Powerware powereware plus 8 - 10 kVA user manual

User manual for the device Powerware powereware plus 8 - 10 kVA

Device: Powerware powereware plus 8 - 10 kVA
Category: Power Supply
Manufacturer: Powerware
Size: 1.6 MB
Added : 11/18/2013
Number of pages: 46
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Powerware powereware plus 8 - 10 kVA. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Powerware powereware plus 8 - 10 kVA.

For your convenience

If looking through the Powerware powereware plus 8 - 10 kVA user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Powerware powereware plus 8 - 10 kVA on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Powerware powereware plus 8 - 10 kVA to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Powerware powereware plus 8 - 10 kVA User manual - Online PDF
Advertisement
« Page 1 of 46 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Powerware powereware plus 8 - 10 kVA but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Powerware powereware plus 8 - 10 kVA. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

User’s Guide
UPS 8 – 10 kVA,
230V 50/60 Hz output
(1-phase input)
&
UPS 8 – 15 kVA,
230V 50/60 Hz output
(3-phase input)

Summary of the content on the page No. 2

Copyright 2005 The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) unless permission granted. Every care has been taken to ensure the accuracy of the information contained in this manual, but no liability can be accepted for any errors or omission. The right to make design modifications is reserved.

Summary of the content on the page No. 3

UPS 8 – 10 kVA, 230V 50/60 Hz output (1-phase input) UPS 8 – 15 kVA, 230V 50/60 Hz output (3-phase input) User’s Guide 1022403 revision B1 Contents 1. Safety instructions ................................................................................................................ 4 Audience ..................................................................................................................................................... 4 CE marking ..........................................

Summary of the content on the page No. 4

1. Safety instructions The UPS operates with mains, battery or bypass power. It contains components that carry high currents and voltages. The properly installed enclosure is earthed and IP20 rated against electrical shock and foreign objects. However, only qualified personal is allowed to install and service the UPS. Warning! Operations inside the UPS must be performed by a service engineer from the manufacturer or from an agent authorised by the manufacturer. Do not ever service inside the UPS

Summary of the content on the page No. 5

Warning! The user is not permitted to open of any screws excluding connectivity plates and the MBS locking plate. Failure to recognise the electrical hazards could prove fatal. Environment The UPS must be installed according to the recommendations in this manual. Under no circumstances the UPS should be installed in an airtight room, in the presence of flammable gases, or in an environment exceeding the specification. Excessive amount of dust in the operating environment of UPS may cause damage

Summary of the content on the page No. 6

2. Mechanical installation The UPS and accessories are delivered on a specifically designed pallet that is easy to move with a forklift or a pallet jack. Keep the UPS always in upright position and do not drop the equipment. Do not either stack the pallets because of high-energy batteries involved and the heavy weight Delivery check The UPS is delivered with the following items: • Plastic bag containing: Quick Installation Guide, paper format, multilingual (coming later) User’s Guide, paper form

Summary of the content on the page No. 7

Check the information on the type designation label of the equipment to verify that the unit is of the correct type. The type designation label includes ratings, a CE marking, a type code, a part number and a serial number. The serial number is important when making inquiries. It allows individual recognition of the equipment. Figure 2. Type designation label. 1022403 7 UPS 8 – 15 kVA, 230V 50/60 Hz output Revision B1 User’s Guide

Summary of the content on the page No. 8

3. Planning before installation The equipment must be installed in upright position. The equipment requires space to front and back to enable cooling airflow, service and maintenance. All cooling air enters at front and exits at unit rear. The required min. clearance from unit rear to an obstruction is 150 mm. Figure 3. Ventilation space around the equipment. It is required to arrange ventilation of the UPS room. Sufficient amount of air cooling is needed to keep the max. room temperature rise a

Summary of the content on the page No. 9

4. Cabinet installation The required distance for UPS units next to each other is ten millimetres. The same applies to the optional battery cabinets that should be installed next to the UPS cabinet. Figure 5. UPS and external battery cabinets. The UPS family has several alternative battery cabinets and configurations depending on the selected back-up time and quality of batteries. Mechanical bypass switch The mechanical bypass switch (MBS) shall be mounted in back of the UPS battery compartment.

