Liebert 30-130kVA user manual

User manual for the device Liebert 30-130kVA

Device: Liebert 30-130kVA
Category: Power Supply
Manufacturer: Liebert
Size: 1.58 MB
Added : 1/10/2014
Number of pages: 112
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Liebert 30-130kVA. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Liebert 30-130kVA.

For your convenience

If looking through the Liebert 30-130kVA user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Liebert 30-130kVA on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Liebert 30-130kVA to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Liebert 30-130kVA User manual - Online PDF
Advertisement
« Page 1 of 112 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Liebert 30-130kVA but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Liebert 30-130kVA. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

AC Power
For Business-Critical Continuity

Npower UPS
Operation & Maintenance Manual–30-130kVA, 60Hz, Single Module System

Summary of the content on the page No. 2

Summary of the content on the page No. 3

TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 OVERVIEW OF MANUAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 1.1 System Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Summary of the content on the page No. 4

3.4 Faults, Alarms, Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 3.4.1 Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 3.4.2 Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 3.4.3 Status . . . . . . . . . . . . . . . . . . . .

Summary of the content on the page No. 5

FIGURES Figure 1 UPS controls and display screen (with example of the monitor/mimic screen). . . . . . . . . . . . . . . . 6 Figure 2 80 kVA UPS outside and inside views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Figure 3 Operator control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Figure 4 Navigation buttons . . . . . . . . . . . . . . . . . . . . . . . . . .

Summary of the content on the page No. 6

Figure 50 Options screen, page 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Figure 51 10% passive filter settings screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Figure 52 Options screen, page 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Figure 53 Options screen, page 3 . . . . . .

Summary of the content on the page No. 7

Figure 100 Summary page screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Figure 101 User settings, page 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Figure 102 Battery time low warning screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Figure 103 Auto restart setting screen . .

Summary of the content on the page No. 8

vi

Summary of the content on the page No. 9

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual contains important instructions that should be followed during maintenance of your Npower UPS and batteries. WARNING ! Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel. Refer to separate installation manual for equipment handling information and installation procedures. Follow all battery safety precautions in 4.0 - Maintenance when installing, charging, or servicing batteries.

Summary of the content on the page No. 10

OVERVIEW OF MANUAL The Npower manual is organized so that information can be found quickly. Each major topic is sepa- rated by sections, and there is a Table of Contents for each section. The names of the sections and their contents are described below. Section 1 - INTRODUCTION is a summary of the Npower Uninterruptible Power System (UPS). It describes some of the unique features and benefits of the Npower UPS, as well as the design princi- ples and standards that Liebert follows in the manuf

Summary of the content on the page No. 11

Introduction 1.0 INTRODUCTION 1.1 System Description The role of the UPS system is to supply uninterruptible, clean power to the critical load. It maintains a full-voltage, low-distortion output, even if the utility source power sags or becomes distorted. If there is an outage of the source power, the UPS maintains power to the load until an alternate source of power is activated, or until the original power source is restored. If input AC power is not restored, the UPS maintains the load (wi

Summary of the content on the page No. 12

Introduction 1.1.1 Reliability Reliability is the most important design goal for Uninterruptible Power Systems. All Liebert 3-Phase UPS systems have demonstrated reliability by achieving a field-proven critical bus MTBF in excess of one million hours. In addition, our Quality Assurance program is certified to the requirements of ISO 9001 standards. Liebert UPS systems are ETL listed to the requirements of UL 1778, CSA Certified and (when appli- cable) CE marked. All equipment and components

Summary of the content on the page No. 13

Introduction ONLY qualified service personnel should perform maintenance on the UPS system. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats. The service personnel should wear insulating shoes for isolation from direct contact with the floor (earth ground). Unless all power is removed from the equipment, one person should never work alone. A second per- son should be standing by to assist and summon

Summary of the content on the page No. 14

Introduction 1.3.4 Overload Overloads in critical systems may be caused by inrush currents during connected equipment startup or by faults in the critical load or distribution network. The Liebert Npower UPS system can maintain full output voltage regulation while sustaining the following overloads: • Up to 125% for 10 minutes • Up to 150% for 1 minute • Up to 200% for 10 cycles For momentary faults above 200% of rated current, the static switch turns on for 10 cycles to supply power from the

