Liebert Ship-Ahead Input/Output Cabinet NXL user manual

User manual for the device Liebert Ship-Ahead Input/Output Cabinet NXL

Device: Liebert Ship-Ahead Input/Output Cabinet NXL
Category: Power Supply
Manufacturer: Liebert
Size: 0.97 MB
Added : 3/24/2013
Number of pages: 20
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Liebert Ship-Ahead Input/Output Cabinet NXL. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Liebert Ship-Ahead Input/Output Cabinet NXL.

For your convenience

If looking through the Liebert Ship-Ahead Input/Output Cabinet NXL user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Liebert Ship-Ahead Input/Output Cabinet NXL on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Liebert Ship-Ahead Input/Output Cabinet NXL to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Liebert Ship-Ahead Input/Output Cabinet NXL User manual - Online PDF
Advertisement
« Page 1 of 20 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Liebert Ship-Ahead Input/Output Cabinet NXL but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Liebert Ship-Ahead Input/Output Cabinet NXL. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

AC Power
For Business-Critical Continuity™
® ™
Liebert NXL Ship-Ahead Input/Output Cabinet
Installation Manual – 250-400kVA, 60Hz

Summary of the content on the page No. 2

CONTACTING LIEBERT FOR SUPPORT To contact Liebert Services for information or repair service in the United States, call 1-800-LIEBERT (1-800-543-2378). Liebert Services offers a complete range of start-up services, repair services, preventive maintenance plans and service contracts. For repair or maintenance service outside the 48 contiguous United States, contact Liebert Services, if available in your area. For areas not covered by Emerson Network Power Liebert Services, the authorized dist

Summary of the content on the page No. 3

TABLE OF CONTENTS 1.0 MECHANICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1.2 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1.3 Environmental Considerations . . . . . . . . . . . . . . . . . .

Summary of the content on the page No. 4

ii

Summary of the content on the page No. 5

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation of your Lie- ™ bert NXL Input/Output Cabinet. Read this manual thoroughly, paying special attention to the sec- tions that apply to your installation, before working with the UPS. Retain this manual for use by installing personnel. WARNING ! Risk of electrical shock. Can cause personal injury or death. Check for voltage with both AC and DC voltmeters befo

Summary of the content on the page No. 6

Mechanical Installation 1.0 MECHANICAL INSTALLATION 1.1 Introduction This following section describes the requirements that must be taken into account when planning the positioning and cabling of the Liebert NXL Input/Output Cabinet. This chapter is a guide to general procedures and practices that should be observed by the installing personnel. The particular conditions of each site will determine the applicability of such procedures. NOTICE All equipment not referred to in this manual is ship

Summary of the content on the page No. 7

Mechanical Installation 1.4.1 Moving the Cabinets The Liebert NXL Input/Output Cabinet can be handled with a forklift or similar equipment. When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a 15-degree tilt with the forklift. Bottom structure will support the unit only if the forks are completely beneath the unit. Handling the cabinet with straps is not authorized. 1.4.2 Clearances Clearance around the front of the equipment should be sufficient to enabl

Summary of the content on the page No. 8

Electrical Installation 2.0 ELECTRICAL INSTALLATION This chapter provides guidelines for qualified installers who must have knowledge of local wiring practices pertaining to the equipment to be installed. WARNING ! Risk of electrical shock. Can cause injury or death. Check for voltage with both AC and DC voltmeters before working within the cabinet. Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should be involved in installing the

Summary of the content on the page No. 9

Electrical Installation The following are guidelines only and are superseded by local regulations and codes of practice where applicable: • Take special care when determining the size of the neutral cable (grounded conductor), because current circulating on the neutral cable may be greater than nominal current in the case of non- linear loads. Refer to the values in Tables 2 and 3. • The grounding conductor should be sized according to the fault rating, cable lengths, type of pro- tection, etc

Summary of the content on the page No. 10

Electrical Installation Top Cable Entry When making the power connections, the recommended order of pulling and installing cables is to start from the top connections to the bottom connections. The cables must be routed around the fault braces (see Detail in Figure 3). This is to prevent the cables from contacting other busbars. The recommended conduit layout is shown in Figure 1. Bottom Cable Entry When making the power connections, the recommended order of pulling and installing cables is

Summary of the content on the page No. 11

Electrical Installation Table 4 Current ratings—battery UPS Rating Maximum Battery External Breaker kVA kW Nominal VDC Current at EOD Trip, Amps 250 225 480 615 700 300 270 480 737 800 400 360 480 981 1000 Notes on Tables 1. Nominal input current (considered continuous) is based on full-rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current are defined in NEC 100. Maximum input cur

Summary of the content on the page No. 12

Electrical Installation Table 6 Recommended lug sizes T&B Series 54000 T&B Series 54000 Cable Size One Hole Two Hole #8 AWG 54930BE 54850BE #6 AWG 54905BE 256-30695-868 #4 AWG 54906BE 256-30695-733 #2-3 AWG 54942BE 54811BE #1 AWG 54947BE 54857BE #1/0 AWG 54950BE 256-30695-593 #2/0 AWG 54951BE 54862BE #3/0 AWG 54965BE 54864BE #4/0 AWG 54970BE 54866BE 250kcmil 54913BE 54868BE 300kcmil 54914BE 54870BE 350kcmil 54915BE 54872BE 400kcmil 54916BE 54874BE 500kcmil 54918BE 54876BE 600kcmil 54920BE 54878B

Summary of the content on the page No. 13

Installation Drawings 3.0 INSTALLATION DRAWINGS Figure 1 Input/output conduit detail drawing, 250-300kVA Liebert NXL UPS DC OUTPUT (2) 3" CONDUIT (2) 3.5" CONDUIT BYPASS INPUT (2) 3.5" CONDUIT (2) 3" CONDUIT INPUT BYPASS (2) 3" CONDUIT (2) 3.5" CONDUIT OUTPUT DC (2) 3.5" CONDUIT (2) 3" CONDUIT LOW VOLTAGE LOW VOLTAGE 1.5" CONDUIT LOW VOLTAGE 1.5" CONDUIT (14) 1" CONDUIT TOP VIEW BOTTOM VIEW SHOWN IN EXTENDED POSITION 76.8 ( 1950 ) BYPASS NEUTRAL DC POSITIVE GROUND BUS DC NEGATIVE (TOP ENTRY) 59.

