Mitsubishi 2033D SERIES user manual

User manual for the device Mitsubishi 2033D SERIES

Device: Mitsubishi 2033D SERIES
Category: Power Supply
Manufacturer: Mitsubishi
Size: 1.38 MB
Added : 12/14/2013
Number of pages: 54
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Mitsubishi 2033D SERIES. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Mitsubishi 2033D SERIES.

For your convenience

If looking through the Mitsubishi 2033D SERIES user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Mitsubishi 2033D SERIES on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Mitsubishi 2033D SERIES to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Mitsubishi 2033D SERIES User manual - Online PDF
Advertisement
« Page 1 of 54 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Mitsubishi 2033D SERIES but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Mitsubishi 2033D SERIES. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1




MITSUBISHI ELECTRIC AUTOMATION, INC.

UNINTERRUPTIBLE POWER SUPPLY SYSTEM

2033D SERIES

OWNERS / TECHNICAL MANUAL













Revision 1.3: December 18, 2003
ALN-H0963
MITSUBISHI ELECTRIC 2033D SERIES UPS

Summary of the content on the page No. 2

Page Number: MITSUBISHI 2033D SERIES UPS i ELECTRIC OWNERS / TECHNICAL MANUAL Preface 23D_00s.doc MITSUBISHI ELECTRIC 2033D SERIES UPS

Summary of the content on the page No. 3

Page Number: MITSUBISHI 2033D SERIES UPS ii ELECTRIC OWNERS / TECHNICAL MANUAL TABLE OF CONTENTS LIST OF TABLES ............................................................................................... iii LIST OF FIGURES ............................................................................................ iv HOW TO USE THIS MANUAL ........................................................................... v 1.0 INTRODUCTION ........................................

Summary of the content on the page No. 4

Page Number: MITSUBISHI 2033D SERIES UPS iii ELECTRIC OWNERS / TECHNICAL MANUAL List of Tables Table 1.1 Power Specifications ................................................................... 1-11 Table 1.2 UPS Module Information.............................................................. 1-11 Table 1.3 Detail of Specifications ................................................................ 1-12 Table 1.4 Rating of Contactor and Fuses..........................................

Summary of the content on the page No. 5

Page Number: MITSUBISHI 2033D SERIES UPS iv ELECTRIC OWNERS / TECHNICAL MANUAL List of Figures Figure 1.1 Single Line Diagram-Normal Operation.................................................... 1-5 Figure 1.2 Single Line Diagram-Bypass Operation.................................................... 1-6 Figure 1.3 Single Line Diagram-Battery Operation .................................................... 1-7 Figure 1.4 UPS Parts Location ..............................................

Summary of the content on the page No. 6

Page Number: MITSUBISHI 2033D SERIES UPS v ELECTRIC OWNERS / TECHNICAL MANUAL How to use this Manual This manual is designed for ease of use, giving the user easy and quick reference to information. This manual uses notice icons to draw attention to the user important information regarding the safe operation and installation of the UPS. The notice icons used in this manual are explained below, and should be taken into account and adhered to whenever they appear in the text of t

Summary of the content on the page No. 7

Page Number: MITSUBISHI 2033D SERIES UPS 1-1 ELECTRIC OWNERS / TECHNICAL MANUAL 1.0 INTRODUCTION Your Mitsubishi Uninterruptible Power Supply System (UPS) is designed to provide many years of reliable protection from power failure, brown-outs, line noise, and voltage transients. To ensure optimum performance of the equipment, follow the manufacturer's instructions. This manual contains descriptions required to operate the UPS. Please read this manual carefully and retain it for

Summary of the content on the page No. 8

Page Number: MITSUBISHI 2033D SERIES UPS 1-2 ELECTRIC OWNERS / TECHNICAL MANUAL WARNING 2 This UPS does not include a Bypass input circuit breaker (MCCB) to protect bypass circuit. Bypass input circuit breaker (MCCB) are to be field supplied and installed. Recommended Breaker (MCCB)'s Specifications are as follows: Recommended Capacity (kVA) Bypass Voltage (Vac) Bypass Rating (Aac) Breaker (Aac) 30 480 36 45 50 480 60 80 80 480 96 125 AC input and AC output over

