Emerson 7000 SERIES 7ADTB user manual

User manual for the device Emerson 7000 SERIES 7ADTB

Device: Emerson 7000 SERIES 7ADTB
Category: Switch
Manufacturer: Emerson
Size: 1.05 MB
Added : 1/15/2014
Number of pages: 12
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Emerson 7000 SERIES 7ADTB. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Emerson 7000 SERIES 7ADTB.

For your convenience

If looking through the Emerson 7000 SERIES 7ADTB user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Emerson 7000 SERIES 7ADTB on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Emerson 7000 SERIES 7ADTB to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Emerson 7000 SERIES 7ADTB User manual - Online PDF
Advertisement
« Page 1 of 12 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Emerson 7000 SERIES 7ADTB but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Emerson 7000 SERIES 7ADTB. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

7000 Series 7ADTB
Operator’s
Automatic Delayed–Transition Transfer
& Bypass–Isolation Switches
Manual
G design 1000 through 3000 amp. sizes
Refer to the outline and wiring drawings provided
with your 7000 Series ADTB for all installation and
DANGER is used in this manual to warn of high
connectiondetailsandaccessories.
voltages capable of causing shock, burns, or death.
RefertoGroup5ControllerUser’sGuide381333–126
forATSstatusdisplaymessages,timedelays,pickup
&dropoutsettings,andadjustments.
WAR

Summary of the content on the page No. 2

SECTION1 INSTALLATION The ASCO 7000 Series Automatic Delayed–Transition Transfer & Bypass–Iolation Switch (ADTB) consists of an upper bypass–isolation switch, a transfer switch, a monitoring and transfer control panel, and door– mounted controls. The ADTB is factory wired and tested. Installationrequiresremovaloftheshippingskid then securing the enclosure to the supporting founda- tion. Remove the Shipping Skid Openthefrontlowerdoorandremovethetwofrontlag screws securing the enclosure to the woo

Summary of the content on the page No. 3

INSTALLATION (continued) BusConnections If bus connection is used, use SAE grade5 hardwareto De–energizetheconductorsbeforemakingany connect bus to appropriate terminal plates on bypass line or auxiliary circuitry connections. Be sure switchingdevice. Wipe offbus surfacesbefore theyare that Normal and Emergency line connections joined. If bus is dirty, gently clean surfaces with a areinproperphaserotation.Placeenginegen- non-flammablesolvent.Avoidtouchingcleanedsurfaces. eratorstartingcontrolint

Summary of the content on the page No. 4

(continued) INSTALLATION GREEN RED observe these lights GREEN RED AMBER Figure 1-3. Standard controls and indicators. Close the normalsource circuit breaker. The Transfer Switch FunctionalTest 1 Connected To Normal and the Load Disconnect Normal Source Accepted lights Active Read all instructions on the Wiring Diagrams and labels should come on. affixedtotheADTB. Notethecontrolfeaturesthatare providedandreviewtheiroperationbeforeproceeding. Use an accurate voltmeter to AfterinstallingtheADTBchec

Summary of the content on the page No. 5

INSTALLATION (continued) GREEN RED operate this switch observe these lights GREEN RED AMBER Figure 1-4. Standard controls and indicators. Turn and hold Transfer Control switch clockwise to Transfer 2–ElectricalOperation Test untilthe engine starts 1 and runs (within 15 sec.). The Load Thisprocedure checkselectricaloperationof the ATS. Disconnect Active Emergency Source Accepted light should come on. Besureto closetheenclosuredoor Transfer switch CN opens and before proceeding to preventpersonal

Summary of the content on the page No. 6

SECTION2 TESTING&SERVICE TRANSFERTEST REPLACEMENTPARTS Test the AutomaticDelayed–Transition TransferSwitch Replacement parts are available in kit form. When or- portionofthe7000SeriesADTBatleastonceamonth. deringpartsprovidetheSerialNo., BillofMaterialNo. This procedure checks the electrical operation of the (BOM),andCatalogNo.fromthetransferswitchname- TransferSwitchandController. TurntheEngineControl plate.ForservicecallASCOServicesat1–800–800–2726; switchtoAutoandputtheengine–generatorstartin

Summary of the content on the page No. 7

TESTING&SERVICE (continued) TROUBLE-SHOOTING Note any optional accessoriesthat maybe furnishedon the ADTB and review their operation. Refer to any separatedrawingsand/orinstructionsthatmaybepacked Hazardousvoltagecapableof causing shock, burns, ordeathis used in this switch. withtheADTB. Do nottouchthepowerorload terminals ofthebypassswitchortransferswitch! Table2-1. Trouble-Shooting Checks. CHECK IN NUMERICAL SEQUENCE PROBLEM 1 2 3 OPERATION GEN-SET VOLTAGE Engine–generatorsetdoes Hold Transfer

