Liebert UPS Systems PSI XR user manual

User manual for the device Liebert UPS Systems PSI XR

Device: Liebert UPS Systems PSI XR
Category: Power Supply
Manufacturer: Liebert
Size: 1.59 MB
Added : 3/24/2013
Number of pages: 32
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Liebert UPS Systems PSI XR. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Liebert UPS Systems PSI XR.

For your convenience

If looking through the Liebert UPS Systems PSI XR user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Liebert UPS Systems PSI XR on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Liebert UPS Systems PSI XR to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Liebert UPS Systems PSI XR User manual - Online PDF
Advertisement
« Page 1 of 32 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Liebert UPS Systems PSI XR but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Liebert UPS Systems PSI XR. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

AC Power
For Business-Critical Continuity™
® ™
Liebert PSI XR
User Manual–1000/1500/1920/3000VA, 60Hz, 120VAC

Summary of the content on the page No. 2

Summary of the content on the page No. 3

TABLE OF CONTENTS 1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 2.0 WHAT’S INCLUDED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 3.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 3.1 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Summary of the content on the page No. 4

7.0 BATTERY MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 7.1 Battery Charging, Storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 7.2 Internal Battery Replacement Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 8.0 SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Summary of the content on the page No. 5

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and mainte- nance of the UPS. • Intended for installation in a temperature-controlled, indoor area free of conductive contami- nants. • Maximum ambient temperature 104°F (40°C). Read this manual thoroughly before attempting to install or operate this UPS. The equipment can be installed and operated by individuals without previous training. WARNING ! Opera

Summary of the content on the page No. 6

ELECTROMAGNETIC COMPATIBILITY—The Liebert PSI XR complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: • This device may not cause harmful interference, and • This device must accept any interference received, including interference that may cause unde- sired operation. This equipment uses, generates and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference with radio commun

Summary of the content on the page No. 7

GLOSSARY OF SYMBOLS Risk of electrical shock Indicates caution followed by important instructions ! Indicates the unit contains a valve-regulated, lead-acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON/Alarm Silence/Manual Self-Diagnostic Test OFF Status Change Button 3

Summary of the content on the page No. 8

Introduction 1.0 INTRODUCTION ™ The Liebert PSI XR is a 2U, line-interactive UPS that may be installed in a rack or used as a tower UPS. Status indicators on the front of the Liebert PSI XR display load level, battery level, buck/boost, site- wiring fault and battery status. Controls include a combination ON/ Alarm Silence/Manual Self-Diag- nostic button, an Off button and a Display Status Change button. The Liebert PSI XR has USB, DB-9 (RS232/contact closure) and SNMP interface ports. The DB-9

Summary of the content on the page No. 9

Introduction Figure 3 1920VA—rear view 15A Output Circuit Breaker Receptacles #3 and #4 for Receptacles #3 & #4 Power Cord; 5-20P NEMA 5-15R (not shown for clarity) RS232 (DB-9) Receptacles #1 and #2; Receptacles Port Liebert NEMA 5-20R T-Slot #5 and #6 30A Input IntelliSlot NEMA 5-15R Circuit Breaker Port INPUT EPO FUNCTION 2 1 VOLTAGE=110V OUTPUT VOLTAGE=120V VOLTAGE=127V DC 48V EPO External Battery USB Port Cabinet Connector RJ-45 Data 20A Input Circuit Breaker 15A Output Circuit Break

Summary of the content on the page No. 10

What’s Included 2.0 WHAT’S INCLUDED The Liebert PSI XR is shipped with the following items: • Multi-Language User Manual on CD • Liebert MultiLink Shutdown Software and User Manual on CD • DB-9 Serial Cable • USB Cable • Tower Stand • Rack-Mount Handles • Battery-UPS Tab • Mounting Hardware • Fixed Mounting Rails •EPO Connector Figure 5 Accessories Liebert Shutdown Software Program Liebert MultiLink Battery-UPS Tab Shutdown Software & User Manual on CD DB-9 USB cable Serial Cable 6 ft (1.8

Summary of the content on the page No. 11

AIR AIR Installation 3.0 INSTALLATION 3.1 Preparation CAUTION ! The UPS and battery cabinets are heavy (see Table 6 and Table 7). Take proper precautions when lifting or moving either the UPS or battery cabinets. The Liebert PSI XR may be installed in either a tower or rack configuration. Determine the method that suits the application and proceed. Decide where to install the Liebert PSI XR. The UPS must be installed indoors in a controlled envi- ronment. Place it in an area with unrestricted

Summary of the content on the page No. 12

Installation 3.2 Tower UPS Installation See Figure 7 when using the Liebert PSI XR in a tower configuration. Figure 7 Tower configuration—attach Tower Stand Step 2 Step 1 8

Summary of the content on the page No. 13

Load Level Battery Level L Bo aa td te L ry e vL ee lvel v B y v v B y v Load Le el atter Le el Load Le el atter Le el Installation 3.3 Rack-Mount UPS Conversion and Installation See Figure 8 when installing the Liebert PSI XR in a rack. External battery cabinets are installed in same manner. Figure 8 Convert the Liebert PSI XR for rack installation Step 1 Step 2 Step 4 Step 3 Step 5 WARNING ! Placing heavy equipment near the top of a rack may increase the risk of tipping. Place the UPS, and b

