Liebert UPSTATION GXT 2U user manual

User manual for the device Liebert UPSTATION GXT 2U

Device: Liebert UPSTATION GXT 2U
Category: Power Supply
Manufacturer: Liebert
Size: 1.42 MB
Added : 3/24/2013
Number of pages: 44
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Liebert UPSTATION GXT 2U. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Liebert UPSTATION GXT 2U.

For your convenience

If looking through the Liebert UPSTATION GXT 2U user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Liebert UPSTATION GXT 2U on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Liebert UPSTATION GXT 2U to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Liebert UPSTATION GXT 2U User manual - Online PDF
Advertisement
« Page 1 of 44 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Liebert UPSTATION GXT 2U but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Liebert UPSTATION GXT 2U. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

POWER AVAILABILITY
UPStation GXT 2U™
USER MANUAL
500-3000VA
120V

Summary of the content on the page No. 2

Summary of the content on the page No. 3

TABLE OF CONTENTS 1.0 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . 3 2.0 INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3.0 MAJOR COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . 5 3.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 3.2 Rectifier/Power Factor Correction (PFC) Circuit . . . . . . 5 3.3 Inverter . . . . . . . . . . . . . . . . . . . . . . . . . .

Summary of the content on the page No. 4

6.0 OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . 17 6.1 Normal Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . 17 6.2 Bypass Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . 17 6.3 Battery Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . 18 6.4 Battery Recharge Mode . . . . . . . . . . . . . . . . . . . . . . . . . 18 7.0 COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 7.1 Communications Interface Port. . . .

Summary of the content on the page No. 5

IMPORTANT SAFETY INSTRUCTIONS WARNING ! Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source. Observe all cautions and warnings in this manual. Failure to do so MAY result in serious injury or death. Refer all UPS and battery service to qualified service personnel. Do not attempt to service this product yourself. Never work alone. SAVE THESE INSTRUCTIONS Thi

Summary of the content on the page No. 6

This UPS contains no user serviceable parts except the internal bat- tery pack. The UPS ON/Standby push buttons do not electrically iso- late internal parts. Under no circumstances attempt to gain access internally other than to replace the batteries due to risk of electric shock or burn. Do not continue to use the UPS if the front panel indi- cations are not in accordance with these operating instructions or if the UPS performance alters in use. Refer all faults to your local dealer, Lieber

Summary of the content on the page No. 7

Glossary of Symbols 1.0 GLOSSARY OF SYMBOLS Risk of electrical shock Indicates caution followed by important instructions AC input AC output Requests the user to consult the manual i Indicates the unit contains a valve-regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON Standby 3

Summary of the content on the page No. 8

Introduction 2.0 INTRODUCTION Congratulations on your choice of the Liebert UPStation GXT 2U™ Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment. Upon generation, AC power is clean and stable. However, during transmission and distribution it may be subject to voltage sags, spikes, or complete power failure that may interrupt computer opera- tions, cause data loss, or even damage equipment. The UPStation GXT 2U protect

Summary of the content on the page No. 9

Major Components 3.0 MAJOR COMPONENTS Input Output Dynamic Bypass TVSS & Rectifier L1 Inverter L1 EMI/RFI /PFC Filters DC to DC Converter Battery Battery Charger L2 L2 G G 3.1 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS These UPS components provide surge protection and filter both elec- tromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the utility line and keep the sensitive equipment protected. 3.

Summary of the content on the page No. 10

Major Components 3.4 BATTERY CHARGER The battery charger utilizes energy from the utility power and pre- cisely regulates it to continuously “float charge” the batteries. The bat- teries are being charged whenever the UPStation GXT 2U is plugged in, even when the UPS is not turned on. 3.5 DC TO DC CONVERTER The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously

Summary of the content on the page No. 11

Major Components 3.8 GXT 2U (REAR VIEW) ® Intellislot Port DB-9 Communications Port Cooling Fan External Battery Input Fuse/Circuit Connector Breaker Output Receptacles AC Input Support Base 7

Summary of the content on the page No. 12

Installation 4.0 INSTALLATION 4.1 PREPARATION 1. Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or Liebert representative. CAUTION ! The UPS is heavy (see 11.0 - Specifications). Take proper precautions when lifting or moving it. 2. Decide where to place the GXT 2U. Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it in an area of unrestricted airflow around the unit, away from water, flam

Summary of the content on the page No. 13

UPStation GXT –+ AC INPUT BATTERY UPS ON BYPASS Installation 4.3 RACK-MOUNT UPS CONVERSION AND INSTALLATION NOTE When rack mounted, the UPS must be supported by a shelf, brackets or slide rails on each side. The rack mount handles WILL NOT support the weight of the UPS. They are used to move the UPS into and out of the rack. 1. For slide rail installations, first remove the top/side fin. Slide the top/side fin forward, then lift it up to remove. If desired, install the optional rack mount ha

