Toshiba G9000 user manual

User manual for the device Toshiba G9000

Device: Toshiba G9000
Category: Power Supply
Manufacturer: Toshiba
Size: 0.42 MB
Added : 11/24/2013
Number of pages: 17
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Toshiba G9000. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Toshiba G9000.

For your convenience

If looking through the Toshiba G9000 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Toshiba G9000 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Toshiba G9000 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Toshiba G9000 User manual - Online PDF
Advertisement
« Page 1 of 17 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Toshiba G9000 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Toshiba G9000. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1




CORPORATE OFFICE
13131 WEST LITTLE YORK ROAD HOUSTON, TX 77041
PHONE: (713) 466-0277 (800) 231-1412
FACSIMILE: (713) 896-5226









TOSHIBA G9000
80/100/160/225 kVA


GUIDE SPECIFICATION
THREE PHASE UNINTERRUPTIBLE POWER SUPPLY



1

Summary of the content on the page No. 2

Guide Specification – 3-Phase Static Uninterruptible Power Supply 2

Summary of the content on the page No. 3

Guide Specification – 3-Phase Static Uninterruptible Power Supply Table of Contents 1 SCOPE ......................................................................................................................................................................... 5 1.1 SYSTEM ............................................................................................................................................................................ 5 2 SYSTEM DESCRIPTION ...................

Summary of the content on the page No. 4

Guide Specification – 3-Phase Static Uninterruptible Power Supply 9.2 REMOTE STATUS ALARM PANEL (RSAP)............................................................................................................................... 15 10 TOSHIBA DISTRIBUTION CABNET (TDC) (OPTION) ..................................................................................................... 16 11 MAINTENANCE BYPASS PANEL (OPTION) ..........................................................................

Summary of the content on the page No. 5

Guide Specification – 3-Phase Static Uninterruptible Power Supply 1 SCOPE 1.1 System These specifications describe a high efficiency continuous duty, three-phase, on-line, solid-state Uninterruptible Power Supply system (UPS). The UPS shall operate utilizing the existing power distribution system to provide high quality, uninterruptible power to critical loads. The UPS shall consist of an AC/DC multi-level Insulated Gate Bipolar Transistor (IGBT) Rectifier, DC/DC Converter/Battery

Summary of the content on the page No. 6

Guide Specification – 3-Phase Static Uninterruptible Power Supply 2.3 System Operation: The UPS shall operate as a fully automatic on-line system in the following modes: 2.3.1 Normal IGBT Rectifier converts AC input power to DC power for the inverter and for charging the batteries. The IGBT inverter supplies clean and stable AC power continuously to the critical load. The UPS Inverter output shall be synchronized with the bypass AC source when the bypass source is within the AC input

Summary of the content on the page No. 7

Guide Specification – 3-Phase Static Uninterruptible Power Supply 3.2.3 Clearances for installation Ceiling Level : 20” minimum from top of UPS to ceiling Front : 40” minimum for maintenance (Local and regional codes may apply) Bottom : Knockouts for power cable access Rear : Zero clearance required Sides : Zero clearance if using bottom cable access (Standard knockouts for left/right side cable access ) Base : Channel mounted

Summary of the content on the page No. 8

Guide Specification – 3-Phase Static Uninterruptible Power Supply Current THD : <3% THD at 60%–100% load <6% THD at 25%–59% load (No input harmonic filter required) 4.1.3 Charging Function: DC Nominal Voltage : 480 V AC Ripple on DC Bus : < 0.2% of DC Voltage DC Voltage Range : 400 V to 545 V DC Float Charging Voltage : 545 V Maximum charging current: 80 kVA : 20 A 100 kVA : 25 A 160 kVA : 40 A 225 kVA : 56 A AC Ripple on D

Summary of the content on the page No. 9

Guide Specification – 3-Phase Static Uninterruptible Power Supply Harmonic Voltage Distortion : < 2% THD (100% Linear Load) : < 5% THD (100% Non-linear Load) Phase Displacement : 1° Maximum at 100% load Voltage Transients: 100% Load Step Change : +/-2% Maximum (Without battery assistance) Loss or Return of Input : +/-1% Maximum Transfer from Bypass to Inverter : +/-5% Maximum (At Bypass Rated Voltage) Recovery Time : 1 cycle 5 FUNCTIONAL DESCRIPTION

Summary of the content on the page No. 10

Guide Specification – 3-Phase Static Uninterruptible Power Supply 5.2.3 Battery Protection The converter shall be provided with monitoring and control circuits to protect the battery system from damage due to excessive discharge. Converter shutdown shall be initiated when the battery voltage reaches a discharge cutoff voltage of 400 VDC. Automatic shutdown based on discharge time is not acceptable. 5.2.4 DC Ripple AC Ripple on the DC Bus shall be less than 0.2%. AC Ripple on the Ba

