American Power Conversion PD80KF6FK1-M user manual

User manual for the device American Power Conversion PD80KF6FK1-M

Device: American Power Conversion PD80KF6FK1-M
Category: Power Supply
Manufacturer: American Power Conversion
Size: 2.85 MB
Added : 11/5/2013
Number of pages: 92
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for American Power Conversion PD80KF6FK1-M. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with American Power Conversion PD80KF6FK1-M.

For your convenience

If looking through the American Power Conversion PD80KF6FK1-M user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual American Power Conversion PD80KF6FK1-M on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual American Power Conversion PD80KF6FK1-M to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
American Power Conversion PD80KF6FK1-M User manual - Online PDF
Advertisement
« Page 1 of 92 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual American Power Conversion PD80KF6FK1-M but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to American Power Conversion PD80KF6FK1-M. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

80kW InfraStruXure PDU
PD80KF6FK1-M
PD80KG6FK1-M
PD80KL6FK1-M
Operation and Configuration
208/480/600V Input

Summary of the content on the page No. 2

Summary of the content on the page No. 3

About This Manual Audience This manual is intended for end-users of an 80kW InfraStruXure PDU. It covers the operation, customization, and quick configuration of the InfraStruXure PDU. It also includes basic InfraStruXure system operation. Companion manuals For additional information about the InfraStruXure system, see the following manuals that were included with the PDU: • InfraStruXure 80kW Installation and Start-Up (990-1467B) covers the installation and start-up of InfraStruXure UPS po

Summary of the content on the page No. 4

Summary of the content on the page No. 5

Contents Safety ......................................................................1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Save these instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Safety symbols used in this manual . . . . . . . . . . . . . . . . . . . 1 Cross-reference symbols used in this manual . . . . . . . . . . . . . 1 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Summary of the content on the page No. 6

Contacts Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Breakers Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Alarms Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 View Active Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Alarm/Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Alarm Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Summary of the content on the page No. 7

Configuring the Network Management Interface . . . . . . . . . . . 45 Connect the InfraStruXure PDU to your network . . . . . . . . . 45 Configuration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . 45 TCP/IP configuration methods . . . . . . . . . . . . . . . . . . . . . . 46 Device IP Configuration Wizard . . . . . . . . . . . . . . . . . . . . . . 46 BOOTP & DHCP configuration . . . . . . . . . . . . . . . . . . . . . . 47 Local access to the control console . . . . . . . . . .

Summary of the content on the page No. 8

Product Information .............................................. 71 InfraStruXure Standard Warranty. . . . . . . . . . . . . . . . . . . . . . . 71 Life-Support Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 How to Obtain Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 Appendix .............................................................. 75 Changes in This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 vi 80kW Infra

Summary of the content on the page No. 9

Safety Overview Save these instructions This manual contains important instructions that must be followed during installation, operation, and maintenance of the PDU. Safety symbols used in this manual Indicates an electrical hazard, which, if not avoided, could result in injury or death. Electrical Hazard Indicates a hazard, which, if not avoided, could result in personal injury or damage to product or other property. Warning Indicates a potential hazard which could result in damage to produc

Summary of the content on the page No. 10

Warnings Installation/Maintenance Only a certified electrician can perform these tasks: • Connect the InfraStruXure PDU to utility power • Connect the cross tie output breaker to another InfraStruXure PDU • Connect a switch to the EPO interface on the InfraStruXure PDU Only a certified electrician or an APC Field Service Engineer can perform these tasks: • Connect the PDU to the Symmetra PX UPS • Perform maintenance of the PDU When you connect the PDU to utility power, you must install a circui

Summary of the content on the page No. 11

Safety Total Power Off 1. Set the Symmetra PX UPS System Enable switch to Off. 2. Set the DC Disconnect breaker of each Battery Enclosure to Off. 3. Set the PDU Main Input (A) switch to Off. 4. If applicable, set the PDU Bypass Input (B) switch to Off 5. If applicable, set the PDU Cross Tie Output (X) breaker to Off. 6. Set the upstream utility power circuit breaker(s) to Off. 7. Disconnect the batteries in the Battery Enclosure by pulling them out to the red disconnect line. DANGER—Risk of El

Summary of the content on the page No. 12

Safety EMI This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with this user manual, may cause harmful interference to radio communications. Operat