Summary of the content on the page No. 14

Installation Drawings Figure 2 Input/output conduit detail drawing, 400kVA Liebert NXL UPS DC OUTPUT (2) 3" CONDUIT (2) 3.5" CONDUIT BYPASS INPUT (2) 3.5" CONDUIT (2) 3" CONDUIT INPUT BYPASS (2) 3" CONDUIT (2) 3.5" CONDUIT OUTPUT DC (2) 3.5" CONDUIT (2) 3" CONDUIT LOW VOLTAGE 1.5" CONDUIT LOW VOLTAGE LOW VOLTAGE (14) 1" CONDUIT 1.5" CONDUIT TOP VIEW BOTTOM VIEW 76.8 (1950) BYPASS NEUTRAL DC POSITIVE DC NEGATIVE GROUND BUS 59.4 LOCATION ( 1509) B 56.4 (TOP ENTRY) (1432) 52.9 SEE NOTE 6 (1343) 49.

Summary of the content on the page No. 15

Installation Drawings Figure 3 Top cable entry routing and installation order OUTPUT CONDUIT INPUT CONDUIT BYPASS CONDUIT DC CONDUIT DC (POSITIVE) DC (POSITIVE) DC (NEGATIVE) DC (NEGATIVE) GROUND (TOP ENTRY) BYPASS NEUTRAL BYPASS NEUTRAL BYPASS INPUT (PHASE C) FAULT BRACE FAULT BRACE BYPASS INPUT BYPASS INPUT BYPASS INPUT RECTIFIER INPUT (PHASE C) FAULT BRACE FAULT BRACE RECTIFIER INPUT RECTIFIER INPUT RECTIFIER INPUT OUTPUT (PHASE C) FAULT BRACE FAULT BRACE OUTPUT OUTPUT OUTPUT GROUND (BOTTOM E

Summary of the content on the page No. 16

Installation Drawings Figure 4 Bottom cable entry routing and installation order DC (POSITIVE) DC (NEGATIVE) DC (POSITIVE) GROUND (TOP ENTRY) DC (NEGATIVE) BYPASS NEUTRAL BYPASS NEUTRAL FAULT BRACE BYPASS INPUT FAULT BRACE BYPASS INPUT (PHASE C) BYPASS INPUT BYPASS INPUT FAULT BRACE RECTIFIER INPUT FAULT BRACE RECTIFIER INPUT (PHASE C) RECTIFIER INPUT RECTIFIER INPUT FAULT BRACE OUTPUT (PHASE C) OUTPUT FAULT BRACE OUTPUT OUTPUT GROUND (BOTTOM ENTRY) OUTPUT NEUTRAL OUTPUT NEUTRAL OUTPUT CONDUIT I

Summary of the content on the page No. 17

Installation Drawings Figure 5 Floor mount brackets—standard and optional layout 20.7 (525mm) 27.4" 27.4" (695mm) (695mm) BOTTOM VIEW (Standard) 7.7" (197mm) 4.7" DETAIL AREA (120mm) FLOOR MOUNTS 36.8" 27.4" (935mm) (695mm) KEEP BRACKETSATTACHED WARNING Brackets MUST remain attached to the frame until the unit is being placed in its final installed position. (The final installation will always require the unit to be bolted BOTTOM VIEW (Optional) to another Liebert NXL product.) Failure to compl

Summary of the content on the page No. 18

Installation Drawings 14

Summary of the content on the page No. 19

Summary of the content on the page No. 20

Ensuring The High Availability 0f Mission-Critical Data And Applications. Technical Support / Service Emerson Network Power, the global leader in enabling business-critical Web Site continuity, ensures network resiliency and adaptability through www.liebert.com a family of technologies—including Liebert power and cooling Monitoring technologies—that protect and support business-critical systems. 800-222-5877 Liebert solutions employ an adaptive architecture that responds monitoring@emersonnetwor


Alternative user manuals
# User manual Category Download
1 Liebert 130 kVA User manual Power Supply 19
2 Liebert 208V User manual Power Supply 13
3 Liebert 1500 User manual Power Supply 27
4 Liebert 30-130kVA User manual Power Supply 8
5 Liebert 115V User manual Power Supply 8
6 Liebert 230V User manual Power Supply 13
7 Liebert 2U User manual Power Supply 11
8 Liebert 2700VA User manual Power Supply 6
9 Liebert 500-650 VA User manual Power Supply 4
10 Liebert 4000 User manual Power Supply 4
11 Liebert 50 and 60 Hz User manual Power Supply 1
12 Liebert 350-700 VA User manual Power Supply 2
13 Liebert 6000 A User manual Power Supply 7
14 Liebert 600TTM User manual Power Supply 2
15 Liebert 700-2200 VA User manual Power Supply 13
16 Sony AC U50A User manual Power Supply 5
17 Sony AC LS1 User manual Power Supply 2
18 Sony NP-FM30 User manual Power Supply 35
19 Sony NP FX101 User manual Power Supply 1
20 Sony NH-AAA-DA User manual Power Supply 2