APC SILCON 990-4053 user manual

User manual for the device APC SILCON 990-4053

Device: APC SILCON 990-4053
Category: Power Supply
Manufacturer: APC
Size: 5.56 MB
Added : 7/6/2013
Number of pages: 76
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for APC SILCON 990-4053. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with APC SILCON 990-4053.

For your convenience

If looking through the APC SILCON 990-4053 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual APC SILCON 990-4053 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual APC SILCON 990-4053 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
APC SILCON 990-4053 User manual - Online PDF
Advertisement
« Page 1 of 76 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual APC SILCON 990-4053 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to APC SILCON 990-4053. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1



APC Silcon
480kW 400V UPS
Installation Guide

Copyright 2000 APC Denmark ApS
This manual is subject to change without
notice and does not represent a commitment
on the part of the vendor

Summary of the content on the page No. 2

Thank You! Thank you for chosing the APC Silcon Series UPS. Please read this Installation Guide thoroughly prior to installing the system. It provides important information on safe and efficient installation. The installation and use of this product must comply with national, federal, state, municipal and local codes. Safety Symbols used in this manual WARNING! Indicates a hazard which, if not avoided, could result in injury or death. CAUTION! Indicates a hazard which, if n

Summary of the content on the page No. 3

Contents 1.0Introduction 5 1.1 Tools and Equipment 5 2.0Unpacking 6 3.0Installation 7 3.1 Requirements on Site 7 3.1.1 Cabinet Dimensions 7 3.2 Footprint 8 3.2.1 1900mm Cabinet for 480kW UPS 8 3.2.2 1600mm Cabinet for 480kW Isolation Transformer 8 4.0 External Connection 9 4.1 Connecting the UPS 9 4.2 System Integration Interface 11 4.2.1 Connections 12 4.3 Parallel Board 13 4.4 Relay Board 16 4.4.1 Relay Board/Relay Functions 17 4.5 Communication Interface Board 19 4.5.1 Connect

Summary of the content on the page No. 4

6.4.1 Extension of Remote Display Communication Distance 57 6.4.2 Remote Display Installation 59 6.4.3 Remote Display Use 60 6.5 Isolation Transformer 61 6.5.1 Connecting Isolation Transformer 62 6.5.2 Wiring up UPS with External Yyn0 Isolation Transformer at Output 64 6.5.3 Wiring up UPS with External Yyn0 Isolation Transformer at Input 65 6.5.4 Wiring up UPS with External Optional Dzn0 Isolation Transformer at Input 66 6.5.5 Wiring up UPS with External Optional Dzn0 Isolation Transf

Summary of the content on the page No. 5

Introduction 1.0 Introduction Power regulation varies from country to country, and information given in this installation guide can therefore only be of a general nature. Electricians should therefore always refer to national and local electrical codes prior to installing the UPS system. 1.1 Tools and Equipment CAUTION! Heavy equipment. To prevent personal injury or equipment damage,

Summary of the content on the page No. 6

Unpacking 2.0 Unpacking NOTICE! Unless otherwise specified by the shipping company use a fork lift to unload equipment from pallet 1. To unpack UPS unit, remove top and bottom screws from side plates of packaging and lift up side plates 2. Verify compliance between type label on reverse side of front door and system ordered. Check input and output voltage 3. Copy type label data to label copy below for easy identification of system 4. Use fork lift to transport system to installat

Summary of the content on the page No. 7

Installation 3.0 Installation 3.1 Requirements on Site All system parts are accessible from front or top of UPS. Cable entries are accessible from bottom. A 1m free space on all sides should be allowed during installation. Once the system is installed it may be placed close to walls as long as free space is allowed for system doors to open. (Per applicable national and/or local codes.) For ventilation and service purposes allow for free space of minimum 1m above the unit or per n

Summary of the content on the page No. 8

Installation 3.2 Footprint 3.2.1 1900mm Cabinet for 480kW UPS Rear Com. cable entry Front 3.2.2 1600mm Cabinet for 480kW Isolation Transformer Rear Power cable entry Front 990-4053 8 Installation Guide APC Silcon 480kW 400V UPS Power cable entry

Summary of the content on the page No. 9

External Connection 4.0 External Connection 4.1 Connecting the UPS Right side view Relay board Please refer to “Relay Board” section Battery Front view System Integration Interface Communication Interface Parallel Controller NOTICE! Check correct phase rotation of mains input voltage!! 2 Max. input/output cables: 3//300 mm . If there is no neutral input Dzn0 or Dyn11 input isolation transformer is required. CAUTION! This UPS unit is an EN 50091-2 product and may cause radio interfere

Summary of the content on the page No. 10

External Connection CAUTION! At a switch mode load of 100% the neutral must be rated for 200% output phase current. UPS External External External PE Maximum External Input Input Cable Cable External Output Cable Fuses* FM [mm2] [mm2] Output [mm2] [A] 380-415V Fuses* 380-415V [A] 480kW 1000 3//185 185 800 3//150 * DIN gL types NOTICE! All cable dimensions are recommended sizes only. Refer to local legal regulations. UPS External Alarm External System External Battery External

