Heat Recovery
Ventilators
HRV-150 • HRV-150D
HRV-200 • HRV-200D • HRV-300D
IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT
CAUTION - Before installation, careful consideration must be given to how this system will operate if connected to any other piece of mechanical equip-
ment, i.e. a forced air furnace or air handler, operating at a higher static. After installation, the compatibility of the two pieces of equipment must be confirmed
by measuring the airflow’s of the Heat R
Summary of the content on the page No. 2
TABLE OF CONTENTS TECHNICAL DATA HRV(D) Series .................................................................................................. 3 HRV Series ...................................................................................................... 5 HRV-300D.................................................................................................... ...7 OPERATION............................................................................................................11 Mo
Summary of the content on the page No. 3
HRV Series HRV 150D & HRV 200D SPECIFICATIONS CASE 22 gauge galvanized steel on the HRV-200D & 24 gauge galvanized steel on the HRV 150D. Baked powder coated paint. Insulated with 1" (25 mm) high density polystyrene foam to prevent condensation and meet the requirements of the Underwriters Laboratories 94HF. MOTORS Two (2) German-manufactured, factory-balanced ebm™ motors with backward curved blades. Motors come with permanently lubricated sealed bearings guarantee long life and maintenance-free
Summary of the content on the page No. 4
HRV-150D & HRV-200D Dimensions TH 5 port for recirculation defrost type models only E 6" A B CD Model A B C D E HRV-150D 2 ¹⁄₄" (56mm) 23 ¹⁄₂" (596mm) 2 ⁵⁄₈" (67mm) 17 ³⁄₈" (441mm) 17 ³⁄₈" (441mm) HRV-200D 2 ¹⁄₄" (56mm) 27 ⁷⁄₈" (707mm) 2 ⁵⁄₈" (67mm) 17 ³⁄₈" (441mm) 20 ¹⁄₂" (520mm) Fan Performance Performance Data Airflow (L/s) 0 19 38 57 76 94 114 1.2 300 Apparent Sensible Apparent Sensible Effectiveness at Effectiveness at - 1 250 Model 32ºF (0ºC) 13ºF (-25ºC) SHR(D) 2005R HRV-200D 0.8 200
Summary of the content on the page No. 5
HRV Series HRV 150 & HRV 200 SPECIFICATIONS CASE 22 gauge galvanized steel on the HRV-200 & 24 gauge galvanized steel on the HRV-150. Baked powder coated paint. Insulated with 1" (25 mm) high density polystyrene foam to prevent condensation and meet the requirements of the Underwriters Laboratories 94HF. MOTORS Two (2) German-manufactured, factory-balanced ebm™ motors with backward curved blades. Motors come with permanently lubricated sealed bearings guarantee long life and maintenance-free ope
Summary of the content on the page No. 6
HRV-150 & HRV-200 Dimensions E 6" B D A C Model A B C D E HRV-150 2 ¹⁄₄" (56mm) 23 ¹⁄₂" (596mm) 2 ⁵⁄₈" (67mm) 17 ³⁄₈" (441mm) 16 ¹⁄₈" (413mm) HRV-200 2 ¹⁄₄" (56mm) 27 ⁷⁄₈" (707mm) 2 ⁵⁄₈" (67mm) 17 ³⁄₈" (441mm) 20 ¹⁄₂" (520mm) Fan Performance Performance Data Airflow (L/s) 0 19 38 57 76 94 114 1.2 300 Apparent Sensible Apparent Sensible Effectiveness at Effectiveness at - Model 1 250 32ºF (0ºC) 13ºF (-25ºC) SHR 2004 HRV-200 0.8 200 HRV-150 72 % 69 % HRV-200 71 % 76 % 0.6 150 AIRFLOW CAP. cfm (L/s
Summary of the content on the page No. 7
HRV Series HRV-300D SPECIFICATIONS CASE 22 gauge galvanized steel. Baked powder coated paint. Insulated with 1" (25 mm) high density polystyrene foam to prevent condensation and meet the requirements of the Underwriters Laboratories 94HF. MOTORS Two (2) German-manufactured, factory-balanced ebm™ motors with backward curved blades. Motors come with permanently lubricated sealed bearings guarantee long life and maintenance-free operation. Seven (7) year limited warranty.* CORES Two (2) aluminum he
Summary of the content on the page No. 8
HRV-300D Dimensions TH 5 port for recirculation defrost type models only 22.20" 564mm 6" 2.20" 50.87" 2.20" 17.36" 56mm 1292mm 56mm 441mm Fan Performance Performance Data Airflow (L/s) 0.00 19.00 38.00 57.00 76.00 94.00 114.00 123.00 142.00 162.00 1.2 300.00 Apparent Sensible Apparent Sensible Effectiveness at Effectiveness at - 1 250.00 Model 32ºF (0ºC) 13ºF (-25ºC) 0.8 200.00 HRV SHR3005R -300D HRV-300D 92 % 91 % 0.6 150.00 AIRFLOW CAP. cfm (L/s) @ 0.4 on High Speed 0.4 100.00 0.2 50.00 Power
Summary of the content on the page No. 9
OPERATION A Heat Recovery Ventilator (HRV) is designed to bring fresh air into a building while exhausting an equal amount of stale air. During the winter months, the incoming cold fresh air is warmed by utilizing the heat recovered from the stale air before it is exhausted to the outdoors. During summer months when the indoor space is air conditioned, the HRV will help in cooling the incoming fresh air with the stale air that is being exhausted. Our HRV’s are designed to run continuous or on in
Summary of the content on the page No. 10
OPERATION (CONT'D) * All controls are low voltage. 18 to 24 OPTIONAL REMOTE CONTROLS gauge wire is recommended. PRACTICAL TIPS Dehumidistat - MD-2W - The wall mount dehumidistat monitors the humidity level in the area it is installed. When the humidity level rises above the To avoid window condensation: desired set-point, the HRV will activate to high speed/override mode. Once • It is not necessary to the humidity level returns to desired condition, the unit will return to the change the humidit
