Emerson GDESIGN 10003000 A user manual

User manual for the device Emerson GDESIGN 10003000 A

Device: Emerson GDESIGN 10003000 A
Category: Switch
Manufacturer: Emerson
Size: 0.28 MB
Added : 1/15/2014
Number of pages: 12
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Emerson GDESIGN 10003000 A. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Emerson GDESIGN 10003000 A.

For your convenience

If looking through the Emerson GDESIGN 10003000 A user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Emerson GDESIGN 10003000 A on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Emerson GDESIGN 10003000 A to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Emerson GDESIGN 10003000 A User manual - Online PDF
Advertisement
« Page 1 of 12 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Emerson GDESIGN 10003000 A but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Emerson GDESIGN 10003000 A. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

Series 386
Operator’s
Non–Automatic Transfer Switches
Manual
E–design 260–400 A, G–design 1000–3000 A
Refertotheoutlineandwiringdrawingsprovidedwith
theASCOSeries386N–ATSforallinstallationdetails.
DANGER is used in this manual to warn of a
hazardous situation which, if not avoided, will
Rating Label
result in death or serious injury.
Eachnon–automatictransferswitchcontainsa rating
labeltodefine the loadsandfault circuit withstand/
closingratings. Referto the labelonthe transferswitch
WARNING is

Summary of the content on the page No. 2

Summary of the content on the page No. 3

SECTION1 INSTALLATION ASCO386Non–AutomaticTransferSwitches(N–ATSs) are factory wiredandtested. Fieldinstallationsimply requiresmountingandconnectionofservicecables, and Be sure that the insulator piece is behind the 260 auxiliary controlcircuits(ifrequired). and 400 ampere transfer switches. insulator Remove the Shipping Skid(large N–ATSs) backing piece ForlargeN–ATSs, openthefrontdoorandremovethe fourlagscrews(2infront, 2inrear)securingenclosure tothewoodskid. SupportingFoundation Thesupporting

Summary of the content on the page No. 4

INSTALLATION (continued) LineConnections BusConnections AWiringDiagramisfurnishedwiththeASCO386 Ifbusconnectionisused, useSAEgrade5hardwareto (separatefromthismanual). Refertothisdrawing. All connect bustoappropriateterminalplatesonthe wiringmust be made inaccordance withthe National transferswitch. Wipeoffbussurfacesbeforethey are ElectricalCodeandlocalcodes. joined.Ifbusisverydirty,gentlycleansurfaceswitha non–flammablesolvent. Avoidtouchingcleaned surfaces. De–energize the conductors before m

Summary of the content on the page No. 5

INSTALLATION (continued) FunctionalTest TheFunctionalTestconsistsofthreechecks: manual handle operation, voltagechecks, andelectricaloperation. NOTICE Do these checks in the order presented to avoid damaging the non–automatic transfer switch. 1–ManualOperationTest Adetachable maintenancehandleisprovidedonthe transferswitchformaintenancepurposesonly.Manual Figure 1-2. Maintenance handle for E–design 260 and 400 ampere operationoftheswitchshouldbecheckedbeforeitis energized(operatedelectrically).

Summary of the content on the page No. 6

INSTALLATION (continued) FunctionalTest (continued) 2–VoltageChecks 3–ElectricalOperation First checknameplateonthetransferswitchforrated Thisprocedure willcheck the electricaloperationof the voltage. Itshouldbethesameasthenormaland Non-AutomaticTransferSwitch. SeeFigure1–4. emergencylinevoltages. Close the transfer switch enclosure door and Use extreme caution when using a meter to tighten the screws before you test electrical measure voltages in the following steps. operation. Do not touch pow

Summary of the content on the page No. 7

SECTION2 SEQUENCEOFOPERATION ControllerCode 1 Refer to Section 5, Optional Accessoriesfor additional control functions. RefertoWiringDiagramfurnishedwiththeASCO386. NoteControlFeaturesfurnishedonthisswitch,andreviewoperation. Transfer Transfer Control Control Transfer Transfer Transfer Transfer To To To To Normal Emergency Normal Emergency TransferToEmergency RetransfertoNormal The sequence for loadtransfer tothe emergency The sequence for load retransfer to the normal source begins whenyouturnt

