Carrier 40RMS user manual

User manual for the device Carrier 40RMS

Device: Carrier 40RMS
Category: Air Cleaner
Manufacturer: Carrier
Size: 0.5 MB
Added : 4/8/2013
Number of pages: 44
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Carrier 40RMS. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Carrier 40RMS.

For your convenience

If looking through the Carrier 40RMS user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Carrier 40RMS on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Carrier 40RMS to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Carrier 40RMS User manual - Online PDF
Advertisement
« Page 1 of 44 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Carrier 40RMS but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Carrier 40RMS. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

40RM
40RMQ
40RMS
Packaged Air-Handling Units
50/60 Hz
Installation, Start-Up and
Service Instructions
filters.All other operations should be performed by trained
CONTENTS
service personnel.
Page
When working on the equipment, observe precautions in
SAFETY CONSIDERATIONS ................. 1
theliteratureandontags,stickers,andlabelsattachedtothe
PRE-INSTALLATION ........................ 1
equipment.
Moving and Storage ........................ 1
•Follow all safety codes.
Rigging ....................

Summary of the content on the page No. 2

Table 1A — 40RM Physical Data, English UNIT 40RM 007 008 012 014 016 024 028 034 1 1 NOMINAL CAPACITY (Tons) 67⁄2 10 12 ⁄2 15 20 25 30 OPERATING WEIGHT (lb) Base Unit with TXV 381 385 405 670 685 690 1020 1030 Plenum 97 97 97 140 140 140 180 180 FANS Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15 2...15 2...18 2...18 Nominal Airflow (cfm) 2400 3000 4000 5000 6000 8,000 10,000 12,000 1800- 2250- 3000- 3750- 4500- 6,000- 7,500- 9,000- Airflow Range (cfm) 3000 3750 5000 6250 7500 10,000 12,500

Summary of the content on the page No. 3

Table 1B — 40RMQ Physical Data, English UNIT 40RMQ 008 012 016 1 NOMINAL CAPACITY (Tons) 7 ⁄2 10 15 OPERATING WEIGHT (lb) Base Unit with TXV 385 427 713 Plenum 97 97 140 FANS Qty...Diam. (in.) 1...15 1...15 2...15 Nominal Airflow (cfm) 3000 4000 6000 Airflow Range (cfm) 2250-3750 3000-5000 4500-7500 Nominal Motor Hp (Standard Motor) 208/230-1-60 2.4 — — 208/230-3-60 and 460-3-60 2.4 2.4 3.7 575-3-60 2.0 2.0 3.0 230-3-50, 400-3-50 2.4 2.9 2.9 Motor Speed (rpm) 208/230-1-60 1725 — — 208/230-3-60 and

Summary of the content on the page No. 4

Table 1C — 40RMS Physical Data, English UNIT 40RMS 008 010 012 014 016 024 028 034 1 1 1 NOMINAL CAPACITY (Tons) 7 ⁄2 8 ⁄2 10 12 ⁄2 15 20 25 30 OPERATING WEIGHT (lb) Base Unit 390 391 391 661 677 683 1035 1042 Plenum 97 97 97 140 140 140 180 180 FANS Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15 2...15 2...18 2...18 Nominal Airflow (cfm) 3000 3400 4000 5000 6000 8000 10,000 12,000 Airflow Range (cfm) 2250-3750 2250-4250 3000-5000 3750-6250 4500-7500 6000-10,000 7500-12,500 9000-15,000 Nomin

Summary of the content on the page No. 5

Table 1D — 40RM Physical Data, SI UNIT 40RM 007 008 012 014 016 024 028 034 NOMINAL CAPACITY (kW) 21 26 35 43 52 70 87 105 OPERATING WEIGHT (kg) Base Unit with TXV 173 175 184 304 311 313 463 467 Plenum 44 44 44 63 63 63 82 82 FANS Qty...Diam. (mm) 1...381 1...381 1...381 2...381 2...381 2...381 2...457 2...457 Nominal Airflow (L/s) 1133 1604 1888 2360 2831 3775 4719 5663 Airflow Range (L/s) 850-1416 1203-2006 1416-2360 1770-2949 2124-3539 2831-4719 3539-5899 4247-7079 Nominal Motor kW (Standard M

