Emerson 7000 SERIES ATB user manual

User manual for the device Emerson 7000 SERIES ATB

Device: Emerson 7000 SERIES ATB
Category: Switch
Manufacturer: Emerson
Size: 0.5 MB
Added : 1/15/2014
Number of pages: 14
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Emerson 7000 SERIES ATB. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Emerson 7000 SERIES ATB.

For your convenience

If looking through the Emerson 7000 SERIES ATB user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Emerson 7000 SERIES ATB on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Emerson 7000 SERIES ATB to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Emerson 7000 SERIES ATB User manual - Online PDF
Advertisement
« Page 1 of 14 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Emerson 7000 SERIES ATB but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Emerson 7000 SERIES ATB. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

7000 Series ATB
Operator’s
Automatic Transfer &
Manual
Bypass–Isolation Switches
F–design, 3000 and 4000 amp. sizes
Refer to the outline and wiring drawings provided
with your 7000 Series ATB for all installation and
connection details and accessories.
TABLE OF CONTENTS
section-page
INSTALLATION ........................ 1-1
RefertoGroup5ControllerUser’sGuide381333–126
Mounting ............................. 1-1
forATSstatusdisplay messages,time delays,pickup
Power Connections ....................

Summary of the content on the page No. 2

SECTION1 INSTALLATION The ASCO 7000 Series Automatic Transfer & Bypass– Mounting IsolationSwitch(ATB)consistsofanupperbypass–isola- Refer to the enclosure outline drawing furnished with tion switch, a transferswitch, a monitoring andtransfer thisswitchandmount the7000SeriesATB accordingto controller, and door–mounted controls. The ATB is thedetailsandinstructionsshownonthedrawing. factorywiredandtested. Installationrequiresremovalof Boltthecubiclesectionstogethersothattheyarelinedup the shipping

Summary of the content on the page No. 3

INSTALLATION (continued) Connecting Power Conductors Bus Connections AWiringDiagramisfurnishedwiththeATB. Allwiring If bus connection is used, use SAE grade 5 hardware to must be made inaccordance withthe localcodes. After connect bus to appropriate terminal plates on bypass the power cableshave beentested, connect them tothe switching device. Wipe offbus surfacesbefore theyare appropriateterminallugsontheBypassSwitchasshown joined. If bus is dirty, gently clean surfaces with a on the wiring dia

Summary of the content on the page No. 4

INSTALLATION (continued) Install theTransfer Switch Remove interference tag after makinginspection After the enclosure is installed and power cables or bus on page 1-4. connected to the Bypass Switch, the Transfer Switch SL1 carriagecanberolledin. Thefloorofthecabinetmustbe solenoid freeofdebrisandclean.Ifnecessary,useavacuumcleaner. lock Make a thorough inspection to be sure no tools are left inside. The Bypass Handle must be in the BYPASS POS handle position (closed on normal). The Isolation H

Summary of the content on the page No. 5

INSTALLATION (continued) Inspection1 sensingleadcontact ! Do notforce the Isolation Handle. Be sure that TS IS thesensing lead isolationcontactsdo nothitthe stab isolation contacts malestabshead on,butratherslideonthem. Figure 1–5. Isolation contacts in TEST position. MoveATSfromDISCONNECTEDToTEST Position (withoutelectricalpower) Action Turn the Isolation Handle (Figure 1–3) clockwiseapproximately7or8turns. The Transfer Switch should be pulled inward; the sensing lead isolation Observe contacts

Summary of the content on the page No. 6

INSTALLATION (continued) AutomaticTransfer &Bypass–IsolationSwitch Transfer Transfer Switch Control Transfer Switch Connected Connected Transfer Retransfer Test To To Delay HOLD FOR Normal Emergency Bypass ( 15 SECONDS) GREEN RED observe Normal Emergency Source Source these lights Accepted Accepted GREEN RED Figure 1-8. Standard controls and indicators. Close the normalsource circuit breaker. The Transfer Switch FunctionalTest 1 Connected To Normal and the Read all instructions on the Wiring Dia

Summary of the content on the page No. 7

INSTALLATION (continued) 2–ManualOperationTest This procedure will check the manual operation of the Bypass Switch, Isolation Switch, and Transfer Switch. Observe the lights on the Status Indicator panel. The Bypass Switch CLOSED ON NORMAL and the TEST lightsshouldbe on. See Figure 1–11. 1. IsolatetheAutomaticTransferSwitch: InstalltheIsolationHandleandturnitcounterclock- wiseuntilitstops (approximately 7 or8 turns). The Automatic Transfer Switch is now in the Discon- nectedposition(See Figure 1

Summary of the content on the page No. 8

INSTALLATION (continued) AutomaticTransfer &Bypass–IsolationSwitch Transfer Transfer Switch Control Transfer Switch Connected Connected Transfer Retransfer Test To To Delay HOLD FOR Normal Emergency Bypass ( 15 SECONDS) GREEN RED operate this switch observe Normal Emergency Source Source these lights Accepted Accepted GREEN RED Figure 1-13. Standard controls and indicators. 3–ElectricalOperation The Transfer Switch Connected 1 to Normal and Normal Source This procedure checks electricaloperation