Summary of the content on the page No. 8

SECTION3 TESTING&SERVICE PREVENTIVEMAINTENANCE REPLACEMENTPARTS Reasonablecareinpreventivemaintenancewillinsure Replacementpartsareavailableinkitform. When highreliabilityandlonglifefortheswitch. Anannual orderingpartsprovidetheSerialNo., BillofMaterial preventivemaintenanceprogramisrecommended. No.(BOM),andCatalogNo.fromthetransferswitch nameplate. ContactyourlocalASCOPowerTechnolo- ASCO Services, Inc. (ASI) is ASCO Power giessalesofficeorASI. IntheUnitedStatescall Technologies’snationalservice

Summary of the content on the page No. 9

TESTING&SERVICE (continued) 1. Opennormalandemergencysourcecircuitbreakers. MANUALLOADTRANSFER Thisprocedurewillmanuallytransfertheloadifthe Controllerisdisconnected. 2. Usemanualhandletomanuallyoperatetransfer switchtotheoppositesource. Removethehandle. See Section 1, Manual Operation. Do not manually operate the transfer switch 3. IfthetransferswitchisintheEmergencyposition until both power sources are disconnected: manuallystarttheenginegeneratorandthenclose open both circuit breakers. the em

Summary of the content on the page No. 10

4 4 SECTION4 ADJUSTMENTS SensorAdjustments NOTICE Voltage andfrequency sensorpickupanddropout pointsare factory set asspecifiedonthe Wiring Do not change any other factory settings. Any Diagram. The frequency settingcanbe set for50or60 change in these settings may affect the normal Hz.. Tochange thissetting, followthe procedure operation of the ASCO 386. This change could below. Use Table 4-1forthe settingandcorresponding allow the load circuits to remain connected to a low voltage source. DIPsw

Summary of the content on the page No. 11

6 6 7 8 7 8 7 8 7 8 5 5 SECTION5 OPTIONALFEATURES MOTORLOADTRANSFER LOADDISCONNECTFEATURE Inphasemonitoringlogiccontrolstransferand Connectexternalcircuitstotheterminalsindicatedon retransferofmotorloads, sothat inrushcurrentsdo theWiringDiagraminthebackofthismanual. not exceednormalstartingcurrents. It avoidsnuisance Thedoublethrow(FormC)contactisratedfor28 trippingofcircuitbreakersandmechanicaldamageto VDCor120VAC(6ampsresistive). Thecontact motorcouplings. operatespriortoaselectable0, 3, 10,

Summary of the content on the page No. 12

INDEX A I O operation auxiliary circuits, 1–1 identificationlabel, cover electrical, 1–4 manual, 1–3 B illustrationof, 1–3 inphase monitor, 5–1 warning, 1–3 barriers, 1–2 sequence of, 2–1 bus connections, 1–2 inspection, 3–1 optionalfeatures, 5–1 load disconnect, 5–1 installation, 1–1 motorload transfer, 5–1 C cable P lugs, 1–1, 1–2 L preparation, 1–1, 1–2 parts, 3–1 catalognumber, inside cover labels, problem, 3–2 cleaning, 3–1 rating, cover connections R line, 1–2 lights, 1–4, 3–1 ratinglabel,


Alternative user manuals
# User manual Category Download
1 Emerson 5081-T User manual Switch 38
2 Emerson ASCO 300 Series User manual Switch 747
3 Emerson ASCO 7000 User manual Switch 91
4 Emerson 7000 User manual Switch 58
5 Emerson ASCO 185 User manual Switch 45
6 Emerson 7ADTB User manual Switch 3
7 Emerson 185 User manual Switch 7
8 Emerson B-294 HD User manual Switch 0
9 Emerson Autochangeover Controllers AC8 User manual Switch 7
10 Emerson 214A401 User manual Switch 0
11 Emerson 214A400 User manual Switch 3
12 Emerson 214A404 User manual Switch 0
13 Emerson 260 User manual Switch 0
14 Emerson 300 User manual Switch 1
15 Emerson 386 User manual Switch 0
16 Sony 4-296-436-11 (2) User manual Switch 0
17 3Com 10/100BASE-TX User manual Switch 61
18 3Com 2226-SFP User manual Switch 688
19 3Com 16985ua.bk User manual Switch 10
20 3Com 10BASE-T User manual Switch 4