Owner’s Manual
SU10KRT3/1X
™
SmartOnline Rack/Tower On-Line UPS System
with Parallel Redundancy Capability
Input: 160-280/277-485V AC, 50/60 Hz, 3Ø, 4-Wire + Ground, Wye
Output: User-Selectable 200/220/230/240V AC, 50/60 Hz, 1Ø, 2-Wire + Ground
Not suitable for mobile applications.
6-3 Normal Mode Startup 13
1 – Introduction 2
6-4 Battery Mode Startup (Cold Start) 14
2 – Important Safety Instructions 2
6-5 UPS System Shutdown 14
3 – Rear Panel Features 4
6-6 UPS System Settings and Measurements
Summary of the content on the page No. 2
1 – Introduction Tripp Lite’s SmartOnline Rack/Tower On-Line UPS System with Parallel Redundancy Capability provides long-lasting battery backup for data centers, telecommunications, networks, industrial facilities, security, emergency systems and other critical applications that require high capacity, high availability and extended runtime. True on-line operation continuously transforms 3-phase input power into precision-regulated single-phase output to guarantee maximum equipment protection
Summary of the content on the page No. 3
2 – Important Safety Instructions continued • E v e n a f t e r t h e A C s u p p l y c i r c u i t i s d i s c on n e c t e d , t h e r e i s a r i s k o f d a n g e r o u s e l e c t r i c a l s h o c k w h e n t h e e x t e r n a l ba t t e r y p a c k i s c on n e c t e d t o t h e U P S s y s t e m . D i s c on n e c t t h e e x t e r n a l ba t t e r y p a c k b e f o r e s e r v i c i n g t h e U P S s y s t e m . • U s e o f t h i s e q u i pm e n t i n l i f e s u p p o r t a p p l i
Summary of the content on the page No. 4
3 – Rear Panel Features Note: Refer to Section 6-1 for a description of the UPS system’s control panel. UPS System Power Module Rear Panel E F G UTILITY - INPUT BREAKER G I + A SLOT B TB1 J C TB2 D H A R S - 2 3 2 P o r t ( N o t e : R e m o v e t h e n e t w o r k c a r d i n o r d e r t o u s e t h e R S - 2 3 2 p o r t . ) B Settings Switch for Parallel Redundancy Operation C C A N B u s C on n e c t i on P o r t s f o r P a r a l l e l R e d u n d a nc y O p e r a t i on D C
Summary of the content on the page No. 5
4 – Mounting Read Section 2 – Important Safety Instructions Before Mounting Warning: The UPS system is very heavy—be careful when moving or lifting it. 4-1 Unpacking R e m o v e t h e p r o t e c t i v e f o a m a n d u n w r a p t h e u n i t . I n s p e c t t h e u n i t c a r e f u l l y p r i o r t o i n s t a l l a t i on. I f a n y t h i n g a p p e a r s t o b e d a m a g e d , c on t a c t T r i p p Lite for service. Retain the packing materials for future use. P a c k i n g L i s t
Summary of the content on the page No. 6
4 – Mounting continued 4-2 Placement I n o r d e r t o m i n i m i z e t h e p o s s i b i l i t y o f d a m a g e t o t h e U P S s y s t e m a n d m a x i m i z e i t s op e r a t i on a l l i f e s p a n , f o l l o w t h e l o c a t i on w a r n i n g s l i s t e d i n Section 2 – Important Safety Instructions. Remember to keep at least 30 cm clearance from the rear panel of the UPS system to the wall and do not block any of the UPS system’s front or rear ventilation openings. Warning: The
Summary of the content on the page No. 7
4 – Mounting continued 4-4 Mounting (Tower) Warning: When mounting the UPS system in a tower position, make sure the control panel is closer to the top of the cabinet than the bottom. Note: The control panel can be rotated to match the UPS system’s position. Pull the panel out slightly, rotate it and push it back into place. Tower Mounting Procedure 1 S2 A5 A4 U s e M 4 f l a t - h e a d s c r e w s to attach covers to four of the tower feet . 2 S1 A4 U s e M 3 f l a t - h e a d s c r e