Summary of the content on the page No. 9

SECTION2 TESTING&SERVICE TRANSFER TEST REPLACEMENTPARTS Test the Automatic Transfer Switch portion of the 7000 Replacement parts are available in kit form. When or- SeriesATBatleastonceamonth. Thisprocedurechecks deringpartsprovide the SerialNo., Billof MaterialNo. the electrical operation of the Transfer Switch and (BOM),andCatalogNo.fromthetransferswitchname- Controller. Puttheengine–generatorstartingcontrol(at plate. ContactyourlocalASCOPowerTechnolgiessales the engine–generatorset)inautomati

Summary of the content on the page No. 10

TESTING&SERVICE (continued) TROUBLE-SHOOTING Note any optional accessoriesthat may be furnishedon Hazardousvoltagecapableof causing shock, theATB andreview theiroperation. Referto anysepa- burns, ordeathis used inthis switch. rate drawings and/or instructions that may be packed Do nottouchthepowerorload terminals withtheATB. of the transfer switch! Table2-1. Trouble-Shooting Checks. CHECK IN NUMERICAL SEQUENCE PROBLEM 1 2 3 OPERATION GEN-SET VOLTAGE Engine–generatorsetdoes Hold Transfer Test swi

Summary of the content on the page No. 11

SECTION3 BYPASSING&ISOLATING BYPASSING ISOLATING This procedure explains how to isolate the Automatic This procedure explains how to Bypass the closed Transfer Switch. Isolatingis requiredbefore anyservice Automatic Transfer Switch contacts. Bypassing is re- work can be performed on the ATS. Observe the ATS quired before the ATS can be tested or isolated. The POSITIONlightsontheSTATUSINDICATORpanel. Bypass Switch must be in the AUTOMATIC POS (posi- tion)andtheIsolationHandlemust bein theconnecte

Summary of the content on the page No. 12

BYPASSING&ISOLATING (continued) TRANSFERSWITCHREMOVAL TRANSFERSWITCHREINSTALLATION This procedure explains how to remove the Transfer ThisprocedureexplainshowtoinstalltheTransferSwitch Switchforinspectionandmaintenance. afterinspectionandmaintenance. 1. BypassandIsolatetheAutomaticTransferSwitchby carefully following directions on page 3–1. Be sure that the ATS POSITION DISCONNECTED light is Hazardousvoltagecapableof causing electrical shock, burns, ordeath. on. Thenremove the IsolationHandle. D

Summary of the content on the page No. 13

BYPASSING&ISOLATING (continued) RETURNTOSERVICE This procedure explains how to return the Automatic Transfer Switch to service after inspection and maintenance. ObservetheATS POSITIONlightsonthe STATUSINDICATORpanel. 1. Install the Transfer Switch into the enclosure. Carefully followdirectionsonpage 3–2. ! Close enclosure doorto preventpersonal injury in case of electrical system fault. 2.. Install the Isolation Handle (through the door) and turnitclockwise(approximately7or8turns)untilthe TESTli

Summary of the content on the page No. 14

INDEX A I R inspection, 1–4, 3–1 ratinglabel, cover auxiliarycircuits, 1–2 installation, 1–1, 1–3 replacementparts, 2–1 isolatingtheATS, 3–1 returntoservice, 3–3 B busconnections, 1–2 L S lights, 1–5, 1–6 bypassingthe ATS, 3–1 service loadconnectedtoemergency, 1–5 ASCOServices,Inc.(ASI),2–1 loadconnectedtonormal, 1–5 settings C seeControllerUser’s Guide lubrication, 2–1 catalognumber, cover cleaning, 2–1 M T maintenance, preventive, 2–1 connections test, functional, 1–5, 1–6, 1–7 power, 1–2 main


Alternative user manuals
# User manual Category Download
1 Emerson 5081-T User manual Switch 38
2 Emerson ASCO 300 Series User manual Switch 747
3 Emerson ASCO 7000 User manual Switch 91
4 Emerson 7000 User manual Switch 58
5 Emerson ASCO 185 User manual Switch 45
6 Emerson 7ADTB User manual Switch 3
7 Emerson 185 User manual Switch 7
8 Emerson B-294 HD User manual Switch 0
9 Emerson Autochangeover Controllers AC8 User manual Switch 7
10 Emerson 214A401 User manual Switch 0
11 Emerson 214A400 User manual Switch 3
12 Emerson 214A404 User manual Switch 0
13 Emerson 260 User manual Switch 0
14 Emerson 300 User manual Switch 1
15 Emerson 386 User manual Switch 0
16 Sony 4-296-436-11 (2) User manual Switch 0
17 3Com 10/100BASE-TX User manual Switch 61
18 3Com 2226-SFP User manual Switch 688
19 3Com 16985ua.bk User manual Switch 10
20 3Com 10BASE-T User manual Switch 4