Summary of the content on the page No. 11

Guide Specification – 3-Phase Static Uninterruptible Power Supply 5.3.5 Overload Capacity: The Inverter output shall be capable of providing an overload current of 125% for 2 min. and 150% for 1 min. A message on the control panel shall indicate this condition. If the time limit associated with the overload condition expires, or the overload is in excess of the set current limit, the load power shall transfer to the bypass source without interruption. 5.4 Static Bypass Circuit:

Summary of the content on the page No. 12

Guide Specification – 3-Phase Static Uninterruptible Power Supply If the bypass source is beyond the conditions stated below, interrupted transfer shall be made upon detection of a fault condition. Bypass voltage greater than + 10%, -10% from the UPS rated output voltage. Bypass frequency greater than + 1 Hz from the UPS rated output frequency. 5.4.2 Overload Capacity in Bypass: Continuous duty : 125% of the system rated capacity Overload duty : 1000% of ampere rating for 1 c

Summary of the content on the page No. 13

Guide Specification – 3-Phase Static Uninterruptible Power Supply 5.5.4 Mimic Panel A one-line diagram of the system shall be displayed on the touch panel display panel to provide a visual status of contactors within UPS. The panel shall display the followings: AC Input, DC Input Rectifier in Operation Inverter in Operation UPS/Bypass supply Battery Operating Condition (float charge/discharge) Fault, Warning Operation Guidance (LCD Display) Fault Guidance (LCD Display) 5.5.5 I

Summary of the content on the page No. 14

Guide Specification – 3-Phase Static Uninterruptible Power Supply 6 MECHANICAL DESIGN 6.1 UPS Enclosure The UPS shall be a freestanding NEMA1 enclosure equipped with a leveling channel base. The enclosure shall include provisions for hoisting, jacking, and forklift handling. 6.2 Cable Access Cable access to the UPS shall be Bottom entry Side entry, Top entry with when using optional side cabinet 7 WARRANTY 7.1 UPS Warranty The UPS shall come with a 36-month warranty o

Summary of the content on the page No. 15

Guide Specification – 3-Phase Static Uninterruptible Power Supply 9.1.2 HTTP Familiarity The RemotEye II shall provide a HTTP interface for the UPS to allow easy access of the UPS information from any machine with a web browser. At any time, a network workstation or management station shall be able to open a RemotEye II website. RemotEye II website shall enable the UPS system information to be configured and monitored remotely. RemotEye II shall provide access to 3 java applets for monit

Summary of the content on the page No. 16

Guide Specification – 3-Phase Static Uninterruptible Power Supply 10 TOSHIBA DISTRIBUTION CABNET (TDC) (OPTION) The manufacturer can optionally provide a matching TDC for the UPS. The TDC can include a step-down, 480/208/120 V transformer in a matching NEMA1 cabinet. The TDC can include a three-breaker MBS with a slidebar interlock. Interlock keys and Solenoid Key-Retractable Unit (SKRU) can be provided. The TDC can include up to eight 225 A sub-feed breakers. The TDC can includ

Summary of the content on the page No. 17

Guide Specification – 3-Phase Static Uninterruptible Power Supply 14 EXTENDED SERVICES (OPTION) The UPS manufacturer can offer : Startup Service Maintenance Contracts (Silver, Gold, Platinum) Preventive Maintenance Contracts Spare-parts kits (A, B, and C level) Extended warranty coverage for up to an additional 5 years Enhanced warranty contract (24/7 + Holiday coverage) Load bank testing Factory witness testing Site monitor and power audits 17


Alternative user manuals
# User manual Category Download
1 Toshiba 1500 User manual Power Supply 1
2 Toshiba 1600 User manual Power Supply 3
3 Toshiba 1600 Series User manual Power Supply 9
4 Toshiba 1500 SERIES User manual Power Supply 3
5 Toshiba 1000 Series User manual Power Supply 8
6 Toshiba 1500 Plus User manual Power Supply 1
7 Toshiba 15-80KVA User manual Power Supply 1
8 Toshiba 1600 XP UPS User manual Power Supply 82
9 Toshiba 1600EP Series User manual Power Supply 57
10 Toshiba 1800 User manual Power Supply 1
11 Toshiba 1700 Series User manual Power Supply 3
12 Toshiba 1800 SERIES User manual Power Supply 1
13 Toshiba 208 User manual Power Supply 1
14 Toshiba 4200FA CT/XT User manual Power Supply 5
15 Toshiba 4200FA XT User manual Power Supply 2
16 Sony AC U50A User manual Power Supply 5
17 Sony AC LS1 User manual Power Supply 2
18 Sony NP-FM30 User manual Power Supply 35
19 Sony NP FX101 User manual Power Supply 1
20 Sony NH-AAA-DA User manual Power Supply 2