Liebert PanelGuard Extension user manual

User manual for the device Liebert PanelGuard Extension

Device: Liebert PanelGuard Extension
Category: Surge Protector
Manufacturer: Liebert
Size: 1.73 MB
Added : 3/8/2013
Number of pages: 31
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Liebert PanelGuard Extension. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Liebert PanelGuard Extension.

For your convenience

If looking through the Liebert PanelGuard Extension user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Liebert PanelGuard Extension on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Liebert PanelGuard Extension to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Liebert PanelGuard Extension User manual - Online PDF
Advertisement
« Page 1 of 31 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Liebert PanelGuard Extension but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Liebert PanelGuard Extension. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

Surge Protection

For Business-Critical Continuity
Interceptor II, SAD Hybrid Advantage, Type SS, LM, AccuVar,
PowerSure LPM/LPL Series, ATF Series, PanelGuard Extension, AccuGuide Products
Installation, Operation and Maintenance Manual
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
800 877 9222 Phone
(US & Canada Only)
614 888 0246 (Outside U.S.)
614 841 6022 FAX
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
Italy
39 049 9719 111 Phone

Summary of the content on the page No. 2

Liebert Interceptor II Printer S2 2 12/29/06 1:37:53 PM

Summary of the content on the page No. 3

Surge Suppression Systems Items Not Covered By Warranty: LIEBERT SURGE PROTECTIVE DEVICE INSTALLATION, OPERATION AND MAINTENANCE MANUAL TABLE OF CONTENTS UNPACKING AND INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Unpacking and Preliminary Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Summary of the content on the page No. 4

Surge Suppression Systems Surge Suppression Systems Limited Warranty INSTALLATION INSTRUCTIONS The Liebert Surge Protective Devices (SPDs) are high quality, The installer should perform the following steps to assure a high energy surge current diversion systems designed to quality installation. The entire installation manual should be protect sensitive equipment from damaging transient voltage read before starting installation. These instructions do not surges. Proper installation is requir

Summary of the content on the page No. 5

Surge Suppression Systems ELECTRICAL CONNECTIONS Items Not Covered By Warranty: THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY misuse, improper application, wrong or inadequate electrical current or connection, negligence, inappropriate on site operating conditions, corrosive atmosphere, repair by non-Liebert designated personnel, accident All electrical connections should be installed by a qualifi ed The following is from the National Electric Code 2002 Edition. in transit, tampering,

Summary of the content on the page No. 6

Surge Suppression Systems Surge Suppression Systems Limited Warranty VOLTAGE RATINGS AND POWER SOURCE CONFIGURATIONS This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordinary course of each purchaser’s business. Nominal Operating Voltage Model Voltage Code Source Confi gurations Maximum Continuous L-N L-G L-L (Found in part number) General: Single Phase L-N, 2 W + G Liebert Corporation products and systems are in our opinion the fi nest available. We take

Summary of the content on the page No. 7

Neutral Neutral Phases Phases Ground Ground Surge Suppression Systems Surge Suppression Systems Typical Parallel Connections (without Internal Rotary Disconnect) To Protected Loads Neutral Liebert Surge Phase(s) Protective Device Transient Ground Protected Safety Ground Panel Wire should be less than 5 feet and straight as possible Typical Parallel Connections (with Internal Rotary Disconnect) To Protected Loads Neutral Liebert Surge Rotary Phase(s) Protective Disconnect Device Transient Groun

Summary of the content on the page No. 8

Surge Suppression Systems Surge Suppression Systems Example Installations System Grounding and Bonding The performance and safety of any SPD system is dependent on proper grounding and bonding. Grounding is required for safety. Correct implementation also enhances equipment FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF performance. Incorrect grounding can reduce or impede the PROVIDED), MUST BE RELIABLY CONNECTED TO THE SPD’s operation. NEUTRAL OF THE SOURCE. FAILURE TO PROVIDE A RELIABL

