Summary of the content on the page No. 1
INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGE HEAT PUMPS
MODELS
W18H1
W24H1
W30H1
W36H1
W42H1
W48H1
W60H1
Bard Manufacturing Company, Inc.
Manual : 2100-511
Bryan, Ohio 43506
Supersedes: NEW
File: Volume III Tab 17
Since 1914...Moving ahead just as planned.
Date: 10-14-08
Manual 2100-511
© Copyright 2008
Page 1 of 27
Summary of the content on the page No. 2
Contents Start Up Getting Other Information and Publications 3 General .............................................................. 15 Topping Off System Charge................................... 15 Wall Mount General Information Safety Practices..................................................... 15 Wall Mount Model Nomenclature ............................ 4 Important Installer Note ......................................... 16 Shipping Damage ................................................
Summary of the content on the page No. 3
GETTING OTHER INFORMATION AND PUBLICATIONS These publications can help you install the air FOR MORE INFORMATION, CONTACT conditioner or heat pump. You can usually find these at THESE PUBLISHERS: your local library or purchase them directly from the publisher. Be sure to consult current edition of each ACCA Air Conditioning Contractors of America standard. 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 National Electrical Code ...................... ANSI/NFPA 70 Fax
Summary of the content on the page No. 4
WALL MOUNT GENERAL INFORMATION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE W 42 H 1– A 10 X X X X X A CONTROL MODULES REVISIONS MODEL NUMBER (See Spec. Sheet S3397) KW CAPACITY 18 - 1½ Ton VOLTS & PHASE COIL OPTIONS 24 - 2 Ton A - 230/208/60/1 X - Standard COLOR OPTIONS 30 - 2½ Ton B - 230/208/60/3 X - Beige (Standard) 1 - Phenolic Coated Evaporator 36 - 3 Ton C - 460/60/3 2 - Phenolic Coated Condenser 1 - White 42 - 3½ Ton 2 - Mesa Tan 3 - Phenolic Coated Evaporator 48 - 4 Ton and Condenser 4 - Buc
Summary of the content on the page No. 5
DUCT WORK FILTERS All duct work, supply and return, must be properly sized A 1-inch throwaway filter is standard with each unit. for the design airflow requirement of the equipment. Air The filter slides into position making it easy to service. Conditioning Contractors of America (ACCA) is an This filter can be serviced from the outside by removing excellent guide to proper sizing. All duct work or portions the filter access panel. A 1-inch washable filter and 2- thereof not in the conditione
Summary of the content on the page No. 6
INSTALLATION INSTRUCTIONS WALL MOUNTING INFORMATION 1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3. WARNING 2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the Failure to provide the 1/4 inch clearance unit without transmitting any unit vibration. between the supply duct and a combustible 3. Concrete block walls must be thoroughly inspected surface for the first 3 feet of duct can
Summary of the content on the page No. 7
FIGURE 2 Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal) SN UPPLY RETUR WIDTH DEPTH HEIGHT MODEL (W) (D) (H) AB C B E F G I J K L M N O P Q R ST W18H1 35 3.30013 7.1278 0.5678 .818 9.818 1.810 9.830 5.015 8.526 5.725 0.526 6.725 8.020 9.223 7.023 .636 4.125 2.010 0.550 .010 2.0 5.0 W24H1 W30H1 35 8.20013 7.1278 0.5678 .828 7.818 3.820 7.840 0.015 8.523 5.715 7.925 6.725 8.720 9.223 7.023 .635 9.124 2.790 .150 .010 2.0 5.0 W36H1 W42H1 42 2.07525 2.4388 4.8798 .
Summary of the content on the page No. 8
Manual 2100-511 Page 8 of 27 FIGURE 3A W18H1, W24H1 MOUNTING INSTRUCTIONS
Summary of the content on the page No. 9
Manual 2100-511 Page 9 of 27 FIGURE 3B W30H1, W36H1 MOUNTING INSTRUCTIONS
Summary of the content on the page No. 10
Manual 2100-511 Page 10 of 27 FIGURE 3C W42H1, W48H1, W60H1 MOUNTING INSTRUCTIONS
Summary of the content on the page No. 11
FIGURE 4 ELECTRIC HEAT CLEARANCE W30H1, W36H1, W42H1, W48H1, W60H1 SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURFACES. WARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is important to insure that the 1/4 inch minimum spacing is maintained at all points. Failure to do this could result in overheating the combust
Summary of the content on the page No. 12
FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 – MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS, FIGURE 2, FOR ACTUAL DIMENSIONS IF REQUIRED IF REQUIRED Manual 2100-511 Page 12 of 27
Summary of the content on the page No. 13
FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS Manual 2100-511 Page 13 of 27
Summary of the content on the page No. 14
WIRING – MAIN POWER WIRING – LOW VOLTAGE WIRING 230/208V, 1 phase and 3 phase equipment dual primary Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring 240V to 208V tap. The acceptable operating voltage range for the 240 and
Summary of the content on the page No. 15
START UP REMEMBER: When adding R-410A refrigerant, it THESE UNITS REQUIRE R-410A must come out of the charging cylinder/tank as a liquid REFRIGERANT AND POLYOL to avoid any fractionation, and to insure optimal system performance. Refer to instructions for the cylinder that ESTER OIL. is being utilized for proper method of liquid extraction. GENERAL: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A WARNING
Summary of the content on the page No. 16
START UP (Continued) IMPORTANT INSTALLER NOTE PHASE MONITOR For improved start up performance wash the indoor coil All units with three phase scroll compressors are with a dish washing detergent. equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal. HIGH & LOW PRESSURE SWITCH The phase monitor in this unit is equipped with two LEDs. If the Y signal is present at the phase monitor All W**H wall mounted air conditioner series models are supplied with a remote re
Summary of the content on the page No. 17
If some abnormal or temporary condition such as a high SEQUENCE OF OPERATION wind causes the heat pump to have a prolonged defrost COOLING – Circuit R-Y makes at thermostat pulling in cycle, the heat pump control will restore the system to compressor contactor, starting the compressor and heating operation automatically after 10 minutes. outdoor motor. The G (indoor motor) circuit is The heat pump defrost control board has an option of automatically completed on any call for cooling 30, 60 or 9
Summary of the content on the page No. 18
FIGURE 8 DEFROST CONTROL BOARD Manual 2100-511 Page 18 of 27
Summary of the content on the page No. 19
TROUBLESHOOTING SOLID STATE HEAT PUMP CONTROL 4. Set system switch to “heat” or “cool”. Adjust thermostat to call for heat or cool. The indoor TROUBLESHOOTING PROCEDURE blower, compressor and outdoor fan should start. 1. NOTE: A thorough understanding of the defrost cycle sequence is essential. Review that section NOTE: If there was no power to 24 volt transformer, earlier in this manual prior to troubleshooting the the compressor and outdoor fan motor will control. Turn on AC power supply
Summary of the content on the page No. 20
3. Check resistance reading to chart of resistance. Use CHECKING TEMPERATURE SENSOR sensor ambient temperature. (Tolerance of part is OUTSIDE UNIT CIRCUIT ± 10%.) 1. Disconnect temperature sensor from board and from outdoor coil. 4. If sensor resistance reads very low, then sensor is shorted and will not allow proper operation of the 2. Use an ohmmeter and measure the resistance of the heat pump control. sensor. Also use ohmmeter to check for short or open. 5. If sensor is out of tolerance, s