APC EPW9 user manual

User manual for the device APC EPW9

Device: APC EPW9
Category: Power Supply
Manufacturer: APC
Size: 1.87 MB
Added : 4/2/2013
Number of pages: 24
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for APC EPW9. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with APC EPW9.

For your convenience

If looking through the APC EPW9 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual APC EPW9 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual APC EPW9 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
APC EPW9 User manual - Online PDF
Advertisement
« Page 1 of 24 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual APC EPW9 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to APC EPW9. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

Installation and
Operation
Emergency Power Off System
test

Summary of the content on the page No. 2

Legal Disclaimer The information presented in this manual is not warranted by the Schneider Electric IT Corporation to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan. Therefore, Schneider Electric IT Corporation assumes no liability for damages, violations of codes, improper installation, system failures, or any other problems that could arise based on the use of this Publication. The infor

Summary of the content on the page No. 3

T able of Contents IMPORT ANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS ............................................................................................................... 1 Safety Instructions for North America ................................................................... 1 Safety Instructions for Europe, Middle East, and Africa ................................... 2 Specifications ..............................................................................................

Summary of the content on the page No. 4

Emer gency Power Of f System Installation and Operation ii 990–161 1C-001

Summary of the content on the page No. 5

IMPORT ANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation, operation, and maintenance of the EPO system. Safety Instructions for North America W ARNING: Only certified electricians may install the system and the wiring to the pr oducts IT contr ols. W ARNING: Assembly has not been evaluated for emergency life critical applications, but is intended for emergency equipment power off. Note: W iring from the system

Summary of the content on the page No. 6

Safety Instructions for Europe, Middle East, and Africa W ARNING: Only certified electricians may install the system and the wiring to the pr oducts IT contr ols. W ARNING: Assembly has not been evaluated for emergency life critical applications, but is intended for emergency equipment power off. Note: W iring from the system to the products IT controls can either be installed in conduits or installed without conduits if the wires are in accordance with IEC/EN 60364-5-52 or equivalent local elec

Summary of the content on the page No. 7

Specifications Electrical Input/Output 24 VDC V oltage 48 VDC/240 V AC (External circuit) Current 1 A at 24 VDC 1 A at 48 VDC (External circuit) Frequency 50/60 Hz Circuits (qty) 9 Contact state Normally Open (NO) Physical Dimensions (W×L×D) EPO box 226 × 251×66 mm (8.9×9.9×2.6 in) Shipping 305 × 305×140 mm (12×12×5.5 in) W eight EPO box 2.9 kg (6.4 lb) Shipping 3.1 kg (6.9 lb) Mounting Surface mount Connection Removable panels in rear , 13 mm (½ in) and 6 mm (¾ in) knockouts on top and bottom P

Summary of the content on the page No. 8

Overview Emergency Power Off System The Emer gency Power Of f (EPO) System consists of one or more wall-mounted, push-button EPO boxes. Each EPO box provides a single point of equipment shutdown for up to eight APC devices and one third-party device (such as an upstream breaker), using Normally Open (NO) contact closure connections. An EPO box can be cascaded with other EPO boxes to support multiple points of equipment shutdown. Note: Although the EPO is designed specifically for APC products, t

Summary of the content on the page No. 9

Note: W iring, conduits, and mounting hardware are not provided. Emer gency Power Of f System Installation and Operation 990–161 1C-001 5

Summary of the content on the page No. 10

Installation Prepare the EPO 1. Open the EPO System box by removing the screws on the side. Keep the screws for use after the system is installed. The box will not close securely without the screws in place. 2. Mount the system in a readily-accessible area, on a wall near the principal entrance doors, according to NEC Articles 645.10 and 645.1 1, IEC/EN 60354-5-537, or equivalent local regulation. There are two dif ferent procedures for mounting the system, depending on whether you are running c

Summary of the content on the page No. 11

3. Install an appropriate fitting with a lock-nut for each knockout used. 4. Connect conduits to the fittings. Note: If not using conduits, run the cables through the knockout directly . Mount the EPO (running conduits or cables behind the wall) Two 120 mm (4 in) square junction boxes One 120 mm (4 in) square junction box One switch box up to 4-gang in size 1. Install a junction box or a switch box behind the wall. The EPO box will fasten directly to the box. Use one of the options above. Emer g

Summary of the content on the page No. 12

2. Run the conduits (or cables) from the connected devices to the junction or switch box. If using conduits, it will contain all wiring from the connected devices and all cascading cables. Remove the knockouts required for installation. Note: When planning conduit requirements, consider that two cascading cables will fit in 13 mm (½ in) conduits and four cascading cables will fit in 19 mm cascading cables will fit in 13 mm (¾ in) conduits. See “Cascade Multiple EPO Boxes “ for more information.