Summary of the content on the page No. 9

Surge Suppression Systems Surge Suppression Systems Troubleshooting / Servicing / Maintenance PanelGuard Series — Type LPGE Troubleshooting Corrective Maintenance If status failure indication occurs or Form C relay has changed The Liebert SPD is designed for years of trouble-free operation. Customer states, a qualifi ed electrician shall fi rst determine if the However, even the most reliable equipment may fail under Supplied systems voltage and proper phasing exists. abnormal conditions. Panel

Summary of the content on the page No. 10

1/2” Offset .188 (4X) Conduit Nipple 5.700 Status 5.250 3.500 4.700 Status 3.00 Max. 2.400 Surge Suppression Systems Surge Suppression Systems Typical Parallel Installations PowerSure Low Exposure Series - Type LPL Surge Protective Devices (SPD) Interceptor II Series Hybrid Advantage Series Type SS Series Type LM Series Type SI Type H Phase L1/A Phase L2/B Service Panel Phase L3/C for Loads to be Protected Disconnect/Main PowerSure Medium Exposure Series AccuVar Series PowerSure Low Exposure Ser

Summary of the content on the page No. 11

0.375 6.000 6.750 .31 (4X) 0.500 2.000 3.000 4.000 .31 (4X) Surge Suppression Systems Surge Suppression Systems PowerSure Medium Exposure Series — Type LPM 100-2 7. An ex ternal circuit breaker is not necessary for over-current protection for most units (LPL Units require a 30A or less circuit breaker). However, it is recommended that the SPD be connected in series with a circuit breaker denoted in the tables below (also indicated on the “Dimensional Information” pages in this manual). The SPD

Summary of the content on the page No. 12

(4X) F Surge Suppression Systems Surge Suppression Systems Liebert Active Tracking Filter Series — Type F Type LM Series Surge Protective Device (SPD) Phase L1/A Phase L2/B Service Panel for Phase L3/C Loads to be Protected Disconnect/Main Breaker for Panel Neutral Buss Dedicated E Disconnect C Ground Buss (Optional) Recommended Wire Entrance Installation Instructions 1. Ampacity: The fi lter’s maximum continuous current (Ampere) rating must be greater than or equal to the protected load’s full

Summary of the content on the page No. 13

Surge Suppression Systems Surge Suppression Systems Typical Series Connections for Wye (4 Wire + Ground) or Single Phase (3 Wire + Ground) System Type SS Series Liebert Active Tracking Filter System Service Panel For Loads to be Protected Phase L1 INPUT OUTPUT Phase L2 Phase (s) Phase (s) ’s Disconnect/Main Dedicated Breaker For Disconnect Panel L1 (Optional) Neutral Neutral Neutral To N B (required) N F “Protected” Load (s) Transient G Ground } Ground L2 Safety Neutral Buss Ground A D Service P

Summary of the content on the page No. 14

F Surge Suppression Systems Surge Suppression Systems Active Tracking Filter Series - Type F Liebert PanelGuard Series - Type LPGE Surge Protective Device (SPD) Large Bezel 2.0” Max. (Options) Small Bezel .50” Max. (No Options) A A D Installation Instructions 1. Insure that all power is removed before beginning installation. A qualifi ed licensed electrician shall install all electrical connections 12” 2. The unit is provided in a NEMA 1 rated industrial-use enclosure and should be installed i

Summary of the content on the page No. 15

STATUS (4X) F Surge Suppression Systems Surge Suppression Systems Liebert AccuGuide Series — Type ACG Hybrid Advantage Series — Type H SPD Interconnect Assembly Phase L1/A Phase L2/B Service Panel for Phase L3/C Loads to be Protected Disconnect/Main Breaker for Panel Neutral Buss Dedicated Disconnect Ground Buss (Optional) Installation Instructions 2.625 E C Recommended Wire Max. Entrance All electrical connections shall be installed by a qualifi ed (licensed) electrician. All wiring must comply

