Liebert 700-3000 VA user manual

User manual for the device Liebert 700-3000 VA

Device: Liebert 700-3000 VA
Category: Power Supply
Manufacturer: Liebert
Size: 0.57 MB
Added : 1/10/2014
Number of pages: 30
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Liebert 700-3000 VA. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Liebert 700-3000 VA.

For your convenience

If looking through the Liebert 700-3000 VA user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Liebert 700-3000 VA on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Liebert 700-3000 VA to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Liebert 700-3000 VA User manual - Online PDF
Advertisement
« Page 1 of 30 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Liebert 700-3000 VA but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Liebert 700-3000 VA. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

R
UPStation GXT™
700-3000 VA
230V
USER MANUAL
English / Deutsch / Français /
Italiano / Español

Summary of the content on the page No. 2

IMPORTANT SAFETY INSTRUCTIONS WARNING: 1. SAVE THESE INSTRUCTIONS. THIS MANUAL CONTAINS IMPORTANT operating the Uninterruptible Power System (UPS). Adhere to all warnings 2. This product is designed for Commercial/Industrial use only. It is not intended for use with life support and other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label. If 3. WHEN REPLACING THE BATTERIES, USE THE APPROPRIATE LIEBERT-APPROVED REPLACEMENT BATTERY KIT. PROPER DISPOSAL

Summary of the content on the page No. 3

9. The UPS output supply sockets may be electrically live whenever the input power lead is plugged into the mains supply socket. Turning the UPS off does not electrically isolate the internal parts. To isolate the UPS, turn the 10. When installing the UPS or making input and output connections, comply 11. This equipment complies with the requirements of the EMC Directive 89/336/EEC and the published technical standards. Continued compliance requires installation in accordance with these instr

Summary of the content on the page No. 4

INTRODUCTION AND SYSTEM DESCRIPTION Congratulations on your choice of the UPStation GXT™ Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other Upon generation, AC power is clean and stable. However, during transmission and distribution it may be subject to voltage sags, spikes, or complete power failure which may interrupt computer operations, cause data loss, or even damage equipment. The UPStation GXT™ protects equipment from these The UPStation GXT™

Summary of the content on the page No. 5

MAJOR COMPONENTS Dynamic Bypass Rectifier/PFC Inverter TVSS OUTPUT INPUT and EMI/RFI Filters DC to DC Converter Battery Battery Charger TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the mains line and keep the sensitive RECTIFIER/POWER FACTOR CORRECTION (PFC) CIRCUIT In normal operation, the rectifier/power factor correction (PFC) circuit converts mains AC power to reg

Summary of the content on the page No. 6

DC TO DC CONVERTER The DC-DC converter utilizes energy from the battery system and raises the DC to operate continuously at its optimum efficiency and voltage, thus increasing BATTERY will last many years. Optional external battery cabinets are available to provide extended run times for the rack-tower (RT) models. For battery run times, refer DYNAMIC BYPASS The UPStation GXT™ provides an alternate path for mains power to the connected load, in the unlikely event of a UPS malfunction. Should t

Summary of the content on the page No. 7

Re-plug the power input cable (A) into mains supply socket. Proceed with step 9.For 3000 VA models, a CEE 19 input cable is supplied. Proceed 6. Connect the molded connector of the mains AC input supply cable into the 7. Fit the supplied retainer bracket around the input supply cable and secure 8. The free end of the input supply cable should be connected to the electrical NOTE: The UPS On/Alarm Silence/Manual Battery Test button does not electrically isolate the internal parts. To isolate the

Summary of the content on the page No. 8

RACK-MOUNT CONVERSION DIAGRAMS RACK-MOUNT UPS CONVERSION AND INSTALLATION 1. Unpack the UPS carefully noting the packing method. Retain the box and 2. CAUTION: 3. Visually inspect the UPS for freight damage. Report damage to the carrier 4. Remove the two screws located at the rear of the top cover with a Phillips (cross head) screwdriver. Push the top cover towards back of UPS and lift 5. Gently lay unit on its right side and remove the six rubber feet with the NOTE: 6. 7. Remove display tem

Summary of the content on the page No. 9

11. Ensure the load equipment is turned off, and plug all loads into the UPS 12. For 700-2000 VA models, unplug power input cable from load equipment input socket and plug it into UPS input socket. Re-plug the power input 13. Connect the molded connector of the mains AC input supply cable into the 14. Fit the supplied retainer bracket around the input supply cable and secure 15. The free end of the input supply cable should be connected to the electrical supply distribution system in accordance

Summary of the content on the page No. 10

OPTIONAL BATTERY CABINET(S) INSTALLATION Up to two optional battery cabinets may be connected to the UPS to provide additional run time. Battery cabinets are designed to be placed on either side or 1. Unpack the UPS battery cabinet(s) carefully noting the packing method. 2. CAUTION: The battery cabinet(s) are heavy (see specifications). Take 3. Visually inspect the UPS for freight damage. Report damage to the carrier 4. Follow the same installation instructions used earlier for the UPS (towe

Summary of the content on the page No. 11

FERRITE BEAD INSTALLATION Serial Communications Attach the smaller enclosed ferrite bead clamp to the communication cable as shown in the drawing using the following • • Place the communication cable inside • Position the ferrite beads as close as possible to the end of the cable that connects to the DB9 connector of the • Close the ferrite bead so that the ferrite bead’s case snaps closed with the cable routed inside the ferrite SNMP Installation Attach the larger enclosed ferrite bead clamp t