Summary of the content on the page No. 13

Overview InfraStruXure PDU Components The APC 80kW InfraStruXure PDU provides distribution and management of electrical power. The InfraStruXure PDU has the capacity of 80kW, accepts 208, 480, or 600V, 3-phase input, and distributes 208V, 3-phase power to equipment racks and Rack Distribution Panels (RDPs). The RDPs sit in the top 10U of specially-designed NetShelter VX enclosures and distribute power to equipment racks. The InfraStruXure PDU is housed in a specially-designed 23-inch NetShel

Summary of the content on the page No. 14

Overview PDU front view (exterior)  PDU wide shielding  troughs—The PDU shielding  troughs accommodate the  power cables exiting the roof of the PDU. Power Cables—These power  cables feed equipment racks; they are fed through knockout panels on the top (or bottom) of the PDU. The power cables consist of five wires: three phases, one neutral, and one ground. The number of power  cables installed in the PDU depends on your system  configuration. Each power cable has a NEMA L

Summary of the content on the page No. 15

Overview Front view (interior) Ground lugs—Ground lugs  are provided for the Main Input switch, Bypass Input  switch, and Cross Tie Output  breaker. The main input lug  has two holes: one for a main  ground and one for the GEC. See the instruction sheet, Certified Electrician’s Instructions for more  information. Main Input switch (A)—   The main power source connects to your system at the Main Input switch. See  the instruction sheet, Certified Electrician’s Instruction

Summary of the content on the page No. 16

Overview Front view (door open) Wraparound  maintenance bypass panel—The  maintenance bypass panel has three circuit breakers that allow the UPS to be electrically isolated from the main power source, while maintaining the power panels. The input circuit breaker is labeled Q1, the output circuit breaker is labeled Q2, and the maintenance bypass  circuit breaker is labeled Q3. The label on the maintenance bypass panel of the PDU illustrates the power flow, and the  H2

Summary of the content on the page No. 17

Overview Rear view (interior) 42-position circuit breaker  panel—Each PDU has a circuit breaker panel with 42 pole positions. Each pole provides power at 120 volts L-N or 208 volts L-L. The  amperage each position  provides depends on the size of the circuit breaker used.  Panel current sensors—   Wires that feed the distribution panel pass through these current sensors, providing data to the PDU monitoring unit.  PDU monitoring unit—The PDU monitoring unit receives signals f

Summary of the content on the page No. 18

Overview PDU monitoring unit This connection provides the input power for the PDU monitoring  unit. The power is supplied by the monitoring unit circuit breaker  on the front of the PDU. If the panel is on, and the monitoring unit circuit breaker is closed, the monitoring unit is powered. Connects to sensors monitoring values such as voltage, current, and  power. Digital input sensing for monitoring such as circuit breaker status,  885-2288 transformer temperature, fans, etc. The Dis

Summary of the content on the page No. 19

Overview User connection plate For a description and location of the user connection plate, see ( ) on page 8. For clarity, the user  connection plate is shown in the following illustration in greater detail. \  !  USER INTERFACE © 2001 APC MADE IN USA  ! – + 1 23 4 EPO 24V EPO Contact Inputs Contact Outputs AC/DC Contact  !  Connect the InfraStruXure PDU to the network of the InfraStruXure Manager through the ethernet port.  The user connection plate has four input contact con

Summary of the content on the page No. 20


Alternative user manuals
# User manual Category Download
1 American Power Conversion 100 User manual Power Supply 0
2 American Power Conversion 120 User manual Power Supply 0
3 American Power Conversion 110, 120, 230 User manual Power Supply 0
4 American Power Conversion 10000 VA User manual Power Supply 1
5 American Power Conversion 1000, 1100, 1400 User manual Power Supply 2
6 American Power Conversion 110Vac User manual Power Supply 0
7 American Power Conversion 1400XLT User manual Power Supply 0
8 American Power Conversion 1050 User manual Power Supply 0
9 American Power Conversion 10-40kW 208/480V User manual Power Supply 0
10 American Power Conversion 2200 VA User manual Power Supply 0
11 American Power Conversion 2200XLT User manual Power Supply 0
12 American Power Conversion 208/220 User manual Power Supply 0
13 American Power Conversion 20000 VA User manual Power Supply 3
14 American Power Conversion 2200VA 3U User manual Power Supply 0
15 American Power Conversion 230 VAC User manual Power Supply 0
16 Sony AC U50A User manual Power Supply 5
17 Sony AC LS1 User manual Power Supply 2
18 Sony NP-FM30 User manual Power Supply 35
19 Sony NP FX101 User manual Power Supply 1
20 Sony NH-AAA-DA User manual Power Supply 2