APC Symmetra LX SYBATT user manual

User manual for the device APC Symmetra LX SYBATT

Device: APC Symmetra LX SYBATT
Category: Power Supply
Manufacturer: APC
Size: 1.28 MB
Added : 9/12/2013
Number of pages: 25
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for APC Symmetra LX SYBATT. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with APC Symmetra LX SYBATT.

For your convenience

If looking through the APC Symmetra LX SYBATT user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual APC Symmetra LX SYBATT on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual APC Symmetra LX SYBATT to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
APC Symmetra LX SYBATT User manual - Online PDF
Advertisement
« Page 1 of 25 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual APC Symmetra LX SYBATT but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to APC Symmetra LX SYBATT. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

®
Symmetra LX
Operations Guide
For use with Symmetra LX UPS Models:
200 V, 4–8 kVA 200 V, 4–16 kVA
208/240 V, 4–8 kVA 208/240 V, 4–16 kVA
220/230/240 V, 4–8 kVA 220/230/240 V, 4–16 kVA
Symmetra LX
Rack-mount UPS
Symmetra LX
Rack-mount
Extended Run
Symmetra LX
Tower UPS
Symmetra LX
Tower
Extended Run
990-1546A-001 06/2005

Summary of the content on the page No. 2

Summary of the content on the page No. 3

TABLE OF CONTENTS Chapter 1: Overview ...................................................................................................................1 PowerView .............................................................................................................................................................1 Keys and Indicators................................................................................................................................................1 Navig

Summary of the content on the page No. 4

Summary of the content on the page No. 5

CHAPTER 1: OVERVIEW Overview ® This manual provides an overview of operations for the Symmetra LX and Extended Run Cabinet, including detailed explanations of monitoring, control, and configuration through the PowerView user interface. Illustrations are representative. Your unit and configuration, including components and optional APC equipment, may vary from those depicted in this document. Manuals may be accessed through the APC Web site, www.apc.com. PowerView PowerView contains an al

Summary of the content on the page No. 6

CHAPTER 1: OVERVIEW Navigation Keys Name Sound Function ? Help Short beep Opens context-sensitive help. Enter Short beep Opens the selected menu item or setting. ESC + ? + Escape + Help Two short When pressed simultaneously for about one second, + Enter beeps resets the PowerView RM interface. One long beep When pressed simultaneously for about three seconds, puts the interface in programming mode for installing new language program files. Navigation The normal display on the Powe

Summary of the content on the page No. 7

CHAPTER 2: BASIC COMMANDS Basic Commands Supply Power to the UPS This procedure supplies power to the Symmetra LX and does not supply power to the equipment connected to the UPS. 1. Turn ON the AC utility power to the UPS 2. Switch ON the circuit breakers for all connected equipment. a. If connected equipment is hardwired, check that the output circuit breakers in the distribution panel are turned ON. b. If connected equipment is plugged into the UPS ! , check that each UPS PDU output

Summary of the content on the page No. 8

CHAPTER 2: BASIC COMMANDS Set the Correct Output Voltage 1. Press the ‘Esc’ button until the Main Menu appears. Use the up and down arrow keys to choose ‘Setup’, and ENTER to select. Control Logging Status Display >Setup Diags Accessories Help 2. Use the arrow keys and ENTER to select ‘Other’. Settings: Alarms Shutdown Bypass Defaults Copy Output Freq >Other 3. If the output voltage is not correct for your application, use the arrow keys,

Summary of the content on the page No. 9

CHAPTER 2: BASIC COMMANDS 5. In approximately 90 seconds, the green Load On indicator will illuminate and this message will appear. UPS LOAD IS ON Press any key… Turn Off UPS Output Power and Load Equipment 1. Press ‘Esc’ until the Main Menu appears. >Control Logging Status Display Setup Diags Accessories Help 2. Scroll down and select the ‘Turn UPS Output Off’ command. Graceful Turn Off Start Runtime Cal >Turn UPS Output Off 3. Confirm choice by selec

Summary of the content on the page No. 10

CHAPTER 2: BASIC COMMANDS Command Bypass Command Bypass requires utilization of the commands on the PowerView display. This mode is used to bypass the UPS electronics and directly supply power to the load. Follow the steps below to directly connect the output power of the UPS to the branch circuit (mains) using the command bypass mode. 1. Use ‘Esc’ to view the Main Menu, and select ‘Control’. >Control Logging Status Display Setup Diags Accessories Help

Summary of the content on the page No. 11

CHAPTER 2: BASIC COMMANDS Language Setting The factory default language of the user interface is English. You can change the language by downloading new firmware into the PowerView. French, German, Italian, and Spanish are available on the enclosed CD. Visit the APC web site at http://www.apc.com for multilingual product documentation and firmware language support. Illustrations are representative. Your configuration may be different from the models shown in this procedure. To change the

Summary of the content on the page No. 12

CHAPTER 2: BASIC COMMANDS Language Setting (continued) 6. Locate the language program file to be downloaded into the UPS. See the APC website at http://www.apc.com/support and download the desired language. 7. Place the PowerView in programming mode simultaneously pressing the three keys on the right (‘Esc’, ‘Help’, and ‘ENTER’) for approximately three seconds, until the PowerView emits a long beep. • The LCD will display the Programming screen. • To leave the Programming screen before