Summary of the content on the page No. 10

Figure 7. The mechanical bypass switch (MBS) when installed in the backside. Figure 8. 9155 MBS assembly 10 1022403 UPS 8 – 15 kVA, 230V 50/60 Hz output Revision B1 User’s Guide

Summary of the content on the page No. 11

Transformer option The galvanic isolation transformer can be ordered as factory installed. The transformer is an integral part of the UPS unit. Alternatively, the isolation transformer can be purchased as a separate item to upgrade your existing system. Figure 9. Transformer option can be ordered factory installed (integral) or separately. The overtemperature sensor cable is connected to the control input (X45 or X44) of the UPS, see the next drawing. In the factory installed systems this cable

Summary of the content on the page No. 12

External battery cabinet option It’s recommended to install external battery cabinets next to the UPS unit. The external battery can be placed on either side of the UPS unit. Check before the installation that the battery voltage values in the type plate of the UPS and external battery cabinets are the same. The cables are delivered with the external battery cabinet. See External Battery Cabinet (EBC) installation procedure. Warning! The UPS contains high DC voltages. A qualified person must do

Summary of the content on the page No. 13

5. Electrical installation The customer has to supply the wiring to connect the UPS to the local power source. The electrical installation procedure is described in the following text. The installation inspection and initial start up of the UPS and extra battery cabinet shall be carried out by a qualified engineer with UPS installation experience. Warning! Physical injury or death may follow, or damage may occur to the UPS, or the load equipment if these instructions are ignored. Figure 12. Loca

Summary of the content on the page No. 14

The UPS unit has the following power connections: • Three-phase (L1, L2, L3) and protective earth (PE) connection for the rectifier input or Single-phase (L1), Neutral (N) isolated connection point (bypass N is used in the rectifier) and protective earth (PE) connection for the rectifier input. • Single-phase (L1), Neutral (N) and protective earth (PE) connection for the bypass input • Single-phase (L1), Neutral (N) and protective earth (PE) connection for the load output • Plus (+), minus (-)

Summary of the content on the page No. 15

Contact the manufacturer’s authorised agent or the local office for assistance at fuse and cable sizing. Refer to the recommended cable and fuse ratings in the below table. Input Bypass Load PE Battery UPS rating Fusing Cable Fusing Cable Cable I nom Cable Cable 8e kVA3A -phas3² x163A x2.5 mm5² 01² 0 mm1A 0 mm3² 4.81² 0 mm 10 mm 1A -phase5² 0 1A 0 mm5² 01² 0 mm1A 0 mm3² 4.81² 0 mm 10 mm 1e 0 kVA3* -phas3² x16 A3A x2.5 mm5² 01² 0 mm1A 0 mm4² 3.51² 0 mm 10 mm 3A -phase3² x203A x4 mm5² 01² 0 mm1A 0

Summary of the content on the page No. 16

Figure 15. Wiring diagram of UPS N-model (3-ph rectifier) with integral MBS. Figure 16. Wiring diagram of UPS N-model (3-ph rectifier). 16 1022403 UPS 8 – 15 kVA, 230V 50/60 Hz output Revision B1 User’s Guide

Summary of the content on the page No. 17

Figure 17. Wiring diagram of UPS NT-model (3-ph rectifier) 1022403 17 UPS 8 – 15 kVA, 230V 50/60 Hz output Revision B1 User’s Guide

Summary of the content on the page No. 18

Figure 18. Wiring diagram of UPS S-model (1-ph rectifier) with integral MBS. Figure 19. Wiring diagram of UPS S-model (1-ph rectifier). 18 1022403 UPS 8 – 15 kVA, 230V 50/60 Hz output Revision B1 User’s Guide

Summary of the content on the page No. 19

Figure 20. Wiring diagram of UPS ST-model (1-ph rectifier). 1022403 19 UPS 8 – 15 kVA, 230V 50/60 Hz output Revision B1 User’s Guide

Summary of the content on the page No. 20

Note! Site wiring fault must be disabled from LCD User Settings menu. Figure 21. Wiring diagram of UPS S-model (1-ph rectifier) with integral MBS, (Norway) Note! Site wiring fault must be disabled from LCD User Settings menu. Figure 22. Wiring diagram of UPS S-model (1-ph rectifier), (Norway) 20 1022403 UPS 8 – 15 kVA, 230V 50/60 Hz output Revision B1 User’s Guide


Alternative user manuals
# User manual Category Download
1 Powerware 208/120V User manual Power Supply 8
2 Powerware 3110 User manual Power Supply 33
3 Powerware 400/230V User manual Power Supply 4
4 Powerware 4500 User manual Power Supply 5
5 Powerware 3115 User manual Power Supply 39
6 Powerware 5075 kVA User manual Power Supply 0
7 Powerware 5110 User manual Power Supply 24
8 Powerware 415/240V User manual Power Supply 0
9 Powerware 380/220V User manual Power Supply 0
10 Powerware 5105 User manual Power Supply 61
11 Powerware 5140 User manual Power Supply 0
12 Powerware 30-160kVA User manual Power Supply 5
13 Powerware 5115A USB User manual Power Supply 4
14 Powerware 5115RM User manual Power Supply 1
15 Powerware 8 - 15 kVA User manual Power Supply 9
16 Sony AC U50A User manual Power Supply 5
17 Sony AC LS1 User manual Power Supply 2
18 Sony NP-FM30 User manual Power Supply 35
19 Sony NP FX101 User manual Power Supply 1
20 Sony NH-AAA-DA User manual Power Supply 2