Carrier TP-PAC user manual

User manual for the device Carrier TP-PAC

Device: Carrier TP-PAC
Category: Thermostat
Manufacturer: Carrier
Size: 1.96 MB
Added : 8/25/2013
Number of pages: 64
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Carrier TP-PAC. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Carrier TP-PAC.

For your convenience

If looking through the Carrier TP-PAC user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Carrier TP-PAC on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Carrier TP-PAC to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Carrier TP-PAC User manual - Online PDF
Advertisement
« Page 1 of 64 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Carrier TP-PAC but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Carrier TP-PAC. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

TP-PAC, TP-PHP
TP-NAC, TP-NHP
PerformanceSeries
AC / HP Thermostat
Installation Instructions
A07049 A07048
Programmable Control Non −Programmable Control
Designed and Assembled in the U.S.A.
NOTE: Read the entire instruction manual before starting the installation.
US patents: US7287709 B2, US20080147242 A1, USD582800 SI, US20060165149 A1, US6956463 B2.

Summary of the content on the page No. 2

Summary of the content on the page No. 3

TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 INSTALLATION CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 SYSTEM START −UP AND CHECKOUT . . . . . . . . . . . . . . . . . . . . . . .

Summary of the content on the page No. 4

INTRODUCTION Carrier’s 7 −day, 5/2 −day, 1 −day programmable and non −programmable Performance Series Thermostat Control is a wall −mounted, low −voltage temperature control in either a single unit or a two −piece unit. In two −piece configuration, the relays are located near the equipment and a two −wire connection is used between the Display Module and the Equipment Control Module. Single −piece installation requires more wiring and results in a higher profile. The Edge Thermostat has no need

Summary of the content on the page No. 5

INSTALLATION CONSIDERATIONS Power This control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and C terminals) of the low −voltage transformer to be connected to it for proper operation. It will not operate without these 2 connections. Rh and Rc are connected via PCB breakout jumper. See Fig. 1. For applications using two 24VAC transformers, one in the indoor unit and one in the outdoor unit, connect the common from each to the C terminal. Connect R from the indoor unit to the Rh term

Summary of the content on the page No. 6

A07052 Fig. 1 − PCB Breakout Jumper Models There are programmable and non −programmable models for all applications. They can be configured for AC or HP installations, allowing it to be used in place of all Carrier thermostats. Programmable thermostats may be configured as non −programmable if user desires. Outdoor Temperature Sensor The outdoor air temperature sensor is not included with the AC/HP Control. It is available as an accessory, part number TSTATCCSEN01 −B. Optimum performance is obta

Summary of the content on the page No. 7

dedicated sensor wires may be used for its connection. Details are provided in sensor instructions. Remote Indoor Temperature Sensor A remote temperature sensor may be used with the programmable heat pump and programmable air conditioner thermostats where it is desirable to install the thermostat in a limited access location while measuring the temperature in the living space. The remote room sensor may be used as a stand alone or average with local sensor. Two −Piece Thermostat Configuration Th

Summary of the content on the page No. 8

Wiring Wire length should be no more than 250 ft (76m). Use 22 AWG for normal wiring applications. Continuous wire lengths over 100 ft (30.5m) should use 20 AWG or larger. INSTALLATION Carton contains the following components. See Fig. 2 for programmable models or Fig. 3 for non −programmable models. A07754 Fig. 2 − TP −PAC / TP −PHP Carton Contents 1. Display Module 2. Stand −off for Equipment Control Module 3. Screws and pig tail 4. Equipment Control Module 6

Summary of the content on the page No. 9

A07755 Fig. 3 − TP −NAC / TP −NHP Carton Contents 1. Display Module 2. Stand −off for Equipment Control Module 3. Screws and pig tail 4. Equipment Control Module AC/HP Control Location AC/HP Control should be mounted:  Approximately 5 ft (1.5m) from floor.  Close to or in a frequently used room, preferably on an inside parti- tioning wall.  On a section of wall without pipes or duct work. 7

Summary of the content on the page No. 10

AC/HP Control should NOT be mounted:  Close to a window, on an outside wall, or next to a door leading to the outside.  Exposed to direct light or heat from a lamp, sun, fireplace, or other temperature −radiating objects which could cause a false reading.  Close to or in direct airflow from supply registers and return −air regis- ters.  In areas with poor air circulation, such as behind a door or in an al- cove. Installer should determine whether control will be installed as single −piece or

Summary of the content on the page No. 11

! CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Improper wiring or installation may damage AC/HP Control. Check to make sure wiring is correct before proceeding with installation or turning on power. 1. Turn off all power to equipment. 2. If an existing thermostat is being replaced a. Remove existing thermostat from wall. b. Disconnect wires from existing thermostat, 1 at a time. c. As each wire is disconnected, record wire color

Summary of the content on the page No. 12

Two −Piece Installation The following steps should be followed for the installation of the two −piece configuration. NOTE: The 2 −wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the equipment Control Module screw terminals. 1. Remove mounting plate from back of Display Module by pressing the two tabs on the bottom edge and pulling away. See Fig. 4 and 5. A07225 Fig. 4 − Press Tabs to Remove Backplate 10