Summary of the content on the page No. 11
OPERATION (CONT'D) OPTIONAL DIGITAL CONTROL DIGITAL DISPLAY DEHUMIDISTAT CONTROL Shows Indoor Humidity Level A Dehumidistat is ideal for use in energy efficient houses where This control will not read below indoor humidity (during the heating season) is higher than outdoor 29% RH levels. High humidity is a major cause of structure damage and IAQ problems such as mold and mildew. OVERRIDE TIMER DMFC When pressed, unit will DIGITAL MULTI-FUNCTION provide high speed WALL CONTROL ventilation for
Summary of the content on the page No. 12
INSTALLATION PRACTICAL TIPS LOCATION The HRV must be located in a heated space where it will be possible to conveniently service the unit. Typically the HRV would be located in the mechanical room or an area close to the outside • Install the unit close to wall where the weatherhoods will be mounted. If a basement area is not convenient or does not the outside wall on exist, a utility or laundry room may be used. which the supply and Attic installations are not normally recommended due to: e
Summary of the content on the page No. 13
INSTALLING DUCTS GOING TO / FROM OUTSIDE A well designed and installed ducting system will allow the HRV to operate at its maximum efficiency. Always try to keep duct runs as short and straight as possible. See Installation Diagrams for installation examples. INSTALLING THE DUCTING PRACTICAL TO THE WEATHERHOODS TIPS The inner liner of the flexible insulated duct •Decide where your intake and must be clamped to the sleeve of the weath- exhaust hoods will be located. erhoods (as close to the ou
Summary of the content on the page No. 14
INSTALLING DUCTS TO / FROM INSIDE To maximize airflow in the ductwork system, all ducts should be kept short and have as few bends or elbows as possible. Forty-five degree are preferred to 90º elbows. Use “Y” tees instead of 90º elbows whenever possible. All duct joints must be fastened with screws or duct sealant and wrapped with a quality duct tape to prevent leakage. Aluminum foil duct tape is recommended. Galvanized ducting from the HRV to the living areas in the house is recommended when
Summary of the content on the page No. 15
INSTALLING DUCTS TO / FROM INSIDE (CONT'D) Exhaust Air Ducting The stale air exhaust system is used to draw air from the points in the house where the worst air quality problems occur. It is rec- ommended that return air ducts be installed in the bathroom, kitchen, and laundry room. Additional return air ducts from strategic locations (i.e. greenhouse, atrium, swimming pool, sauna, etc.) may be installed. The furnace return duct may be also used to exhaust from. In this method, the exhaust
Summary of the content on the page No. 16
1800 mm INSTALLATION EXAMPLES It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended. All air movement devices have a performance curve. The amount of air (CFM) that an HRV/ERV will deliver is directly related to the total external static pressure (E.S.P.) of the system. Static pressure is a measure of resistance imposed on the blower by length of duct work/number of fittings used in duct work, duct hea
Summary of the content on the page No. 17
1800 mm INSTALLATION EXAMPLES (CONT'D) Example diagram only-duct configuration may change depending on model DIRECT CONNECTION of the SUPPLY AIR STREAM to the FURNACE COLD AIR RETURN (Stale air drawn from key areas of home) Partially Dedicated System Exhaust Central Control - optional Bathroom Stale air drawn from key areas of Bedrooms Return Air home (bathroom, kitchen, laundry) Furnace thermostat Fresh air supplied to main living areas via the forced air system. HRV must be balanced HRV Connec
Summary of the content on the page No. 18
INSTALLATION EXAMPLES (CONT'D) Example diagram only-duct configuration may change depending on model DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM and EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN Simplified Installation Option 1 (Return/Return Method) • HRV must be balanced • It is mandatory that the furnace blower run continuously or HRV operation be interlocked with the furnace blower • Check local codes/authority having jurisdiction for acceptance Note: Option 1 is the pre- ferr
Summary of the content on the page No. 19
INSTALLATION EXAMPLES (CONT'D) Example diagram only-duct configuration may change depending on model DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM & EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN & SUPPLY AIR SIDE Simplified Installation Option 2 (Supply/Return Method) • HRV must be balanced • It is recommended that the furnace blower run continuously or HRV operation be interlocked with the furnace blower • Check local codes /authority having jurisdiction for acceptance Note: Option
Summary of the content on the page No. 20
Magnehelic AIR FLOW BALANCING CAUTION • If the unit’s airflows are not properly balanced... - The unit may not operate at it’s maximum efficiency. - Heat recovery core damage may occur. - The unit’s use could cause negative or positive pressure in your home causing cold air to enter or other combustible equipment to backdraft. - The unit may not defrost properly. PITOT TUBE BALANCING PROCEDURE PITOT TUBE ing. The value read on the gauge is called the velocity pressure. The Pitot tube comes with