Summary of the content on the page No. 16

Surge Suppression Systems Surge Suppression Systems Dimensional Information Connection Interceptor II Series - Type SI The AccuGuide assembly is provided in standard lengths of 5, 8, 10, 12, 15, and 20 feet. Each end of the assembly will include an Summary Alarm Contacts (X2) additional fi ve feet of #10, 8, 6, or 4 AWG pigtails for connection to the service and to the surge protective device (SPD). Gauge of Pin 1 = Normally Open Phase L1/A the pigtail is based on the SPD lug size. See chart b

Summary of the content on the page No. 17

Surge Suppression Systems Surge Suppression Systems Dimensional Information Connection Interceptor II Series - Type SI The AccuGuide assembly is provided in standard lengths of 5, 8, 10, 12, 15, and 20 feet. Each end of the assembly will include an Summary Alarm Contacts (X2) additional fi ve feet of #10, 8, 6, or 4 AWG pigtails for connection to the service and to the surge protective device (SPD). Gauge of Pin 1 = Normally Open Phase L1/A the pigtail is based on the SPD lug size. See chart b

Summary of the content on the page No. 18

STATUS (4X) F Surge Suppression Systems Surge Suppression Systems Liebert AccuGuide Series — Type ACG Hybrid Advantage Series — Type H SPD Interconnect Assembly Phase L1/A Phase L2/B Service Panel for Phase L3/C Loads to be Protected Disconnect/Main Breaker for Panel Neutral Buss Dedicated Disconnect Ground Buss (Optional) Installation Instructions 2.625 E C Recommended Wire Max. Entrance All electrical connections shall be installed by a qualifi ed (licensed) electrician. All wiring must comply

Summary of the content on the page No. 19

F Surge Suppression Systems Surge Suppression Systems Active Tracking Filter Series - Type F Liebert PanelGuard Series - Type LPGE Surge Protective Device (SPD) Large Bezel 2.0” Max. (Options) Small Bezel .50” Max. (No Options) A A D Installation Instructions 1. Insure that all power is removed before beginning installation. A qualifi ed licensed electrician shall install all electrical connections 12” 2. The unit is provided in a NEMA 1 rated industrial-use enclosure and should be installed i

Summary of the content on the page No. 20

Surge Suppression Systems Surge Suppression Systems Typical Series Connections for Wye (4 Wire + Ground) or Single Phase (3 Wire + Ground) System Type SS Series Liebert Active Tracking Filter System Service Panel For Loads to be Protected Phase L1 INPUT OUTPUT Phase L2 Phase (s) Phase (s) ’s Disconnect/Main Dedicated Breaker For Disconnect Panel L1 (Optional) Neutral Neutral Neutral To N B (required) N F “Protected” Load (s) Transient G Ground } Ground L2 Safety Neutral Buss Ground A D Service P


Alternative user manuals
# User manual Category Download
1 Liebert 160 User manual Surge Protector 0
2 Liebert 480 User manual Surge Protector 0
3 Liebert 100 - 2 User manual Surge Protector 0
4 Liebert F277Y800-03 User manual Surge Protector 0
5 Liebert AccuVar User manual Surge Protector 2
6 Liebert H User manual Surge Protector 0
7 Liebert 25 - 2 User manual Surge Protector 0
8 Liebert II User manual Surge Protector 1
9 Liebert Interceptor H2120Y444R-03 User manual Surge Protector 0
10 Liebert 277 User manual Surge Protector 0
11 Liebert 350-500 VA User manual Surge Protector 1
12 Liebert Integrated Secured Protection User manual Surge Protector 0
13 Liebert Interceptor II User manual Surge Protector 0
14 Liebert ATF Series User manual Surge Protector 3
15 Liebert 700VA User manual Surge Protector 1
16 Edelbrock 2101 User manual Surge Protector 1
17 Adcom ACE-615 User manual Surge Protector 0
18 Acoustic Research PW100 User manual Surge Protector 0
19 Alesis 7-51-0265-A User manual Surge Protector 2
20 Amtrol SPT-18 User manual Surge Protector 26