Summary of the content on the page No. 8

SECTION3 BYPASSING&ISOLATING BYPASSING THE ATS* This procedure explains how to Bypass the closed Youcanonly bypassto thesamesource automatictransferswitchcontacts. Bypassingisrequired thatthe Transfer Switchis connected. before the ATS can be tested or isolated. The Bypass Solenoid interlockprevents incorrectoperation. HandlemustbeintheOPENposition (greenindicator) 1. ObservewhichTransferSwitch ConnectedTo light is and the Isolation Handle must be in the CLOSED on (Normal or Emergency) on the do

Summary of the content on the page No. 9

BYPASSING&ISOLATING (continued) ISOLATING THE ATS position Isolating is required before any service work can be window performedontheautomatictransferswitch(ATS).Refer CONN toFigures3–4, 3–5, 3–6, and3–7. TEST ISOLATE 1. Bypasstheclosedautomatictransferswitchcontacts. See BYPASSINGonpage3–1. unfold Align position indicator. Do notleave crank thehandleinanintermediateposition. 2. TurntheIsolationHandlecounterclockwise(approx. 16 turns)untilwindowshowsTEST.TheATScanbe testednowwithoutloadinterrupt

Summary of the content on the page No. 10

BYPASSING&ISOLATING (continued) RETURNTOSERVICE This procedure explains how to return the automatic Solenoid interlock prevents you from closing transfer switch (ATS) to service after inspection and the isolation contacts until the ATS is in the samepositionastheBypassSwitch. maintenance. ObservetheBypassSwitchPositionindica- torandlights).RefertoFigures3–7,3–8,3–9,and3–10. 3. Observe which Bypass Switch Position indicator is black (NORMAL or EMERGENCY)attheBypass 1. Slide the transfer switch (A

Summary of the content on the page No. 11

BYPASSING&ISOLATING (continued) RETURNTOSERVICE continued* ThisprocedureexplainshowtoreturntheBypassSwitch Youcanonly bypassto thesamesource HandletotheOPENposition. TheBypassHandlemust thatthe ATS is connected. Solenoid be in the CLOSED position (yellow indicator on NOR- interlockprevents incorrectoperation. MALorEMERGENCY)andtheIsolation Handlemust 1 Observe which Bypass Switch Position indicator is beintheTESTposition(window).Ifthehandlesarenot yellow (NORMAL or EMERGENCY)attheBypass inthesep

Summary of the content on the page No. 12

INDEX A I R ratinglabel, cover auxiliarycircuits,1–2 inspection, 3–1 removalofshippingangles, 1–1 installation, 1–1 removalofshippingskid, 1–1 B isolatingtheATS,3–2 replacementparts,2–1 busconnections, 1–2 returntoservice, 3–3 L bypassingtheATS, 3–1 lights, 1–3, 1–4 S loadconnectedtoemergency,1–5 C service loadconnectedtonormal, 1–4 catalognumber, cover ASCOServices,Inc.(ASI),2–1 LoadDisconnectActivelight,1–4 settings cleaning, 2–1 seeControllerUser’s Guide connections lubrication,2–1 shippingan


Alternative user manuals
# User manual Category Download
1 Emerson 5081-T User manual Switch 38
2 Emerson ASCO 300 Series User manual Switch 747
3 Emerson ASCO 7000 User manual Switch 91
4 Emerson 7000 User manual Switch 58
5 Emerson ASCO 185 User manual Switch 45
6 Emerson 7ADTB User manual Switch 3
7 Emerson 185 User manual Switch 7
8 Emerson B-294 HD User manual Switch 0
9 Emerson Autochangeover Controllers AC8 User manual Switch 7
10 Emerson 214A401 User manual Switch 0
11 Emerson 214A400 User manual Switch 3
12 Emerson 214A404 User manual Switch 0
13 Emerson 260 User manual Switch 0
14 Emerson 300 User manual Switch 1
15 Emerson 386 User manual Switch 0
16 Sony 4-296-436-11 (2) User manual Switch 0
17 3Com 10/100BASE-TX User manual Switch 61
18 3Com 2226-SFP User manual Switch 688
19 3Com 16985ua.bk User manual Switch 10
20 3Com 10BASE-T User manual Switch 4