Summary of the content on the page No. 9

Page Number: MITSUBISHI 2033D SERIES UPS 1-3 ELECTRIC OWNERS / TECHNICAL MANUAL 1.1 GENERAL The Mitsubishi 2033D Series UPS is designed to provide continuous and clean electrical power to a critical load. Additionally the UPS monitors power conditions affecting the load. In the event of an input power failure, the UPS will supply power to the critical load for the specified battery time. If the input power is not restored promptly, back up power from the UPS battery permits

Summary of the content on the page No. 10

Page Number: MITSUBISHI 2033D SERIES UPS 1-4 ELECTRIC OWNERS / TECHNICAL MANUAL 1.2 Definitions UNINTERRUPTIBLE POWER SUPPLY SYSTEM (UPS) - All components within the UPS Module Cabinet and associated batteries that function as a system to provide continuous, conditioned AC power to a load. This is sometimes referred to as the "System". UPS MODULE CABINET - The metal enclosure which contains the Converter, the Inverter, the Chopper, the Static Transfer Switch, the Internal By

Summary of the content on the page No. 11

Page Number: MITSUBISHI 2033D SERIES UPS 1-5 ELECTRIC OWNERS / TECHNICAL MANUAL 1.3 Overview The UPS provides two power paths between the utility source and the critical load. Figure 1.1 shows the path for normal operation, with the load powered from the inverter. Figure 1.2 shows the path for bypass operation, with the load supplied through the static bypass line. Figure 1.3 shows the path for battery operation, with the load supplied from the inverter. A) Normal Operatio

Summary of the content on the page No. 12

Page Number: MITSUBISHI 2033D SERIES UPS 1-6 ELECTRIC OWNERS / TECHNICAL MANUAL B) Internal Static Bypass Line FIGURE 1.2 Single Line Diagram- Bypass Operation. Load fed through static bypass line. CB Maintenance AC Bypass Static Transfer Bypass Input Switch Switch 52RS CONVERTER INVERTER CB AC input Output 52RC 52C FI FO User 52CS supplied FB 72B Power Flow Not in Use BATTERY 50kVA, 80kVA: UPS Module External Battery Referring to Figure 1.2, t

Summary of the content on the page No. 13

Page Number: MITSUBISHI 2033D SERIES UPS 1-7 ELECTRIC OWNERS / TECHNICAL MANUAL C) Inverter supply at battery operation FIGURE 1.3 Single Line Diagram - Battery Operation CB Maintenance AC Bypass Static Transfer Bypass Input Switch Switch 52RS CONVERTER INVERTER CB AC input Output 52RC 52C FI FO User 52CS supplied FB 72B Power Flow Not in Use BATTERY 50kVA, 80kVA: UPS Module External Battery Referring to Figure 1.3: In the event of AC input s

Summary of the content on the page No. 14

Page Number: MITSUBISHI 2033D SERIES UPS 1-8 ELECTRIC OWNERS / TECHNICAL MANUAL FIGURE 1.4-a UPS Parts Location (30kVA) UPS module FRONT VIEW Inverter Converter Unit unit Chopper Unit DC 52RS Capacitor 52RC 52CS 72B 1. External I/F Circuit PCB 52C IOAU-05 2. Grounding Bar Parallel I/F PCB GND GND ELEC TERM FIGURE 1.4-b UPS Parts Location (50kVA, 80kVA) UPS module FRONT VIEW Inverter unit Converter Chopper Unit 52C 52RS

Summary of the content on the page No. 15

Page Number: MITSUBISHI 2033D SERIES UPS 1-9 ELECTRIC OWNERS / TECHNICAL MANUAL FIGURE 1.5 UPS Parts Location (Continued) UPS module BACKSIDE OF FRONT DOOR(Right side) SYNC.LED INVERTER INVERTER 5 6 START STOP | | | | | | BOOT FAULT MAINTENANCE TEST SWITCH RESET BUTTON SWITCH 10 8 9 7 FIGURE 1.6 External I/F PCB IOAU-05 3. External Contact Signal Terminal IOAU-05 4

Summary of the content on the page No. 16

Page Number: MITSUBISHI 2033D SERIES UPS 1-10 ELECTRIC OWNERS / TECHNICAL MANUAL Description of Figures 1.4, 1.5, and 1.6: 1. External I/F Board (IOAU-05) : FOR SERVICE PERSONNEL ONLY (FIGURE 1.6): - (3) External contact signal terminal - (4) RS232C communication connector 2. Grounding Bar (E) 3. External Contact Signal Terminal Block - Terminal block to connect contact signal input/output lines to and from the external devices. Refer to Figure 2.15 section 2.5 for details.