Summary of the content on the page No. 8
5 – Wiring DANGER! LETHAL HIGH VOLTAGE HAZARD! All wiring should be performed by a qualified electrician, in accordance with the warnings in this manual and all applicable e l e c t r i c a l a n d s a f e t y c o d e s . I nc o r r e c t w i r i n g m a y c a u s e s e r i o u s p e r s on a l i n j u r y a n d p r op e r t y d a m a g e . R e a d , s t u d y a n d understand the warnings listed in Section 2 – Important Safety Instructions before proceeding. 5-1 Wiring Preparation • D e - e
Summary of the content on the page No. 9
5 – Wiring continued 5-4 AC Input/Output Wiring Instructions 1 S5 A1 U s e M 3 p a n - h e a d s c r e w s to attach the cable attachment tray beneath the terminal block. 2 Route the AC input/output wiring through cable sleeves and route the cable sleeves through the knockouts in the terminal block cover A2 . Each input/output wire should terminate with a ring terminal. 3 C on n e c t t h e r i n g t e r m i n a l f o r e a c h i n p u t / o u t p u t c a b l e t o t h e a p p r op r i
Summary of the content on the page No. 10
5 – Wiring continued 5-5 External Battery Pack Connection • W a r n i n g : D o no t a t t e m p t t o c o n n e c t o r d i s c o n n e c t a n e x t e r n a l b a t t e r y p a ck w he n t he U P S s y s t e m i s o p e r a t i n g f r o m t he b a t t e r y s u p p l y . • W a r n i n g : K e e p t he r e a r p a n e l o f t he e x t e r n a l b a t t e r y p a ck a t l e a s t 2 0 c m a w a y f r o m t he w a l l o r a n y o b j e c t t h a t m a y i m p e d e a i r f l o w . ( T he r e a
Summary of the content on the page No. 11
6 – Standard Operation 6-1 Control Panel Features 2 3 4 5 6 1 7 8 9 10 11 12 1 L C D S c r e e n : Provides detailed information about operating conditions, UPS system settings and more. See the next page for a description o f t h e L C D s y m b o l s . 2 L I N E L E D : T h i s g r e e n L E D i l l u m i n a t e s c on t i n u o u s l y t o i n d i c a t e t h e u t i l i t y - s u p p l i e d A C l i n e v o l t a g e o f t h e A C s u p p l y c i r c u i t i s n o m i n a l . I t
Summary of the content on the page No. 12
6 – Standard Operation continued 6-1 Control Panel Features continued LCD Symbols Symbol Description LINE Utility or Bypass Source Battery Low Battery Abnormal/Fault UPS Overload U P S O p e r a t i n g i n S p e c i f i e d M o d e ( N o r m a l , E c on o m y , e t c . ) A Transfer to Battery Occurred in the UPS Output U P S F a i l u r e t o T r a n s f e r t o B y p a s s o r B y p a s s A b n o r m a l i n E CO M o d e U t i l i t y I n p u t A b n o r m a l OFF UPS Shutoff LINE
Summary of the content on the page No. 13
6 – Standard Operation continued 6-3 Normal Mode Startup 1. Confirm that the UPS system is properly grounded. 2 . M a k e s u r e t h e u t i l i t y A C s u p p l y c i r c u i t b r e a k e r a n d t h e U P S s y s t e m ’ s i n p u t b r e a k e r a r e s w i t c h e d o f f . 3 . Wi r e t h e u t i l i t y A C s u p p l y c i r c u i t a n d o u t p u t c i r c u i t t o t h e U P S s y s t e m ’ s t e r m i n a l b l o c k a n d c on n e c t t h e e x t e r n a l ba t t e r y p a c k ,
Summary of the content on the page No. 14