Summary of the content on the page No. 13

CHAPTER 3: MENU COMMANDS Menu Commands The following sections describe the details of each command. Commands are organized according to the menu hierarchy in the PowerView. Accessories Menu The Accessories Menu allows you to monitor APC accessories if they are installed. The PowerView must be connected to the computer interface port at the back of the UPS frame in order to monitor internal accessories. Control Menu Use the Control Menu and its submenus to control power flows to and from

Summary of the content on the page No. 14

CHAPTER 3: MENU COMMANDS Display Menu The Display Menu allows the user to customize the PowerView display. Display Function Options Date/Time Sets the correct date and time. Date: dd-mmm-yyyy Ex:11-Aug-2003 Time: hh:mm:ss Ex: 21:36:10 Protects against unauthorized Password configuration changes. Valid characters include: A–Z, or 0–9 Password Sets a password. Type ‘_’ to complete. 1, 2, 5, 10 (default); 30 minutes; Timeout Sets the inactivity timer. 1, 2, or 4 Hours

Summary of the content on the page No. 15

CHAPTER 3: MENU COMMANDS Diagnostics Menu The Diagnostics Menu provides useful information for troubleshooting. Menu Item Function Fault and Diagnostics Displays current system fault and diagnostic information of that fault. (Main) Intelligence Module Displays detailed intelligence module status and information. Redundant Intelligence Displays detailed redundant intelligence module status and information. Module Power Modules Displays detailed power module status and information. Ba

Summary of the content on the page No. 16

CHAPTER 3: MENU COMMANDS Logging Menu (continued) Menu Item Function List Event Groups Lists the specific events in each group. Power Events UPS Control Events User Activities UPS Fault Events Measure UPS Events Clear Log Clears the view log. Does not clear the active event lists. Status Menu The Status Menu displays load, battery/power module, voltage, and electrical current information. Menu Item Function Ø Vin Vout Iout Displays input voltage(s), output voltage(s), a

Summary of the content on the page No. 17

CHAPTER 3: MENU COMMANDS Setup Menu The Setup Menu allows the user to customize the UPS functionality. Menu Item Function Options Sets the shutdown parameters in the event of a None Shutdown utility power failure. Low Batt(ery) Sets the number of minutes an audible alarm 2 (default), 5, 7, 10, 12, 15, Dur(ation) sounds before the UPS shuts down due to battery 18, or 20 minutes exhaustion. Shutdown Delay Sets the additional runtime for computer issuing 0, 20 (default), 60, 120, 240,

Summary of the content on the page No. 18

CHAPTER 3: MENU COMMANDS Setup Menu (continued) Menu Item Function Options Alarms Sets the alarm thresholds. None Redundancy An audible alarm sounds if the redundancy falls 0 (default), 1, or 2 below this level. Load An audible alarm sounds when the load exceeds Never (default), 1, 2, 3, 4, 5, this limit. (Upper value is limited by the maximum 6, 7, 8, 9, 10, or 12 kVA power of the UPS.) Runtime An audible alarm sounds if the available runtime 0:0 (default),5m, 10m, 15m, falls be

Summary of the content on the page No. 19

CHAPTER 4: TROUBLESHOOTING Troubleshooting The PowerView reports various messages on the display, including alarm status and changes in system configuration. This section lists all the PowerView display messages, the reason for the message, and the appropriate corrective action. Contact APC Technical Support Staff for assistance with complex UPS problems. Refer to the APC Web site at http://www.apc.com for a location near you. Messages may occur simultaneously. If this happens, be sure t

Summary of the content on the page No. 20

CHAPTER 4: TROUBLESHOOTING Condition PowerView Message Reason Corrective Action Start-Up AC adequate for UPS but The UPS will function on-line with Option 1: Improve the (continued) not for bypass. the input voltage. But, in the event incoming voltage. that bypass is required, the input Option 2: Proceed with start- voltage is not adequate to power up. Normal bypass is not the load equipment. available. Low/No AC input, start-up Input voltage is not adequate to Option 1: Abort start-u


Alternative user manuals
# User manual Category Download
1 APC 208 Vac User manual Power Supply 8
2 APC 1400XLT User manual Power Supply 23
3 APC 15A User manual Power Supply 0
4 APC 120V User manual Power Supply 5
5 APC 2200XLT User manual Power Supply 24
6 APC 2000XL User manual Power Supply 15
7 APC 1000VA User manual Power Supply 24
8 APC 1500 VA User manual Power Supply 46
9 APC 300 User manual Power Supply 404
10 APC 5000VA User manual Power Supply 60
11 APC 500 User manual Power Supply 26
12 APC 3000VA User manual Power Supply 12
13 APC 3000T User manual Power Supply 1
14 APC 600 User manual Power Supply 64
15 APC 2AP9604S User manual Power Supply 1
16 Sony AC U50A User manual Power Supply 5
17 Sony AC LS1 User manual Power Supply 2
18 Sony NP-FM30 User manual Power Supply 35
19 Sony NP FX101 User manual Power Supply 1
20 Sony NH-AAA-DA User manual Power Supply 2