Summary of the content on the page No. 6

Table 1E — 40RMQ Physical Data, SI UNIT 40RMQ 008 012 016 NOMINAL CAPACITY (kW) 26 35 52 OPERATING WEIGHT (kg) Base Unit with TXV 175 194 323 Plenum 44 44 63 FANS Qty...Diam. (mm) 1...381 1...381 2...381 Nominal Airflow (L/s) 1604 1888 2831 Airflow Range (L/s) 1203-2006 1416-2360 2124-3539 Nominal Motor kW (Standard Motor) 208/230-1-60 1.79 — — 208/230-3-60 and 460-3-60 1.79 1.79 2.76 575-3-60 1.49 1.49 2.24 230-3-50, 400-3-50 1.79 2.16 2.16 Motor Speed (r/s) 208/230-1-60 28.8 — — 208/230-3-60 and

Summary of the content on the page No. 7

Table 1F — 40RMS Physical Data, SI UNIT 40RMS 008 010 012 014 016 024 028 034 NOMINAL CAPACITY (kW) 26 29 35 43 52 70 87 105 OPERATING WEIGHT (kg) Base Unit 177 177 177 300 307 310 469 473 Plenum 44 44 44 63 63 63 82 82 FANS Qty...Diam. (mm) 1...381 1...381 1...381 2...381 2...381 2...381 2...457 2...457 Nominal Airflow (L/s) 1416 1605 1888 2360 2831 3775 4719 5663 1062- 1204- 1416- 1770- 2124- 2831- 3539- 4247- Airflow Range (L/s) 1770 2006 2360 2949 3539 4719 5899 7079 Nominal Motor kW (Standard

Summary of the content on the page No. 8

TXV — Thermostatic Expansion Valve NOTES: 1. Dimensions in [ ] are in millimeters. 2. Direction of airflow. 3. Recommended clearance: •Rear: 3 in. (76 mm ) •Front: 2 ft, 6 in. (762 mm) •Right Side: 2 ft, 6 in. (762 mm) •Left Side: 2 ft, 6 in. (762 mm) •Local codes or jurisdiction may prevail. 4. Liquid piping not supplied by Carrier. 5. Duct flange is factory supplied and field installed. 6. 40RMSunitsmayrequirealternateorad- ditionalfield-fabricatedpipingaccessholes. UNIT WEIGHT UNIT lb (kg) 40RM00

Summary of the content on the page No. 9

TXV — Thermostatic Expansion Valve NOTES: 1. Dimensions in [ ] are in millimeters. 2. Direction of airflow. 3. Recommended clearance: •Rear: 3 in. (76 mm) •Front: 2 ft, 6 in. (762 mm) •Right Side: 2 ft, 6 in. (762 mm) •Left Side: 2 ft, 6 in. (762 mm) •Local codes or jurisdiction may prevail. 4. Liquid piping not supplied by Carrier. 5. Duct flange is factory supplied and field installed. 6. 40RMQ016 and 40RMS units may re- quirealternateoradditionalfield-fabricated piping access holes. UNIT WEIGHT

Summary of the content on the page No. 10

UNIT WEIGHT UNIT lb (kg) 40RM028 1020 (463) 40RM034 1030 (467) 40RMS028 1035 (469) 40RMS034 1042 (473) TXV — Thermostatic Expansion Valve NOTES: 1. Dimensions in [ ] are in millimeters. 2. Direction of airflow. 3. Recommended clearance: •Rear: 3 in. (76 mm) •Front: 2 ft, 6 in. (762 mm) •Right Side: 2 ft, 6 in. (762 mm) •Left Side: 2 ft, 6 in. (762 mm) •Local codes or jurisdiction may prevail. 4. Liquid piping not supplied by Carrier. 5. Ductflangeisfactorysuppliedandfield installed. 6. 40RMSunitsm

Summary of the content on the page No. 11

*YC and WD option codes for all 034 size units and 008, 010 units with 208/230-1-60 power designate standard motor and high-static drive. NOTE: See the following table for the sizes available for each unit. UNIT 007 008 010 012 014 016 024 028 034 40RM XX XXXXXX 40RMQ XXX 40RMS XXXXXXXX Fig. 2 — Model Number Nomenclature Unit Positioning — The unit can be mounted on the floorforverticalapplicationwithreturnairenteringtheface oftheunitandsupplyairdischargingverticallythroughthe top of the unit. Th