Summary of the content on the page No. 13

7. Reinforce the EPO box with 6 mm (¼ in) screws in the corner mounting holes. Note: The top two 6 mm (¼ in) mounting holes may be blocked by some junction boxes. In this instance, use only the bottom two 6 mm (¼ in) mounting holes for reinforcement. Connect Devices to the EPO Box Connect APC devices to terminals 1–8. Connect an auxiliary device to terminal 9. Connect only one 0.10–0.75 mm² (24–18 A WG) wire pair to each terminal block. 1. Attach EPO circuits to each device according to the spec

Summary of the content on the page No. 14

5. Connect a suitable ground or PE wire to the #8-32 ground stud in the lower left corner of the EPO box. Mount Additional EPO Boxes There are two alternatives for wiring additional EPO boxes. Either cascade the boxes only to wire devices to one box (see “Cascade Multiple EPO Boxes “ ), or wire devices directly to each EPO box (see “Direct W iring Alternative “ ). Cascade Multiple EPO Boxes When cascading EPO boxes, connect a wire pair from each device to the first EPO box according to the proce

Summary of the content on the page No. 15

EPO PAIRS 5 –8 EPO PAIRS 1 –4 APC APC APC APC APC APC APC APC Note: The recommended maximum total distance of wire, to run per circuit is 300 m (1000 ft). Cascade the APC Devices with CA T -5 Cables Connect the CA T -5 cables to the jacks inside the EPO box. Each cable can support up to four APC device wire pairs. Follow these guidelines when connecting CA T -5 cables: • Use only the bottom jacks (3 and 4) if cascading Box 1 Box 2 four (4) or fewer devices. Output Input 1 2 • Use both the bottom

Summary of the content on the page No. 16

Cascade the Auxiliary Device with W ire Pairs 1. After wires are run from auxiliary device (1) to terminal block position 9, run a second set of wires (2) from terminal block position 9 on the first EPO box to terminal block position 9 1 on the second EPO box. 2. Continue until all boxes are connected. (See 2 the diagram in “Cascade Multiple EPO Boxes “ for reference.) Direct W iring Alternative If the APC devices are centrally located between exit doors, it may be more practical to run separate

Summary of the content on the page No. 17

Note: If an APC FM Series Precision Air Conditioning System connected to the EPO box, pressing the check point will shut of f functionality to the unit, but the unit will still be powered. B. After verifying the wiring, close the system box, making sure not to pin wires or disturb connections, and secure with the screws, previously removed when opening the box. C. As a final test, apply power to all APC devices and auxiliary devices, and press the EPO button. All connected devices should power O

Summary of the content on the page No. 18

Operation Engage the System 1. Lift the shield on any of the installed EPO boxes and press the button. A red flag will drop down from the box, providing an easy visual mark as to which EPO box in your room has been activated. Reset the EPO System 1. Pull the button towards you (1) and push the flag up until it catches (2). Pulling the button does not bring power back to the connected equipment; it only resets the EPO system. Close the shield after resetting the system. 2 1 Emer gency Power Of f

Summary of the content on the page No. 19

Reset the Equipment Apply power to the devices according to the procedures for each device. Note: Refer to the operation manual included with each device for specific instructions on how to apply power to the device. Emer gency Power Of f System Installation and Operation 990–161 1C-001 15

Summary of the content on the page No. 20

W iring Diagram Emer gency Power Of f System Installation and Operation 16 990–161 1C-001


Alternative user manuals
# User manual Category Download
1 APC 208 Vac User manual Power Supply 8
2 APC 1400XLT User manual Power Supply 23
3 APC 15A User manual Power Supply 0
4 APC 120V User manual Power Supply 5
5 APC 2200XLT User manual Power Supply 24
6 APC 2000XL User manual Power Supply 15
7 APC 1000VA User manual Power Supply 24
8 APC 1500 VA User manual Power Supply 46
9 APC 300 User manual Power Supply 404
10 APC 5000VA User manual Power Supply 60
11 APC 500 User manual Power Supply 26
12 APC 3000VA User manual Power Supply 12
13 APC 3000T User manual Power Supply 1
14 APC 600 User manual Power Supply 64
15 APC 2AP9604S User manual Power Supply 1
16 Sony AC U50A User manual Power Supply 5
17 Sony AC LS1 User manual Power Supply 2
18 Sony NP-FM30 User manual Power Supply 35
19 Sony NP FX101 User manual Power Supply 1
20 Sony NH-AAA-DA User manual Power Supply 2