* kW* kW* 1-Stage 1-Stage 1-Stage Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 10.4, 16.0 0.3 NA NA 13.9, 16.5 0.3 NA NA 17.0, 34.0 0.3 NA NA 27.8, 33.0 50TFQ 24.8, 32.0 0.6 0.3 0.3 42.4, 50.0 0.9 0.6 0.3 41.7, 50.0 0.6 0.3 0.3 51.0 0.6 0.3 0.3 *kW is based on 240, 480, or 575 v. CONVENIENCE OUTLET — An optional convenience out- let pro

Summary of the content on the page No. 14

PREMIERLINK™ CONTROL — The PremierLink control- ler is compatible with Carrier Comfort Network® (CCN) devices. This control is designed to allow users the access and ability to change factory-defined settings, thus expanding the function of the standard unit control board. Carrier’s diag- nostic standard tier display tools such as Navigator™ module or Scrolling Marquee can be used with the PremierLink controller. The PremierLink controller (see Fig. 15A and 15B) requires a Carrier electronic the

Summary of the content on the page No. 15

Table 5 — PremierLink™ Sensor Usage OUTDOOR AIR RETURN AIR OUTDOOR AIR RETURN AIR APPLICATION TEMPERATURE SENSOR TEMPERATURE SENSOR ENTHALPY SENSOR ENTHALPY SENSOR Dry Bulb Temperature with PremierLink™* Included — —— — (PremierLink HH79NZ017 requires4-20mA Actuator) Differential Dry Bulb Temperature with Required — PremierLink* Included — 33ZCT55SPT —— (PremierLink HH79NZ017 or Equivalent requires4-20mA Actuator) Single Enthalpy with PremierLink* Included — Required — (PremierLink — — Not Used

Summary of the content on the page No. 16

J6 J5 J4 ANAL OG 0-20mAIN DISCRETE PREMIERLINK CONTROL HINGED DOOR PANEL PREMIERLINK COVER Fig. 15B — PremierLink™ Controller (Installed) BLK VIO RED HK50AA039 TB-2 SAT BLU PNK PNK BRN 7 7 BLK BLU 1 BRN ORN VIO VIO PNK PremierLink 6 6 2 BRN OAT BRN RED 11 11 Space Temp./ Set 3 BLK Point Adjustment BRN 10 BLU 10 BRN 4 YEL GRN 8 8 RED 5 YEL BLU 2 Indoor Air 2 BLU Quality Sensor 6 BRN 3 WHT 3 7 BLU PNK BLK Outdoor Air J7 4 J9 J8 4 J2 Quality Sensor GRA J1 PP/MP 0-20 mA Relays COMMS 8 PWR ORN RED Po

Summary of the content on the page No. 17

C7400A1004 + Enthalpy Sensors and Control — The enthalpy control ENTHALPY CONTROLLER (OUTDOOR S RED (HH57AC077) is supplied as a field-installed accessory to be AIR BRN + ENTHALPY B used with the economizer damper control option. The outdoor TR TR1 BLK A C SENSOR) air enthalpy sensor is part of the enthalpy control. The separate D RED SO + field-installed accessory return air enthalpy sensor S (RETURN AIR SR + (HH57AC078) is required for differential enthalpy control. ENTHALPY + SENSOR) 3 NOTE:

Summary of the content on the page No. 18

OPTIONAL ECONOMI$ER IV AND ECONOMI$ER2 — 4. Swing out indoor coil access panel and insert the hood See Fig. 19 for EconoMi$er IV component locations. See sides under the panel (hood top). Use the screws provided Fig. 20 for EconoMi$er2 component locations. to attach the hood sides to the hood top. Use screws pro- vided to attach the hood sides to the unit. See Fig. 24. NOTE: These instructions are for installing the optional 5. Remove the shipping tape holding the economizer baro- EconoMi$er IV

Summary of the content on the page No. 19

6. Insert the hood divider between the hood sides. See 8. Caulk the ends of the joint between the unit top panel and Fig. 24 and 25. Secure hood divider with 2 screws on the hood top. See Fig. 23. each hood side. The hood divider is also used as the bot- 9. Replace the filter access panel. tom filter rack for the aluminum filter. 10. Install all EconoMi$er IV accessories. EconoMi$er IV 7. Open the filter clips which are located underneath the wiring is shown in Fig. 26. EconoMi$er2 wiring is sho

Summary of the content on the page No. 20

BLACK 4 3 5 BLUE 2 500 OHM RESISTOR 8 VIOLET 6 NOTE 1 PINK 7 RUN RED 1 - NOTE 3 + 10 50HJ540573 ACTUATOR ASSEMBLY 11 OPTIONAL CO2 SENSOR4-20mA OUTPUT 9 WHITE DIRECT DRIVE 12 ACTUATOR ECONOMISER2 PLUG NOTES: 1. Switch on actuator must be in run position for economizer to operate. 2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sensor or HH57A077 enthalpy sensor. 3. 50HJ540573 actuator consists of the 50HJ540567 act


Alternative user manuals
# User manual Category Download
1 Carrier 25HCR3C User manual Heat Pump 48
2 Carrier 10 SEER SPLIT-SYSTEM 38YCW User manual Heat Pump 19
3 Carrier 38AC User manual Heat Pump 10
4 Carrier 38AN,BK User manual Heat Pump 14
5 Carrier 25HCS3C User manual Heat Pump 8
6 Carrier 25HBB User manual Heat Pump 5
7 Carrier 38AQ028 User manual Heat Pump 5
8 Carrier 38BYB User manual Heat Pump 4
9 Carrier 38AQ024 User manual Heat Pump 4
10 Carrier 380B User manual Heat Pump 4
11 Carrier 38AUQ User manual Heat Pump 37
12 Carrier 38AYB User manual Heat Pump 1
13 Carrier 38BYC User manual Heat Pump 4
14 Carrier 38AQ034 User manual Heat Pump 2
15 Carrier 38QB User manual Heat Pump 1
16 Edelbrock 15005 User manual Heat Pump 0
17 A.O. Smith AH User manual Heat Pump 2
18 ACS 882.00217.00 User manual Heat Pump 1
19 A.O. Smith AHD 290 User manual Heat Pump 3
20 AC International SELF-PRIMING CENTRIFUGAL PUMPS User manual Heat Pump 5