Summary of the content on the page No. 12

Unit Isolation — Where extremely quiet operation is RefrigerantPiping— SeeTables1A,1B,1D,1Efor essential, install isolators between floor and base of unit, or refrigerant pipe connection sizes. For ease in brazing, it is between ceiling and top section of unit. recommended that all internal solder joints be made before unit is placed in final position. Be sure that unit is level and adequately supported. Use channelsatfrontandsidesofunitforreferencepointswhen The 40RM and 40RMQ direct-expansion un

Summary of the content on the page No. 13

IMPORTANT: Neverattachthesensortothesuction manifold.DoNOTmountthesensoronatrappedpor- tion of the suction line. 40RMSeriesevaporatorcoilshaveaface-splitdesign.En- sure that lower circuit of coil is first on/last off when con- nected to the condensing unit and/or system controls. See Fig. 6. ExternalTXVequalizerconnectionsareprovidedandfactory- brazed into the coil suction manifolds. If suction line must be horizontal, clamp bulb to suction line at least 45 degrees above bottom, at approximately

Summary of the content on the page No. 14

Table 2 — Factory-Installed Nozzle and Distributor Data FEEDER TUBES TXV DISTRIBUTOR NOZZLE UNIT PER DISTRIBUTOR* Qty...Part No. Qty...Part No. Qty...Part No. Qty...Size (in.) 40RM007 1...XVE-5 1...1116 12 1...E5 40RM008 1...SVE-8 1...1126 15 1...C6 40RMQ008 1...SVE-8 1...1657 15 1...C6 40RM012 2...XVE-4 2...1115 9 2...E4 40RMQ012 2...XVE-4 2...1655 9 2...E4 40RM014 2...XVE-5 2...1115 9 2...E5 40RM016 2...XVE-8 2...1116 12 2...E6 40RMQ016 2...SVE-8 2...1126 16 2...C6 40RM024 2...XVE-10 2...1116

Summary of the content on the page No. 15

Table 3 — Fitting Requirements ACCESS CONNECTION FITTINGS REQUIRED† UNIT CIRCUIT HOLE NO.* TYPE (in.) 1 1 ⁄8 Street Elbow 1 5 1 Suction — 1 ⁄8 Nipple, 10 ⁄8 L 1 1 ⁄8 Long Radius Elbow 40RM 5 007 ⁄8 Street Elbow 5 5 3 Liquid — ⁄8 Nipple, 8 ⁄8 L 5 ⁄8 Long Radius Elbow 1 1 ⁄8 Street Elbow 1 5 1 Suction — 1 ⁄8 Nipple, 8 ⁄8 L 40RM 1 1 ⁄8 Long Radius Elbow 40RMQ 5 ⁄8 Street Elbow 008 5 5 3 Liquid — ⁄8 Nipple, 8 ⁄8 L 5 ⁄8 Long Radius Elbow 3 3 1 ⁄8 Nipple, 4 ⁄8 L 3 1 ⁄8 Long Radius Elbow 4 Return — 3 3

Summary of the content on the page No. 16

Table 3 — Fitting Requirements (cont) ACCESS CONNECTION FITTINGS REQUIRED† UNIT CIRCUIT HOLE NO.* TYPE (in.) 1 1 ⁄8 Street Elbow 1 3 1 Suction Lower 1 ⁄8 Nipple, 2 ⁄4 L 1 1 ⁄8 Long Radius Elbow 5 ⁄8 Street Elbow 5 3 2 Liquid Lower ⁄8 Nipple, 1 ⁄8 L 5 ⁄8 Long Radius Elbow 40RM 5 ⁄8 Street Elbow 016 5 1 3 Liquid Upper ⁄8 Nipple, 11 ⁄2 L 5 ⁄8 Long Radius Elbow 1 5 1 ⁄8 Nipple, 5 ⁄8 L 1 1 ⁄8 Long Radius Elbow 4 Suction Upper 1 1 ⁄8 Nipple, 13 L 1 1 ⁄8 Long Radius Elbow 1 1 ⁄8 Nipple, 3 L 3 Suction L

