Bay Technical Associates V79 PDI-1 user manual

User manual for the device Bay Technical Associates V79 PDI-1

Device: Bay Technical Associates V79 PDI-1
Category: Switch
Manufacturer: Bay Technical Associates
Size: 0.11 MB
Added : 5/5/2013
Number of pages: 49
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Bay Technical Associates V79 PDI-1. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Bay Technical Associates V79 PDI-1.

For your convenience

If looking through the Bay Technical Associates V79 PDI-1 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Bay Technical Associates V79 PDI-1 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Bay Technical Associates V79 PDI-1 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Bay Technical Associates V79 PDI-1 User manual - Online PDF
Advertisement
« Page 1 of 49 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Bay Technical Associates V79 PDI-1 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Bay Technical Associates V79 PDI-1. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

OWNER'S MANUAL
________________
MODEL V79 PDI-1 AND V80 PDI-2
SWITCH INPUT AND OPTICALLY
ISOLATED INPUT MODULES
BayTech Publication #U140E105

Summary of the content on the page No. 2

Thank you for selecting a BayTech Model V79 PDI-1 Switch Input Module or Model V80 PDI-2 Optically Isolated Input Module. The data provided in this Owner's Manual explains the various ways you can operate the V79 PDI-1 or V80 PDI-2, and how to configure your unit. We suggest that you read this manual carefully before attempting to install a PDI, and that you place special emphasis on correct cabling and configuration. If you have any problems with your installation, please contact a BayTech ap

Summary of the content on the page No. 3

TABLE OF CONTENTS 1 GENERAL 1 ............................................................................................................................................................................................ 1.1 V79 PDI-1 MODULE 2 .................................................................................................................................................. 1.2 V80 PDI-2 MODULE 2 .....................................................................................

Summary of the content on the page No. 4

5 CONFIGURATION 19 ........................................................................................................................................................................... 5.1 MENU-DRIVEN CONFIGURATION 19 ..................................................................................................................... 5.1.1 CONFIGURATION MAIN MENU 21 .................................................................................................. 5.1.2 MODULE STATUS 22

Summary of the content on the page No. 5

1 GENERAL BayTech's PDI modules are designed for use with the M16 and M8 (DAC) Data Acquisition Controllers. Both modules are used to detect events where an event is defined as a change-in-state of an input and return to the original state. The V79 PDI-1 module is used for the detection of switch closure in applications requiring notification of device status such as burglar alarms, fire alarms, event counters and timers, process control, etc.. The V80 PDI-2 is used for the detection of optic

Summary of the content on the page No. 6

1.1 V79 PDI-1 MODULE The main features of the V79 PDI-1 module are sixteen microprocessor-controlled input channels that can be connected with individual ground returns, or a common single-point ground. The input channels provide a flexible, reliable method to detect and report the change-in-state of a circuit. The change can be from infinite resistance (open) to continuity (closed), and vice versa. For example, the change- in-state could be for a set of form C (dry) relays or switch contacts.

Summary of the content on the page No. 7

These optically isolated inputs provide an efficient means for the monitoring of external process and control functions. All functions provided by the board are programmable through a series of detailed configuration menus. Additional functionality is made available through the use of BayTech or user provided application software. Input connections to the PDI-2 are made through a standard DC-37F connector. 2 SPECIFICATIONS 2.1 V79 PDI-1 SWITCH INPUT STATUS MODULE o (typical for 25 C unless ot

Summary of the content on the page No. 8

2.2 V80 PDI-2 OPTICALLY ISOLATED INPUT MODULE MODULE TYPE PDI-2A PDI-2B NUMBER OF INPUTS: 16 16 INPUT VOLTAGE RANGE: 5-24 100-130 AC/DC MAXIMUM INPUT CURRENT: 50ma 20ma MINIMUM TURN ON CURRENT:8ma 8ma MAX TURN ON TIME: 1ms 1ms MAX TURN OFF TIME: 1ms 1ms VOLTAGE ISOLATION: 500V 500V (Input to Input and Input to ground) POWER REQUIREMENTS: +5VDC, 40 ma typical (provided by M16/M8 pwr supply) DEBOUNCE TIME: 0 to 60000 ms (software selectable) ENVIRONMENTAL: o o Operating