Summary of the content on the page No. 12

UPSTATION GXT™ Fault Indicator On/Alarm Silence/ Bypass Indicator Manual Battery Test Button UPS On Indicator Battery Indicator Off/ Bypass Button AC Input Indicator Load/Battery Level Indicators 1- Output Receptacles 2- DB-9 Interface Port 3- AC Inlet 4- Intellislot TM Communications Port 5- Circuit Protector or fuse 6- Output Voltage Selector 624624624 Switches 7- Battery Cable Connector 5 3 3 6 4 2 5 3 5 7 7 3 5 1 7 1 3 700/1000 VA 1000/1500 VA 3000 VA 2000 VA Mini-Tower Rack Tower Ra

Summary of the content on the page No. 13

CONTROLS AND INDICATORS On/Alarm Silence/Manual Battery Test Button This button controls output power to connected load(s) and has three functions: On, Alarm Silence, and Manual Battery Test. Pressing this button will start up the UPS in order to provide conditioned and protected power into the mains To silence alarms, press this button for at least one half second while alarm conditions are present. After the alarm is silenced, the UPStation GXT™ will NOTE: To initiate a manual battery test,

Summary of the content on the page No. 14

UPS On Indicator (Green) The UPS On indicator is illuminated when the UPS inverter is operating and Battery Indicator (Amber)The Battery indicator is illuminated when the UPS is AC Input Indicator (Green) The AC Input indicator is illuminated when mains power is available and within Output Voltage Selector Switches The Output Voltage Selector Switches, located on the rear of the UPS, are designed to allow selecting or changing the desired output voltage to match the NOTE: Never change the switc

Summary of the content on the page No. 15

BATTERY MODE OPERATION Battery mode occurs in event of an extreme input voltage condition or complete mains failure. The battery system supplies power through the DC-DC converter During battery mode an alarm sounds every 10 seconds. This will change to 2 beeps every 5 seconds when battery runs low (approximately 2 minutes to warn that a mains problem has occurred. Each load/battery level indicator NOTE: CAUTION: Turning off the UPS while in battery mode will result in loss of output BATTERY R

Summary of the content on the page No. 16

COMMUNICATIONS INTERFACE PORT The UPStation GXT™ UPS contains a standard DB-9 female connector located on the rear of the UPS unit. Several signals are provided on this port and are 1 2 3 4 5 6 7 8 9 PIN ASSIGNMENT COLLECTOR TO EMITER* *Maximum voltage and current on pins 1,7,8,9 is 80V DC; 10.0 UPS MONITORING The UPStation GXT™ UPS has the capability of being monitored with stand alone computers, network workstations, network servers, or UNIX hosts via the This capability is used in applicati

Summary of the content on the page No. 17

UPS INTELLIGENT COMMUNICATIONS The UPStation GXT™ UPS has the capability to communicate intelligently with the DB-9 female connector located at the rear of the UPS. By purchasing the optional Liebert SiteNet® 2 software package (sold separately), intelligent - - - - - Consult your local Liebert sales representative for more information about UPS INTELLISLOT™ COMMUNICATIONS The UPStation GXT™ UPS contains an Intellislot™ communications port for the optional internal Ethernet SNMP card. Opt

Summary of the content on the page No. 18

BATTERY REPLACEMENT PROCEDURES CAUTION – current. The following precautions should be observed before replacing the - Turn off and disconnect the UPS from the mains power prior to opening the - - - - If the battery replacement kit is damaged in any way or shows signs of - - If you feel unqualified to replace the batteries, do not open the battery door. Call Liebert Technical Support (LTS). World Wide Technical Support MINI-TOWER BATTERY REPLACEMENT B atter y d o or scr ews Battery connect

Summary of the content on the page No. 19

8. Carefully stand the UPS upright. Connect the UPS to the mains supply 9. FOR 1000 TO 3000 VA RACK/TOWER MODELS: CAUTION: TOWER MODELS ONLY: - Remove top cover by removing the two screws located on rear of top cover. Push the top cover towards the back of UPS and lift off. Remove the two - Gently lay the UPS on its right side and remove the two front rubber feet. RACK/TOWER MODELS: 1. NOTE: The two securing flanges must be removed before front bezel 2. Remove the two screws from the small

Summary of the content on the page No. 20

RACK / TOWER BATTERY REPLACEMENT Top cover screws Flange screws Rear View Aerial View w/top cover removed Two front Front bezel (cover) rubber feet Small battery door Large battery door Screw hidden by small battery door Battery connector Large battery door 20


Alternative user manuals
# User manual Category Download
1 Liebert 130 kVA User manual Power Supply 19
2 Liebert 208V User manual Power Supply 13
3 Liebert 1500 User manual Power Supply 27
4 Liebert 30-130kVA User manual Power Supply 8
5 Liebert 115V User manual Power Supply 8
6 Liebert 230V User manual Power Supply 13
7 Liebert 2U User manual Power Supply 11
8 Liebert 2700VA User manual Power Supply 6
9 Liebert 500-650 VA User manual Power Supply 4
10 Liebert 4000 User manual Power Supply 4
11 Liebert 50 and 60 Hz User manual Power Supply 1
12 Liebert 350-700 VA User manual Power Supply 2
13 Liebert 6000 A User manual Power Supply 7
14 Liebert 600TTM User manual Power Supply 2
15 Liebert 700-2200 VA User manual Power Supply 13
16 Sony AC U50A User manual Power Supply 5
17 Sony AC LS1 User manual Power Supply 2
18 Sony NP-FM30 User manual Power Supply 35
19 Sony NP FX101 User manual Power Supply 1
20 Sony NH-AAA-DA User manual Power Supply 2