Summary of the content on the page No. 1
QUANTUM PLUS 13 SEER
650A (60 Hz)
HEAT PUMP WITH
PURON™ REFRIGERANT
Sizes 024 thru 060
wire dome top results in quieter and more efficient operation.
Energy-Efficient Fan and Fan Motor provide a slower fan
operation, thus reducing noise and improving efficiency.
Sound Hood muffles noise from operation.
Discharge Muffler minimizes low frequency sound and
pressure pulsation generated by compressor discharge gas.
WEATHER-PROTECTIVE CABINET—Steel is galv
Summary of the content on the page No. 2
DIMENSIONS
—2— NOTES: 1. Allow 30 in. clearance to service end of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side,
and 24 in. between units for proper airflow. 2. Minimum outdoor operating ambient in cooling mode is 55°F (unless low ambient control is used) max 125°F. 3. Maximum outdoor operating ambient in heating mode is 66°F. 4. Series designation is the 14th position of the unit model number. 5. Center of gravity . 3 /8 IN. DIA (9.5) TIEDOWN K
Summary of the content on the page No. 3
H T G I N W I G N N O I I Y T L I P D M N O O C A C S R A I R I E S I R A Q T A A U O I N T P RECOMMENDED TUBE DIAMETERS LIQUID TUBE DIAMETER (IN.) VAPOR TUBE DIAMETER (IN.) UNIT 0 to 50 Ft 0 to 50 Ft RST* SIZE Tube Length Alternate Tube Length Alternate (Not Permitted) 024 3/8 3/8 5/8 3/4 ACR 3/4 030 3/8 3/8 3/4 7/8 1-1/8 036 3/8 3/8 3/4 7/8 1-1/8 042, 048 3/8 3/8 7/8 7/8 3/4 and 1-1/8 060 3/8 3/8 1-1/8 7/8 3/4 * RST—Refrigeration Service Tubing, standard refrigerant gra
Summary of the content on the page No. 4
SPECIFICATIONS UNIT SIZE-SERIES 024-A,C 030-A,C 036-A,C Operating Weight (Lb) 214 205 217 ELECTRICAL Unit Volts—Hertz—Phase 208/230—60—1 Operating Voltage Range* 187—253 Compressor Rated Load Amps 15.1 14.7 15.4 Compressor Locked Rotor Amps 61.0 72.5 83.0 Condenser Fan Motor—Full Load Amps 0.8 1.1 1.1 Minimum Unit Ampacity for Wire Sizing 19.7 19.5 20.4 Minimum Wire Size (60°C Copper) (AWG)† 14 14 12 Minimum Wire Size (75°C Copper) (AWG)† 14 14 12 Maximum Wire Length (60°C) (Ft)‡ 3
Summary of the content on the page No. 5
SPECIFICATIONS Continued UNIT SIZE-SERIES 042-A.C 048-A,C 060-B,C Operating Weight (Lb) 218 266 295 ELECTRICAL Unit Volts—Hertz—Phase 208/230—60—1 Operating Voltage Range* 187—253 Compressor Rated Load Amps 21.1 20.5 27.6 Compressor Locked Rotor Amps 104.0 109.0 158.0 Condenser Fan Motor—Full Load Amps 1.1 1.4 1.4 Minimum Unit Ampacity for Wire Sizing 27.5 27.0 35.9 Minimum Wire Size (60°C Copper) (AWG)† 10 10 8 Minimum Wire Size (75°C Copper) (AWG)† 10 10 8 Maximum Wire Length (
Summary of the content on the page No. 6
THERMOSTATS AND ACCESSORIES Thermostat—Auto Changeover, Non-Programmable, °F/°C, 2-Stage Heat, 1-Stage Cool TSTATBBNHP01-B Thermostat—Auto Changeover, 7-Day Programmable, °F/°C, 2-Stage Heat, 1-Stage Cool TSTATBBPHP01-B Thermostat—Auto Changeover, 7-Day Programmable, °F/°C, Dual Fuel, Includes Outdoor Sensor (TSTATXXSEN01) TSTATBBPDF01-B* Thermidistat™ Control—Non-Programmable/Programmable Thermostat with Humidity Control (For use in Dual Fuel, AC, HP, and 2S applications. Includes O
Summary of the content on the page No. 7
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) 1. Compressor Start Assist—Capacitor and Relay Start capacitor and start relay which gives a “hard” boost to compressor motor at each start-up. SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft. Installations where outdoor design temperature exceeds 105°F (40.6°C). Units installed with Low Ambient Pressure Switch. Units installed with Liquid-Line Solenoid Valve. 2. Compressor
Summary of the content on the page No. 8
COMBINATION RATINGS* ARI STANDARD RATINGS* Cooling Heating Seasonal Efficiency SEER Field-Supplied High-Temp Low-Temp Factory- Accessory‡ UNIT Supplied SIZE- INDOOR Enhance- Standard Puron Puron TXV SERIES UNIT CFM†† TC ment Rating TXV & TDR** EER TC COP TC COP HSPF FX4ANF030† 800 25,000 TDR&TXV 13.00 — — 11.10 25,000 3.30 16,600 2.38 8.00 F(A,B)4AN(F,C)030 800 23,600 TDR — 12.50 — 10.95 24,400 3.18 16,500 2.32 7.50 FC4BNF030 800 24,000 TDR — 12.50 — 10.95 24,400 3.18 16,500 2.32 7.50 FK4
Summary of the content on the page No. 9
COMBINATION RATINGS Continued ARI STANDARD RATINGS* Cooling Heating Seasonal Efficiency SEER Field-Supplied High-Temp Low-Temp Factory- Accessory‡ UNIT Supplied SIZE- INDOOR Enhance- Standard Puron Puron TXV SERIES UNIT CFM†† TC ment Rating TXV & TDR** EER TC COP TC COP HSPF CJ5A/CK5A/CK5BA060 1400 45,000 NONE — — 12.50 10.75 48,000 3.50 28,600 2.38 8.20 CJ5A/CK5A/CK5BN060 1400 45,500 NONE — — 13.00 10.90 48,500 3.52 28,600 2.38 8.25 048-A,C CJ5A/CK5A/CK5BX060 1400 45,