Summary of the content on the page No. 14

INPUT OUTPUT EPO FUNCTION 2 1 VOLTAGE=110V VOLTAGE=120V VOLTAGE=127V DC 24V Installation 3.4 Orient Display for Installation The Liebert PSI XR features a rotating display that may be oriented for either tower or rack installa- tions. To set the display for your installation, pull out on the display and rotate it until it is oriented cor- rectly, then press it into the UPS until it is seated. Figure 9 Adjusting the UPS display 3.5 Connect Input Power and Load Connect input power to the UPS, then

Summary of the content on the page No. 15

INPUT OUTPUT EPO FUNCTION 2 1 VO LTAGE= 110V VO LTAGE=120V VO LTAGE=127V DC 24V Installation 3.6 Connect Network Surge protection Connect a 10 base-T/100 network cable to the RJ-45 network surge protection IN jack on the rear of the UPS. Connect from the OUT jack with network cabling to network equipment (see Figure 11). Figure 11 Connect network surge protection Network Equipment INPUT OUTPUT EPO FUNCTION 2 1 VOLTAGE=110V VOLTAGE=120V VOLTAGE=127V DC 24V Network surge Network surge protection

Summary of the content on the page No. 16

Installation 3.8 EPO Switch The Liebert PSI XR is equipped with an Emergency Power Off (EPO) switch. The user must supply a means of interfacing with the EPO circuit to allow disconnecting the UPS input feeder breaker to interrupt all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations. Figure 13 EPO connection for normally open operation 1 = EPO+ 2 = Ground 12 Short Pin 1 and Pin 2 to enable the EPO function 3.9 External Battery

Summary of the content on the page No. 17

Installation Figure 15 Connect battery cabinets to UPS INPUT OUTPUT EPO FUNCTION 2 1 VOLTAGE=110V VOLTAGE=120V VOLTAGE=127V DC 24V See Table 8 for approximate battery run times. 13

Summary of the content on the page No. 18

Controls and Indicators 4.0 CONTROLS AND INDICATORS Buttons on the front panel display control the Liebert PSI XR. Eight LEDs indicate the UPS’s status. Refer to Figure 16 and Table 2. Figure 16 Display and status indicators 12 3 4 5 Load Level Battery Level 67 8 91011 Table 2 Display and status indicators function, legend Item Name Status Indicators Description 1 LED 1 AVR Boost UPS Operation in AVR Boost Mode 2 LED 2 AVR Buck UPS Operation in AVR Buck Mode 3 LED 3 Battery Condition Battery Fa

Summary of the content on the page No. 19

Controls and Indicators 4.1 Control Buttons 4.1.1 On/Alarm Silence/Manual Self-Diagnostic Test This button controls output power to connected load(s). It has three functions: •On •Alarm Silence • Manual Self-Diagnostic Test ON—Start the UPS by pressing this button for more than 3 seconds, then releasing the button (an alarm will sound briefly). If the ON button is pressed and utility is outside input parameters, the UPS will start on battery (dark start). Alarm Silence—Silence a battery mode a

Summary of the content on the page No. 20

Controls and Indicators 4.2.3 Battery Level Indicator The five LEDs illuminate with a steady glow to indicate battery capacity. Battery capacity is shown for five seconds after the Status Change Button is pressed. The LEDs show the battery capacity as a range, ± 5% The LEDs’ battery level meanings and colors are: LED 1LED 2LED 3LED 4LED 5 100 - 76% — Green 75 - 51% — Green 50 - 26% — Yellow 25 - 11% — Yellow 10% or less — Red 4.2.4 UPS Status Indicators LEDs on the display panel illuminate wit


Alternative user manuals
# User manual Category Download
1 Liebert 130 kVA User manual Power Supply 19
2 Liebert 208V User manual Power Supply 13
3 Liebert 1500 User manual Power Supply 27
4 Liebert 30-130kVA User manual Power Supply 8
5 Liebert 115V User manual Power Supply 8
6 Liebert 230V User manual Power Supply 13
7 Liebert 2U User manual Power Supply 11
8 Liebert 2700VA User manual Power Supply 6
9 Liebert 500-650 VA User manual Power Supply 4
10 Liebert 4000 User manual Power Supply 4
11 Liebert 50 and 60 Hz User manual Power Supply 1
12 Liebert 350-700 VA User manual Power Supply 2
13 Liebert 6000 A User manual Power Supply 7
14 Liebert 600TTM User manual Power Supply 2
15 Liebert 700-2200 VA User manual Power Supply 13
16 Sony AC U50A User manual Power Supply 5
17 Sony AC LS1 User manual Power Supply 2
18 Sony NP-FM30 User manual Power Supply 35
19 Sony NP FX101 User manual Power Supply 1
20 Sony NH-AAA-DA User manual Power Supply 2