Summary of the content on the page No. 11

External Connection 4.2 System Integration Interface NOTICE! Consistent use of designations (Q001, Q002, Q003, H002, H003) in diagrams simplifies information exchange. System Integration Interface (SII) is the control link between UPS and system main switches as shown in above diagram. The purpose of the SII is to ensure correct operation of switches without losing system output power. Auxiliary contacts on the main switches transmit the SII board inputs. Lamps on Service Bypass Pane

Summary of the content on the page No. 12

External Connection 4.2.1 Connections Blue Brown 990-4053 12 Installation Guide APC Silcon 480kW 400V UPS

Summary of the content on the page No. 13

External Connection Terminal Blocks: X003/X004 (Anxiliary Contacts) When switching Q001, Q002, Q010, Battery Breaker 1 or Battery Breaker 2 from “ON or 1” to “OFF or 0”, the anxiliary contact has to be open BEFORE the corresponding main contacts are opened. When switching Q001, Q002, Q010, Battery Breaker 1 or Battery Breaker 2 the opposite way from “OFF or 0” to “ON or 1”, the anxiliary contact has to close with a maximum delay of 0.5 seconds from the time the corresponding main

Summary of the content on the page No. 14

External Connection The built-in parallel board connects two or more UPS systems in parallel, either to obtain increased system reliability or to obtain higher output power. The parallel board also ensures correct load-sharing between paralled systems. NOTICE! For reliability reasons, APC recommends separate battery packs in redundant/parallel conigurations. To prepare the UPS for parallel/redundant mode, disconnect all sources of AC and DC power supply to the UPS and connect the ri

Summary of the content on the page No. 15

External Connection Parallel Board X021:15-pin SUB-D female X020:15-pin SUB-D female External multicore cable with 14 wires + shield to other parallel units UPS 2 UPS 1 UPS 3 External Control Cables External multicore cable is equipped with 15-pin SUB-D plug at either end. Connect pin 1 to pin 1, and pin 2 to pin 2 etc. up to pin 15 - with the exception of pin 8, which is not to be connected. Shield is connected to plug cover at both ends. Terminals X020 and X021 for control cables l

Summary of the content on the page No. 16

External Connection 4.4 Relay Board 1 Maximum load: 8.0A – 250VAC 2 0.3A – 60VDC 3 Minimum load: 0.05A – 6VAC 0.05A – 6VDC Relays All relays are “fail safe”: In alarm modes, relay coil will be de-energized. 990-4053 16 Installation Guide APC Silcon 480kW 400V UPS

Summary of the content on the page No. 17

External Connection 4.4.1 Relay Board/Relay Functions NOTICE If alarm mode “Communication to controller lost” is active, ALL relays will indicate failure Relay Message Alarm-trigging Events Number 1 ## (X002) Mains outside limits Mains voltage RMS outside limits Mains wave form (fast detector) outside limits Mains frequency outside limits 2 ## (X003) Bypass outside limits Bypass voltage RMS outside limits Bypass wave form (fast detector) outside limits Bypass frequency outside limits 3

Summary of the content on the page No. 18

External Connection ## Delay programmable in configuration stack : “Common fault delay”. Settings 0,10,20,30 seconds. See section 5.2: System configuration NOTICE! Alarm Trigging Events 1-2-3-9-10-11-13 activates the corresponding alarm relay after the delay. Alarm Trigging Events 4-5-6-7-8-12-14-15 activates the corresponding alarm relay momentarily. Common fault relay 16 is activated at the

Summary of the content on the page No. 19

External Connection 4.5 Communication Interface Board The 3-port ComInterface is used to establish an interaction between UPS and e.g. a computer system. Main purpose: To ensure a controlled computer shut-down in case of a mains supply failure. 4.5.1 Connections . . 990-4053 Installation Guide APC Silcon 480kW 400V UPS 19

Summary of the content on the page No. 20

External Connection 4.6 Connecting of APC Silcon Tripel Chassis The enclosed Triple Chassis must be connected to the serial port on the Communication Interface Board, and to the 24V supply (cables included). Terminal locations shown below. 480 Serial ports X50 X50 is a 24V supply for Triple Chassis. Front view of UPS Cabinet (doors open) Only to be used for this purpose. Not suitable for telephone equipment. Triple Chassis must be connected to both X50 and a serial port. APC Silc


Alternative user manuals
# User manual Category Download
1 APC 208 Vac User manual Power Supply 8
2 APC 1400XLT User manual Power Supply 23
3 APC 15A User manual Power Supply 0
4 APC 120V User manual Power Supply 5
5 APC 2200XLT User manual Power Supply 24
6 APC 2000XL User manual Power Supply 15
7 APC 1000VA User manual Power Supply 24
8 APC 1500 VA User manual Power Supply 46
9 APC 300 User manual Power Supply 404
10 APC 5000VA User manual Power Supply 60
11 APC 500 User manual Power Supply 26
12 APC 3000VA User manual Power Supply 12
13 APC 3000T User manual Power Supply 1
14 APC 600 User manual Power Supply 64
15 APC 2AP9604S User manual Power Supply 1
16 Sony AC U50A User manual Power Supply 5
17 Sony AC LS1 User manual Power Supply 2
18 Sony NP-FM30 User manual Power Supply 35
19 Sony NP FX101 User manual Power Supply 1
20 Sony NH-AAA-DA User manual Power Supply 2