Summary of the content on the page No. 14

Installation 3. Determine the height position inside the rack enclosure where you want to mount the UPS or battery cabinet. CAUTION ! Reduce risk of tipping the rack enclosure by placing UPS or battery cabinet in the lowest possible rack position. Install rear member of each M5 screws bracket assembly into rack Front rack mounting rails enclosure with two (2) M5 screws provided in this kit. (See figure at right.) Return flanges on bracket assembly fit to the inside of rack mounting rai

Summary of the content on the page No. 15

Installation 5. Prepare the UPS or battery M4 Retaining cabinet (the “equipment”) for screws latch rack mounting by following instructions in the equipment’s user manual. The equipment may require additional parts to UPS or battery be added or parts to be removed cabinet for rack mounting. After it is prepared, lay equipment in rack-mounting position. Fasten inner members from Step 2 to Front the equipment on both sides as M4 shown in the figure at right screws with (8) M4 screw

Summary of the content on the page No. 16

Installation 8. Secure front of the equipment to rack mounting rails to prevent the equipment from sliding out of position. If securing holes are provided on front of the equipment that align with the center holes on return flange of front members, you can use the four (4) extra M5 screws provided in this kit to secure the equipment. Otherwise, the equipment should be secured to front of rack mounting rails with four (4) customer-supplied fasteners. 9. To orient the display for Vertical H

Summary of the content on the page No. 17

Installation 4.4 EXTERNAL BATTERY CABINET INSTALLATION Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath the UPS. There is no limit to the number of external battery cabinets that can be used but each cabinet will increase the battery recharge time. CAUTION ! The external battery cabinet(s) are heavy (see 11.0 - Specifications). Exter

Summary of the content on the page No. 18

Controls and Indicators 5.0 CONTROLS AND INDICATORS All LEDs illuminated for illustrative purposes only. 5.1 ON/ALARM SILENCE/MANUAL BATTERY TEST BUTTON This button controls output power to connected load(s) and has three functions: •ON •Alarm Silence •Manual Battery Test ON - Pressing this button will start up the UPS in order to provide conditioned and protected power. Alarm Silence - To silence alarms, press this button for at least one second. After the alarm is silenced, the UPStation GX

Summary of the content on the page No. 19

Controls and Indicators 5.2 STANDBY/MANUAL BYPASS BUTTON This button controls output power to connected load(s) and has dual functions: Standby and Manual Bypass. CAUTION ! While the UPS is in Normal Mode operation, pressing the Standby/ Manual Bypass button once will put the UPS into Bypass Mode. Once the UPS is in Bypass Mode operation, press the Standby/ Manual Bypass button two distinct times (for about one second each time) to turn off the UPS. Perform all necessary shutdown procedure

Summary of the content on the page No. 20

Controls and Indicators 5.8 AC INPUT INDICATOR LED (GREEN) The AC Input indicator LED is illuminated when utility power is available and within the input specifications. 5.9 OUTPUT VOLTAGE SELECTION The Output Voltage is user configurable and is designed to allow selecting or changing the desired output voltage to match the utility via the GXT 2U Configuration Program provided with the UPS. The settings to choose from are 100, 110, 115, 120, and 127 VAC output. The factory default setting


Alternative user manuals
# User manual Category Download
1 Liebert 130 kVA User manual Power Supply 19
2 Liebert 208V User manual Power Supply 13
3 Liebert 1500 User manual Power Supply 27
4 Liebert 30-130kVA User manual Power Supply 8
5 Liebert 115V User manual Power Supply 8
6 Liebert 230V User manual Power Supply 13
7 Liebert 2U User manual Power Supply 11
8 Liebert 2700VA User manual Power Supply 6
9 Liebert 500-650 VA User manual Power Supply 4
10 Liebert 4000 User manual Power Supply 4
11 Liebert 50 and 60 Hz User manual Power Supply 1
12 Liebert 350-700 VA User manual Power Supply 2
13 Liebert 6000 A User manual Power Supply 7
14 Liebert 600TTM User manual Power Supply 2
15 Liebert 700-2200 VA User manual Power Supply 13
16 Sony AC U50A User manual Power Supply 5
17 Sony AC LS1 User manual Power Supply 2
18 Sony NP-FM30 User manual Power Supply 35
19 Sony NP FX101 User manual Power Supply 1
20 Sony NH-AAA-DA User manual Power Supply 2