Summary of the content on the page No. 17

Table 3 — Fitting Requirements (cont) ACCESS CONNECTION FITTINGS REQUIRED† UNIT CIRCUIT HOLE NO.* TYPE (in.) 1 2 ⁄8 Long Radius Elbow 1 1 5 Supply Lower 2 ⁄8 Nipple, 3 ⁄2 L 1 2 ⁄8 Long Radius Elbow 1 2 ⁄8 Long Radius Elbow 1 6 Return Lower 2 ⁄8 Nipple, 3 L 1 2 ⁄8 Long Radius Elbow 40RMS 1 028, 034 2 ⁄8 Long Radius Elbow 1 7 7 Return Upper 2 ⁄8 Nipple, 6 ⁄8 L 1 2 ⁄8 Long Radius Elbow 1 2 ⁄8 Long Radius Elbow 1 7 8 Supply Upper 2 ⁄8 Nipple, 11 ⁄8 L 1 2 ⁄8 Long Radius Elbow 3 1 ⁄8 Street Elbow 3 1

Summary of the content on the page No. 18

outlet at both ends of the unit, push drain pan down in CondensateDrain— Installatrappedcondensatedrain the slots near the drain connection, and up in the slots line to unit connection as shown in Fig. 10. The unit drain on the opposite end. Retighten screws. The pan should connection is a PVC stub. See Fig. 11. Some areas may re- 1 haveapitchofatleast ⁄4-in.overitslengthtowardthedrain quire an adapter to connect to either galvanized steel or connection. copper pipe. For these applications, inst

Summary of the content on the page No. 19

21 22 23 230-v,3-ph,60Hzoperation.Rewirethemotoraccordingto Power Supply and Wiring — Check the unit data thediagramplateonthemotor.Afterreconfiguringthemo- plate to ensure that available power supply matches electri- tor,placethestickerspecifying230-voperation(suppliedin calcharacteristicsoftheunit.Provideadisconnectswitchof installation packet) over the 460-v sticker on the units cor- sizerequiredtoprovideadequatefanmotorstartingcurrent. ner post. See Tables4-6for unit electrical data. Fan moto

Summary of the content on the page No. 20

Table 4 — Electrical Data, Standard Motors FAN MOTOR POWER SUPPLY VOLTAGE UNIT V*-PH-HZ Minimum LIMITS Hp FLA MOCP Circuit Amps 208/230-1-60 187-253 1.3 7.6 9.5 15 208/230-3-60 187-253 2.4 5.8 7.3 15 460-3-60 414-528 2.4 2.6 3.3 15 40RM 007 575-3-60 518-632 1.0 1.35 1.7 15 230-3-50 207-253 2.4 5.8 7.3 15 400-3-50 360-440 2.4 2.6 3.3 15 208/230-1-60 187-253 2.4 11.0 13.8 20 208/230-3-60 187-253 2.4 5.8 7.3 15 40RM 460-3-60 414-528 2.4 2.6 3.3 15 40RMQ 40RMS 575-3-60 518-632 2.0 2.4 3.0 15 008 230


Alternative user manuals
# User manual Category Download
1 Carrier 31MC User manual Air Cleaner 89
2 Carrier 31KAX User manual Air Cleaner 12
3 Carrier 40RM User manual Air Cleaner 126
4 Carrier 31MM User manual Air Cleaner 5
5 Carrier INFINITY 1625 User manual Air Cleaner 3
6 Carrier 40RMQ User manual Air Cleaner 4
7 Carrier INFINITY 2420 User manual Air Cleaner 0
8 Carrier INFINITY 2025 User manual Air Cleaner 6
9 Carrier INFINITY 2020 User manual Air Cleaner 3
10 Carrier INFINITY 1620 User manual Air Cleaner 1
11 Carrier 31MP User manual Air Cleaner 2
12 Carrier 120-60-1 User manual Air Cleaner 4
13 Carrier 40RMS User manual Heat pumps 0
14 Sony PK-HS1FL User manual Air Cleaner 1920
15 Sony PK-R1FL User manual Air Cleaner 11
16 Philips AC4053 User manual Air Cleaner 30
17 Philips AC4002/00 User manual Air Cleaner 13
18 Philips AC4055 User manual Air Cleaner 9