Summary of the content on the page No. 9

3 INSTALLATION The PDI-1 and PDI-2 are installed in the M Series chassis as described in Section 3.5 of the base unit operator's manual. NOTE: The PDI-1 or PDI-2 cannot be installed as Module 1. If an PDI-1 or PDI- 2 is removed from a module slot and a different PDI-1 or PDI-2 is installed in that location, the newly installed module acquires the previous module's configuration. Moving an PDI-1 or PDI-2 to a different module location requires reconfiguration because the configuration paramete

Summary of the content on the page No. 10

3.2 PDI-2 AC INPUT SETUP The PDI-2 module has two banks of dip switches which are used to add ripple filtering for AC inputs. AC input is selected by individual channel. Location of the dip switches is shown in Figure 3. CHANNEL SW1 SW2 1 1 2 2 3 3 Figure 3 4 4 5 5 6 6 7 7 8 8 9 1 10 2 11 3 12 4 13 5 14 6 15 7 16 8 Table 1 Dip switch SW1 1-8 provides filtering control for channels 1-8 while SW2 1-8 controls channels 9-16. Refer to Table 1 to determine wh

Summary of the content on the page No. 11

4 OPERATION This section discusses the general PDI operation (Section 4.1), user-programmable features (Section 4.2), data commands (Section 4.3), event sample reporting (Section 4.4), and presentation (Section 4.5). 4.1 GENERAL The V79 PDI-1 and V80 PDI-2 modules are used in applications requiring notification of device status (e.g., burglar and fire alarms, event counters/timers, process control, etc.). The PDI-1 module has 16 channel switch inputs providing a reliable method to detect and re

Summary of the content on the page No. 12

4.2 USER-PROGRAMMABLE FEATURES You may program the Sampling Setup, Reporting Setup, and Dynamic Configuration on the PDI which are discussed in Section 4.2.1 through Section 4.2.3 respectively. 4.2.1 SAMPLING SETUP Sampling Setup allows you to program the Debounce Delay and Latch Polarity for the input channels. The Debounce Delay is used to guard against erroneous events. An event will not be valid unless the input channel has remained at a changed state for the debounce duration. The deboun

Summary of the content on the page No. 13

4.2.2.2 REPORT START TIME Report Start Time is the time reporting begins when Schedule Reporting Method is selected. The start of reporting may be delayed up to 24 hours from the current time recorded by the M Series time-of-day clock and reporting will occur in cyclic periods as determined by the Report Interval. The default Report Start Time is 00:00. 4.2.2.3 REPORT INTERVAL You may program the PDI to report in repetitive periods using Schedule Reporting Method, where the PDI will report all

Summary of the content on the page No. 14

4.2.2.6 TERMINATING CHARACTER(S) The Terminating Character(s) is added at the end of an event sample to match the requirements of the host terminal or application software. The Terminating Character(s) consists of one or two hexadecimal characters. The default Terminating Characters are 0D Hex ( ) followed by 0A Hex ( Carriage Return Line ). Feed 4.2.3 DYNAMIC CONFIGURATION You may enable or disable Dynamic Configuration for the PDI. Dynamic configuration mode allows non-verbose or "on-the-fl

Summary of the content on the page No. 15

2. Once the PDI is selected, it will go into Command Mode and allow you to send data commands. The PDI data commands begin with two capital letters designating the specific command and are terminated with a Carriage Return. Most data commands also require a number between the command letters and Carriage Return. This number is typically the desired channel(s) for the data command. If you have a requirement to send the data command to multiple channels simultaneously, you may use one of the f