Summary of the content on the page No. 13

A07226 Fig. 5 − Take Apart 2. Route wires through large hole in mounting base. Level mounting base against wall (for aesthetic value only—Display Module need not be lev- eled for proper operation) and mark wall through 4 mounting holes. To avoid unintended bending of wall plate plastic, use all 4 screws and an- chors. See Fig. 6. 11

Summary of the content on the page No. 14

A07165 Fig. 6 − Backplate Mounting 3. Drill two 3/16 −in. mounting holes in wall where marked. Thermostat may be mounted to a standard junction box, if desired. Hole pattern on ther- mostat mounting base matches junction box mounting holes. 4. Secure rear plastic mounting base to wall with 4 screws and anchors pro- vided. To avoid unintended bending of wall plate plastic, use all 4 screws and anchors. Make sure all wires extend through hole in mounting base. 5. Adjust length and routing of each

Summary of the content on the page No. 15

Control Module Wiring Gu Control Module Wiring Guide ide Re Rellays ays OAT OAT Rc Rc OA OAT / T / RRS RRS Rh Rh RR RRS S ret retu urn rn { { W / W / W1 W1 SR SRTN TN HUM HUM G G Y u Y us se ed d fo for r sing single st le stage age D1 D1 Y/Y2 Y/Y2 dr dry y cool cooling ing cont contact act D2 D2 C C con conn ne ec ct t V+ V+ O/W O/W2 2/B /B to u to us ser er Vg Vg inter interf fac ace e Y1 Y1 Y1 Y1 u us sed ed f fo or r m mu ult lti-sp i-spee eed d cool cooling ing Y Y1 1 = st = s

Summary of the content on the page No. 16

A07166 Fig. 8 − Secure Wires to Terminal Strip A07167 Fig. 9 − Connect Pigtail Wires to Display Module 14

Summary of the content on the page No. 17

NOTE: The 2 −wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the equipment Control Module screw terminals.  Red is V+  Black is Vg 7. Push any excess wire into wall and against mounting base. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature measurement. 8. Make sure to attach 2 −wire pigtail to Display Module mounting base. It is packed loose in the box from the factory. Then attach

Summary of the content on the page No. 18

10. Find suitable indoor mounting location for Equipment Control Module, either near or on equipment. See Fig. 11. IMPORTANT NOTE: Equipment Control Module should not be mounted to duct work or below any other controls or equipment (i.e. humidistat, humidifier, etc.) A07217 Fig. 11 − Equipment Control Module on Equipment 11. Route wires through rear of Equipment Control Module using either a clearance hole or supplied standoff. See Fig. 12. 16

Summary of the content on the page No. 19

A07227 Fig. 12 − Standoff NOTE: Standoffs are provided as an aid when installing Equipment Control Module on inside equipment or a solid wall. 12. Match and connect equipment wires to proper terminals of each connector block being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the thermostat mounting base. If wires are connected incorrect- ly, the Display Module will not operate. See Fig. 7, 8 and 9. 1

Summary of the content on the page No. 20

A07218 Fig. 13 − Cover on Equipment Control Module 14. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2 −digit code appears on large display which identifies AC/HP Control configuration. Refer to Option 33. a. AC — 1 −stage air conditioner, AC, with furnace or fan coil b. HP — 1 −stage heat pump, HP only with fan coil c. H — heating only system, furnace only or fan coil with electric heat only d. C — cooling only system, AC with fan coil


Alternative user manuals
# User manual Category Download
1 Carrier 33CS250-01 User manual Thermostat 319
2 Carrier 33CSIRRCVR-01 User manual Thermostat 60
3 Carrier 53DFS250-FS User manual Thermostat 43
4 Carrier 33CS450-01 User manual Thermostat 118
5 Carrier 33CS250-FS User manual Thermostat 21
6 Carrier 33CS400-01 User manual Thermostat 76
7 Carrier 48/50TF User manual Thermostat 20
8 Carrier 48/50TJ User manual Thermostat 26
9 Carrier 49004DP21 User manual Thermostat 8
10 Carrier APOLLO CONTROL 48/50HJ004-024 User manual Thermostat 11
11 Carrier 53DFS250-SL User manual Thermostat 15
12 Carrier APOLLO CONTROL 50HJQ004-016 User manual Thermostat 9
13 Carrier AQUAZONE 50QE900 User manual Thermostat 49
14 Carrier APOLLO CONTROL 50TFQ004-012 User manual Thermostat 5
15 Carrier DEBONAIR 33CS User manual Thermostat 54
16 Edelbrock 2116 User manual Thermostat 0
17 A&D MF-50 User manual Thermostat 8
18 A&D ML-50 User manual Thermostat 8
19 A&D MS-70 User manual Thermostat 15
20 Acu-Rite D1523 User manual Thermostat 2