6 – Standard Operation continued 6-4 Battery Mode Startup (Cold Start) The UPS system supports battery mode startup (cold start), allowing it to operate as a standalone power source when AC input power is unavailable. 1 . M a k e s u r e t h e U P S s y s t e m i s p r op e r l y i n s t a l l e d a n d t h e ba t t e r y i s a t l e a s t p a r t i a l l y c h a r g e d . 2 . S o m e e l e c t r on i c e q u i pm e n t m a y d r a w m o r e a m p s d u r i n g s t a r t u p ; c on s i d e r
Summary of the content on the page No. 15
6 – Standard Operation continued 6-6 UPS System Settings and Measurements continued Settings and Special Functions After the UPS starts up completely, press to view settings and execute special functions. Scroll down to review the settings. Use the Q1 Q2 R1 R2 bu t t on t o e x e c u t e s p e c i a l f u nc t i on s . S p e c i a l f u nc t i on s i nc l u d e bu z z e r O N o r bu z z e r O F F and self-test OFF o r s e l f - t e s t O N . Q1 S2 V3 B u z z e r “ O N ” B y p a s s
Summary of the content on the page No. 16
7 – Parallel Redundancy Operation (Optional) DANGER! LETHAL HIGH VOLTAGE HAZARD! All wiring should be performed by a qualified electrician, in accordance with the warnings in this manual and all applicable e l e c t r i c a l a n d s a f e t y c o d e s . I nc o r r e c t w i r i n g m a y c a u s e s e r i o u s p e r s on a l i n j u r y a n d p r op e r t y d a m a g e . R e a d , s t u d y a n d understand the warnings listed in Section 2 – Important Safety Instructions before proceeding.
Summary of the content on the page No. 17
8 – Communications Note: These connections are optional. The UPS system will function without these connections. 8-1 Network Card The UPS system includes an internal network card that provides an Ethernet interface for remote monitoring and control of the UPS system. Refer to the network card documentation for additional information. Note: The network card must be removed in order to use the UPS system’s RS-232 port. 8-2 EPO Connection Shorting the EPO terminals activates the EPO (emergency po
Summary of the content on the page No. 18
9 – Troubleshooting I f t h e U P S s y s t e m m a l f u nc t i on s d u r i n g op e r a t i on , c h e c k t h e f o l l o w i n g : • I s t h e i n p u t a n d o u t p u t w i r i n g c o r r e c t ? • I s t h e u t i l i t y A C i n p u t v o l t a g e w i t h i n t h e a c c e p t a b l e r a n g e f o r t h e U P S s y s t e m ? I f p r o b l e m s p e r s i s t s , p l e a s e r e f e r t o t h e i n s t r uc t i on s b e l o w . I f t h e p r o b l e m c on t i n ue s t o p e r s i s
Summary of the content on the page No. 19
10 – Specifications Input Voltage Range U p t o 1 6 0 - 2 8 0 / 2 7 7 - 4 8 5 V A C ( 3 Ø , 4 - Wi r e + G r o u n d , W y e ) ( 1 6 0 - 1 7 6 / 2 7 7 - 3 05 V A C a t L o a d < 7 5 % ) Frequency Range 4 5 t o 6 5 H z Power Factor U p t o 0 . 9 9 a t 1 0 0 % L i n e a r L o a d Output Voltage Range U s e r - Se l e c t a b l e 2 0 0 / 2 2 0 / 2 3 0 / 2 4 0 V A C ( 1 Ø , 2 - Wi r e + G r o u n d ) Voltage Adjustment ± 0 % ; ± 1 % ; ± 2 % ; ± 3 % Voltage Regulation ± 2% Capacity 1 0 k V A
Summary of the content on the page No. 20
12 – Battery Replacement DANGER! LETHAL HIGH VOLTAGE HAZARD! All service, including battery replacement, should be performed by qualified service personnel, in accordance with the warnings in this manual and all applicable electrical and safety codes. Read, study and understand the warnings listed in “Section 2 – Important Safety Instructions” before proceeding. Under normal conditions, the original batteries in the UPS system will last several years. The batteries are designed for hot-swap r