Summary of the content on the page No. 16

4.3.1 CLEAR EVENT BUFFER COMMAND The Clear Event Buffer (CB) command is used to clear all stored event samples from the buffer of the selected channel(s). The Clear Event Buffer command has the following format: CB n where c = Channel# (1 to 16 or 0 for all). 4.3.2 CLEAR EVENT COUNTER COMMAND The Clear Event Counter (CC) command is used to reset the event counter for one or more channels to zero without reading the value of the event counter. The function of the event counters is discussed

Summary of the content on the page No. 17

4.3.4 REPORT ALL BUFFERED EVENTS COMMAND The Report All Buffered Events (RA) command instructs the PDI to report all event samples currently stored in the buffer of the selected channel(s). The Report All Buffered Events command has the following format: RA n where c = Channel# (1 to 16 or 0 for all). 4.3.5 REPORT EVENT COUNTER COMMAND The Report Event Counter (RC) command instructs the PDI to report how many times an event has occurred for one or more channels since the last time a counter

Summary of the content on the page No. 18

4.3.7 REPORT EVENT LATCH DATA COMMAND The Report Event Latch Data (RL) command instructs the PDI to report the active state of the initial event and the time the initial event occurred (if time tagging is enabled). This command does not reset the latch buffer. The Report Event Latch Data has the following format: RL c where c = Channel# (1 to 16 or 0 for all). 4.3.8 REPORT EVENT COUNTER AND RESET COMMAND The Report Event Counter and Reset (RO) command instructs the PDI to report how many

Summary of the content on the page No. 19

4.3.10 REPORT A SINGLE BUFFERED EVENT COMMAND The Report A Single Buffered Event (RS) command instructs the PDI to report the first event sample stored in the buffer of the selected channel(s). The Report A Single Buffer Sample command has the following format: RS c where c = Channel# (1 to 16 or 0 for all). 4.4 EVENT SAMPLE REPORTING An event is defined as a change-in-state of an input channel and return to the original state. An event may be started on a rising edge (LO to HI) or a fall

Summary of the content on the page No. 20

The PDI module can observe, record, and report when an event happened, how long the event lasted, and how many events occurred for each individual channel. The initial occurrence of an event will set the event latch bit and store the associated time in the latch buffer. You may read the state of the initial event and the time it was recorded (if time tagging is enabled) by issuing the RL or RR commands. Each occurrence of an event starts the duration counter and increments the event counter.


Alternative user manuals
# User manual Category Download
1 Bay Technical Associates DS62-MD4 User manual Switch 1
2 Bay Technical Associates REMOTE POWER CONTROLLER DS4D-RPC User manual Switch 0
3 Bay Technical Associates DS Series User manual Switch 0
4 Bay Technical Associates BayTech DS72 User manual Switch 1
5 Bay Technical Associates DS2-RPC, DS4-RPC User manual Switch 1
6 Bay Technical Associates BayTech DS74 User manual Switch 0
7 Bay Technical Associates REMOTE POWER CONTROLLER DS4-RPC User manual Switch 0
8 Bay Technical Associates BayStack 304 User manual Switch 4
9 Bay Technical Associates V80 PDI-2 User manual Switch 0
10 Bay Technical Associates BayStack 303 User manual Switch 5
11 Bay Technical Associates 350 User manual Switch 0
12 Bay Technical Associates BayTech DS73 User manual Switch 0
13 Bay Technical Associates REMOTE POWER CONTROLLER DS2-RPC User manual Switch 0
14 Bay Technical Associates DS2-RPC DS4-RPC User manual Switch 0
15 Bay Technical Associates S2-RPC User manual Switch 0
16 Sony 4-296-436-11 (2) User manual Switch 0
17 3Com 10/100BASE-TX User manual Switch 61
18 3Com 2226-SFP User manual Switch 688
19 3Com 16985ua.bk User manual Switch 10
20 3Com 10BASE-T User manual Switch 4