Summary of the content on the page No. 1
Model CSV
Vertical R-410A
Air Conditioning Units
Supersedes: 145.15-IOM7 (312) Form 145.15-IOM7 (412)
MODEL CSV060B-240B
VERTICAL R-410A
WATER COOLED AIR CONDITIONING UNITS
INSTALLATION INSTRUCTIONS
B Style
Summary of the content on the page No. 2
FORM 145.15-IOM7 (412) IMPORTANT! READ BEFORE PROCEEDING! GENERAL SAFETY GUIDLINES This equipment is a relatively complicated apparatus. which it is situated, as well as sever personal injury or During installation, operation, maintenance or service, death to themselves and people at the site. individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, oils, This document is intended for use by owner-authorized materials under press
Summary of the content on the page No. 3
FORM 145.15-IOM7 (412) CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls policy for continu- It is the responsibility of operating/service personnel as ous product improvement, the information contained in to the applicability of these documents to the this document is subject to change without notice. equipment in question. If there is any question in the While Johnson Controls makes no commitment to up- mind of operating/service personnel as to the date or provide cur
Summary of the content on the page No. 4
FORM 145.15-IOM7 (412) GENERAL INFORMATION All models are shipped as factory-charged unitized To ensure safe installation of the unit when ceiling mount application is specified, estimate the packages. All models are designed for freestanding mounting on the floor, or on a field fabricated approximate center of gravity of the unit. The configuration of internal components for each unit is structural steel stand. All models are shipped with vertical evaporator fan discharge as sta
Summary of the content on the page No. 5
FORM 145.15-IOM7 (412) UNIT MOUNTING - Use appropriate tubing couplings and splice The 5 ~ 20 ton models are shipped as a fully previously cut refrigerant lines. Pressure test assembled integral package. If required units may be refrigerant circuits with dry nitrogen (500 psig). field split to allow for passage through doors, elevators, hallways, etc. - Evacuate each circuit to at least 350 microns. If gauge pressure rises above 500 microns in one Duct flanges for evaporato
Summary of the content on the page No. 6
FORM 145.15-IOM7 (412) CSV060 DIMENSIONAL DATA 6 JOHNSON CONTROLS
Summary of the content on the page No. 7
FORM 145.15-IOM7 (412) CSV096-120 DIMENSIONAL DATA JOHNSON CONTROLS 7
Summary of the content on the page No. 8
FORM 145.15-IOM7 (412) CSV180 DIMENSIONAL DATA 8 JOHNSON CONTROLS
Summary of the content on the page No. 9
FORM 145.15-IOM7 (412) CSV240 DIMENSIONAL DATA JOHNSON CONTROLS 9
Summary of the content on the page No. 10
FORM 145.15-IOM7 (412) DUCTWORK When installing ductwork, adhere to local Codes and - Remove the panel attachments screws on the sensible practice. Minimize duct runs and avoid abrupt blower outlet mounting panel. Do not remove changes in direction where possible. Allow ample fasteners securing blowers to panel! The blowers access space for servicing of the coils and changing are to remain attached to the mounting panel at all of filters. Perform regular maintenance on ducts to time
Summary of the content on the page No. 11
FORM 145.15-IOM7 (412) ELECTRICAL WIRING Provide individual power disconnects for each unit. Follow local electrical codes when making electrical Install a secure ground to the bonding lug located in connections. Units are completely factory wired for the electrical control panel. If canvas flexible joints are normal supply voltages (ie.208-230, 460, used on ductwork, install a ground wire to the 575V/3Ph/60Hz) Confirm unit specifications by ductwork as well. checking unit data
Summary of the content on the page No. 12
FORM 145.15-IOM7 (412) TYPICAL WIRING SCHEMATIC 12 JOHNSON CONTROLS
Summary of the content on the page No. 13
FORM 145.15-IOM7 (412) JOHNSON CONTROLS 13
Summary of the content on the page No. 14
FORM 145.15-IOM7 (412) 14 JOHNSON CONTROLS
Summary of the content on the page No. 15
FORM 145.15-IOM7 (412) JOHNSON CONTROLS 15
Summary of the content on the page No. 16
FORM 145.15-IOM7 (412) ELECTRICAL DATA ELECTRICAL DATA - STANDARD EVAPORATOR MOTOR EVAPORATOR MAX FUSE / MIN. CCT. COMPRESSOR FAN VOLTAGE CCT. BKR. MODEL # AMPACITY AMP QTY RLA LRA HP FLA CSV060B2 208-230/3/60 1 @ 16.0 110.0 1.00 3.1 23.10 35 CSV060B4 460/3/60 1 @ 7.8 52.0 1.00 1.5 11.25 15 CSV060B5 575/3/60 1 @ 5.7 38.9 1.00 1.2 8.33 15 CSV096B2 208-230/3/60 2 @ 13.1 83.1 1.50 4.5 33.98 45 CSV096B4 460/3/60 2 @ 6.1 41.0 1.50 2.2 15.93 20 CSV096B5 575/3/60 2 @ 4.
Summary of the content on the page No. 17
FORM 145.15-IOM7 (412) FAN PERFORMANCE CSV060B SUPPLY AIR BLOWER PERFORMANCE AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹ SUPPLY 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1600 645 0.29 733 0.36 814 0.43 888 0.50 958 0.57 1024 0.64 1087 0.72 1154 0.83 1211 0.91 1245 0.99 1800 708 0.40 788 0.48 863 0.55 933 0.63 999 0.71 1061 0.79 1121 0.87 1178 0.95 1233 1.04 1295 1.17 2000 763 0.52 837 0.61 907 0.6
Summary of the content on the page No. 18
FORM 145.15-IOM7 (412) CSV180B SUPPLY AIR BLOWER PERFORMANCE AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹ SUPPLY 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 4800 634 1.20 697 1.42 757 1.62 813 1.84 867 2.06 918 2.30 968 2.52 1015 2.76 1065 3.02 1109 3.32 5400 701 1.66 758 1.90 812 2.14 864 2.38 914 2.62 962 2.88 1009 3.12 1053 3.38 1097 3.66 1139 3.92 6000 765 2.22 817 2.48 867 2.74 916 3.00 962 3.28 10
Summary of the content on the page No. 19
FORM 145.15-IOM7 (412) MOTOR AND PULLEY DATA EVAPORATOR-STANDARD BLOWER MOTOR AND DRIVE DATA Adjustable Fixed Motor Belts Motor Pulley Blower Pulley Drive Model Range Pitch Pitch Frame Eff. Browning Browning (RPM) Dia. Dia. HP Rating/Size Size (%) (in) Part No. (in) Part No. CSV060B 745-1117 1 145 88.5 1.9-2.9 1VP34X7/8 4.7 AK49H A29 CSV096B 614-921 1.5 145 88.5 1.9-2.9 1VP34X7/8 5.7 AK59H AX35 CSV120B 711-984 2 145 88.5 2.4-3.4 1VP40X7/8 6.4 AK66H AX37 CSV180B 724-925 3
Summary of the content on the page No. 20
FORM 145.15-IOM7 (412) BLOWER SPEED ADJUSTMENT The RPM of the supply air and condenser air blowers will depend on the required CFM, and the static resistances of both the supply/discharge and the return/intake duct systems. With this information, the RPM for the blowers can be determined from the blower performance tables. Adjustment of blower speed is accomplished as follows: 1) Loosen belt tension by moving motor towards the blower shaft via the adjustable mounting. 2) Loosen t