Summary of the content on the page No. 10
650A BALANCE POINT WORKSHEET 23.4 80 20.5 70 650AN060-B,C FV4A006 17.6 60 650AN048-A,C FV4A005 650AN042-A,C FV4A003 50 14.7 650AN036-A,C FX4A042 40 11.7 650AN030-A,C FX4A030 650AN024-A,C 30 8.8 FX4A030 20 5.9 10 2.9 BASED ON INDOOR ENT. AIR AT 70˚F AND AT RATED CFM -10 0 10 20 30 40 50 60 70 80 A99002 OUTDOOR TEMPERATURE, ˚F NOTE: The performance shown includes the PressureGuard™ cycling the outdoor fan. The ambient temperature that the outdoor fan cycles depends on the outdoor/indoor combinatio
Summary of the content on the page No. 11
DETAILED COOLING CAPACITIES* CONDENSER ENTERING AIR TEMPERATURES °F EVAP AIR 75 85 95 105 115 125 Capacity Capacity Capacity Capacity Capacity Capacity Total Total Total Total Total Total MBtuh† MBtuh† MBtuh† MBtuh† MBtuh† MBtuh† Sys Sys Sys Sys Sys Sys CFM EWB Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** 650AN024-A,C Outdoor Section , With FX4ANF030 Indoor Section 72 29.7 14.5 1.85 28.4 14.0 2.07 26.9 13.5 2.31 25.4 12.9 2.57 23.
Summary of the content on the page No. 12
DETAILED COOLING CAPACITIES* Continued CONDENSER ENTERING AIR TEMPERATURES °F EVAP AIR 75 85 95 105 115 125 Capacity Capacity Capacity Capacity Capacity Capacity Total Total Total Total Total Total MBtuh† MBtuh† MBtuh† MBtuh† MBtuh† MBtuh† Sys Sys Sys Sys Sys Sys CFM EWB Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** 650AN030-A,C Outdoor Section With FX4ANF030 Indoor Section 72 34.3 17.2 2.07 32.6 16.6 2.31 30.9 15.9 2.58 29.0 1
Summary of the content on the page No. 13
DETAILED COOLING CAPACITIES* Continued CONDENSER ENTERING AIR TEMPERATURES °F EVAP AIR 75 85 95 105 115 125 Capacity Capacity Capacity Capacity Capacity Capacity Total Total Total Total Total Total MBtuh† MBtuh† MBtuh† MBtuh† MBtuh† MBtuh† Sys Sys Sys Sys Sys Sys CFM EWB Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** 650AN042-A,C Outdoor Section With FV4ANF003 Indoor Section 72 48.5 24.4 2.95 46.4 23.6 3.32 44.1 22.8 3.72 41.7 2
Summary of the content on the page No. 14
DETAILED COOLING CAPACITIES* Continued CONDENSER ENTERING AIR TEMPERATURES °F EVAP AIR 75 85 95 105 115 125 Capacity Capacity Capacity Capacity Capacity Capacity Total Total Total Total Total Total MBtuh† MBtuh† MBtuh† MBtuh† MBtuh† MBtuh† Sys Sys Sys Sys Sys Sys CFM EWB Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** Total Sens‡ Kw** 650AN060-B,C Outdoor Section With FV4ANB006 Indoor Section 72 70.1 35.6 4.43 66.6 34.4 4.92 63.1 33.1 5.47 59.2 31.7
Summary of the content on the page No. 15
HEAT PUMP HEATING PERFORMANCE OUTDOOR COIL ENTERING AIR TEMPERATURES °F INDOOR AIR –3 7 172737475767 Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr EDB CFM Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† 650AN024-A,C Outdoor Section With FX4ANF030 Indoor
Summary of the content on the page No. 16
HEAT PUMP HEATING PERFORMANCE Continued OUTDOOR COIL ENTERING AIR TEMPERATURES °F INDOOR AIR –3 7 172737475767 Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr EDB CFM Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† 650AN036-A,C Outdoor Section With FX4ANF042 Indoor
Summary of the content on the page No. 17
HEAT PUMP HEATING PERFORMANCE Continued OUTDOOR COIL ENTERING AIR TEMPERATURES °F INDOOR AIR –3 7 172737475767 Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total Capacity Total MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr MBtuh† Pwr EDB CFM Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† Total Int* Kw† 650AN048-A,C Outdoor Section With FV4ANF005 Indoor Se
Summary of the content on the page No. 18
System Design 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C). 3. Maximum outdoor operating air temperature for cooling mode is 125°F (51.7°C). 4. Minimum outdoor operating air temperature for heating mode is –30°F (–34.4°C). 5. Maximum outdoor operating air temperature for heating mode
Summary of the content on the page No. 19
—19—
Summary of the content on the page No. 20
SERVICE TRAINING Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:
• Unit Familiarization • Maintenance
• Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book.
Classroom Service Training plus "hands-on" the products in our labs can mean