Summary of the content on the page No. 15

Introduction 1.4 Operator Controls Liebert Npower UPS modules are equipped with a microprocessor-based Operator Display Screen and Control Panel designed for convenient and reliable operation. The front panel location of the monitor- ing and control system enables the Operator to quickly identify the current status of the UPS and to perform most of the manual operations. The operator display screen is driven by an easy-to-follow menu-prompted software program that con- trols and monitors the

Summary of the content on the page No. 16

Theory of Operation 2.0 THEORY OF OPERATION 2.1 General Component Description The UPS system includes all of the equipment necessary to continuously provide computer- grade AC power to a critical load, even when there is an interruption of the utility line power. It consists of the UPS modules and a back-up battery plant. Refer to Figure 2. 2.1.1 UPS Module The UPS module consists of system controls, a rectifier/charger, an inverter, protective devices, and other accessories. System Controls:

Summary of the content on the page No. 17

Theory of Operation 2.2 Detailed Component Descriptions 2.2.1 Controls Hardware The Npower UPS operator interface display system is designed to provide all of the information that is required for the operation of each UPS module. The following is a list of the hardware features: 1. The control logic performs automatic operations with minimal operator interface. The limited number of manual controls are easy-to-use. 2. Each Npower UPS cabinet is equipped with an easy-to-read liquid crystal disp

Summary of the content on the page No. 18

Theory of Operation 2.2.2 Rectifier/Charger The UPS module rectifier/charger consists of input fuses, AC current-limiting circuit, battery equalize charge circuit, DC filter, battery charge-current-limiting circuit, and bridge rectifiers. Operation The rectifier/charger converts the AC input power to DC power. This conversion is accomplished by 3- phase bridge rectifiers using SCRs. All phases are individually fused. For all modules, reflected input current THD is less than 30% at full load (w

Summary of the content on the page No. 19

Theory of Operation Operation After End-of-discharge The battery time screen displayed on the control panel enables you to estimate when battery shut- down will occur. You will have enough time to energize an alternate AC power source or to initiate an orderly shutdown of the critical load. If the battery plant discharges to the shutdown point during an outage, the UPS automatically disconnects the load, the AC input, and the battery. After AC input power is restored, the rectifier can be man

Summary of the content on the page No. 20

Theory of Operation Nonlinear Load Characteristics Computers and computer equipment with switching power supplies generate nonlinear currents rich in fifth and seventh harmonics. The inverter pulse-width-modulated waveform, coupled with the output filter, provides a natural path for reducing the fifth and seventh harmonic currents produced by the load. The inverter/filter limits the output voltage THD to less than 3% with up to 100% typical electronic data processing (EDP) loads. EDP equipme


Alternative user manuals
# User manual Category Download
1 Liebert 130 kVA User manual Power Supply 19
2 Liebert 208V User manual Power Supply 13
3 Liebert 1500 User manual Power Supply 27
4 Liebert 115V User manual Power Supply 8
5 Liebert 230V User manual Power Supply 13
6 Liebert 2U User manual Power Supply 11
7 Liebert 2700VA User manual Power Supply 6
8 Liebert 500-650 VA User manual Power Supply 4
9 Liebert 4000 User manual Power Supply 4
10 Liebert 50 and 60 Hz User manual Power Supply 1
11 Liebert 350-700 VA User manual Power Supply 2
12 Liebert 6000 A User manual Power Supply 7
13 Liebert 600TTM User manual Power Supply 2
14 Liebert 700-2200 VA User manual Power Supply 13
15 Liebert GXT2 - 3X1 User manual Power Supply 27
16 Sony AC U50A User manual Power Supply 5
17 Sony AC LS1 User manual Power Supply 2
18 Sony NP-FM30 User manual Power Supply 35
19 Sony NP FX101 User manual Power Supply 1
20 Sony NH-AAA-DA User manual Power Supply 2