Summary of the content on the page No. 17

Page Number: MITSUBISHI 2033D SERIES UPS 1-11 ELECTRIC OWNERS / TECHNICAL MANUAL 1.4 Specifications The UPS name plate displays the rated kVA as well as nominal voltages and currents. The name plate is located on the inside of the UPS front door. TABLE 1.1 Power Specifications Rated output Input voltage Bypass input voltage Output voltage Power 3 phase / 3 wire 3 phase / 3 wire 3 phase / 3 or 4 wire 30kVA / 24kW 480V 480V 208V or 480V 50kVA / 40kW 480V 480V 208V or 480

Summary of the content on the page No. 18

Page Number: MITSUBISHI 2033D SERIES UPS 1-12 ELECTRIC OWNERS / TECHNICAL MANUAL TABLE 1.3 Detail of Specifications Rated Output kVA 30 50 80 Rated Output kW 24 40 64 AC INPUT Configuration 3 phase, 3 wire Voltage 480 V +15% to -15% (-30% can be operated) Frequency 60 Hz (45.4Hz to 65Hz) Reflected Current THD 4% typ. at 100% load; 7% typ. at 50% load STATIC BYPASS INPUT Configuration 3 phase, 3 wire Voltage 480 V +/-10% Frequency 60 Hz BATTERY Type Lead Acid

Summary of the content on the page No. 19

Page Number: MITSUBISHI 2033D SERIES UPS 1-13 ELECTRIC OWNERS / TECHNICAL MANUAL TABLE 1.4 Rating of Contactors and Fuses NUMBER APPLICATION OUTPUT CAPACITY OF EQUIPMENT 2033D-B 2033D-A 2033D-B 30VA 50kVA 50kVA 80kVA 208V 480V 208V 480V 208V 480V 208V 480V C 52RC AC Input 60A 100A O Contactor N 52C AC Output 60A 100A T Contactor A 52RS Bypass Contactor 60A 100A C 72B Battery Disconnect 80A 135A 200A T Contactor O 88RC Control circuit 90A R Contactor FIU, FIV,

Summary of the content on the page No. 20

Page Number: MITSUBISHI 2033D SERIES UPS 2-1 ELECTRIC OWNERS / TECHNICAL MANUAL 2.0 OPERATOR CONTROLS AND INDICATORS The 2033D Series operator controls and indicators are located as follows: Circuit breakers and contactors: Inside the module UPS status indicators: Outside of front door FIGURE 2.1 Operation/Display Panel (Front panel) 3 4 2 5 1 6 BATTERY LOAD ON LCD UPS LOAD ON INVERTER OP. BYPASS FAULT FAULT OVER LOAD 9 540V 48A STS 52


Alternative user manuals
# User manual Category Download
1 Mitsubishi 9800A Series User manual Power Supply 54
2 Mitsubishi FR - S500 User manual Power Supply 1426
3 Sony AC U50A User manual Power Supply 5
4 Sony AC LS1 User manual Power Supply 2
5 Sony NP-FM30 User manual Power Supply 35
6 Sony NP FX101 User manual Power Supply 1
7 Sony NH-AAA-DA User manual Power Supply 2
8 3Com 3645A User manual Power Supply 0
9 3Com 3CNJPSE24 User manual Power Supply 2
10 3Com COREBUILDER 5000 User manual Power Supply 0
11 3Com 3646A User manual Power Supply 0
12 3Com External PoE Power System PSE2500-A3 User manual Power Supply 1
13 Sony AC E45HG User manual Power Supply 10
14 3Com Powerware Uninterruptible Power System Prestige Series User manual Power Supply 7
15 AB Soft ATX 12V User manual Power Supply 0