CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
APC Smart-UPS RT
BID SPECIFICATIONS FOR
3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC
Uninterruptible Power Supply
PART 1 - GENERAL
1.1 SUMMARY
A. This specification describes the operation and functionality of a continuous duty, single-
phase, solid-state, static Uninterruptible Power System (UPS) hereafter referred to as
the UPS.
B. The UPS utilizes double conversion online topology designed to protect electronic
equipment by sup
Summary of the content on the page No. 2
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM H. Configuration Specifics: The UPS is available in one of the following configurations: MODEL SKU # TOWER APC Smart-UPS RT 3000VA RM 230V SURT3000XLI APC Smart-UPS RT 5000VA RM 230V SURT5000XLI APC Smart-UPS RT 6000VA RM 230V SURT6000XLI RACK MOUNT APC Smart-UPS RT 3000VA RM 230V SURT3000RMXLI APC Smart-UPS RT 5000VA RM 230V SURT5000RMXLI APC Smart-UPS RT 6000VA RM 230V SURT6000RMXLI 1.2 STANDARDS A. EN50091-1 B. EN50091-2 C.
Summary of the content on the page No. 3
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM A. Online: The input PFC power stage and the output power stage (inverter) shall operate in an on-line manner to continuously regulate power to the critical load. The input PFC stage shall be capable of full battery recharge while simultaneously providing regulated power to the load for all line and load conditions within the range of the UPS specifications. B. On Battery: Upon failure of the AC input source, the critical load shall continue
Summary of the content on the page No. 4
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 2.1 MECHANICAL DESIGN A. The UPS is contained in a rugged steel cabinet with two plastic front bezels; B. The UPS dimensions are 13 x 43 x 66cm (5.1 x 17 x 26 in.); C. The UPS cabinet is capable of conversion between Tower and Rack-Mount configurations; 2.2 SYSTEM CHARACTERISTICS A. System Capacity: 1. The system is rated to be capable of supporting: a. 3000VA or 2100W whichever limit is reached first (for the 3000VA model). b. 5000VA o
Summary of the content on the page No. 5
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 3. Output frequency: 50/60 +/- 3Hz tracking or 50/60 +/- 0.1Hz tracking (user selectable); 4. AC output voltage distortion: Max. 2% @ 100% linear load; Max. 5% @ 100% non-linear Load; 5. AC output static voltage regulation: +/-1%; 6. AC output dynamic voltage regulation: +/- 8% maximum for 100% load step at less than 10ms recovery time; 7. Overload Rating: a. Online: 105% - infinite; 125% - 1 minute; 150% - 30 seconds; b. I
Summary of the content on the page No. 6
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM C. Input Current Limit: 1. The input converter shall control and limit the input current draw from utility to 150% of the UPS output. During conditions where input current limit is active, the UPS shall be able to support 100% load, charge batteries at 10% of the UPS output rating, and provide voltage regulation with mains deviation of up to +/- 20% of the nominal input voltage. 2. In cases where the source voltage to the UPS is nominal a
Summary of the content on the page No. 7
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM condition is removed from the critical bus output of the system. Automatic transfers of load to bypass also take place if for any reason the UPS cannot support the critical bus. D. Manual Transfers: Manually initiated transfers to and from bypass may be initiated through the UPS computer interface (via serial or USB communications) or by engaging the bypass switch on the rear panel of the unit. 2.7 BATTERY A. The UPS battery system is compr
Summary of the content on the page No. 8
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 6. Self-diagnostics, self-test and proactive fault detection; 7. Communication to the host server via serial port; 8. Communication to the Network Interface Card or another SmartSlot accessory card if equipped. 9. Etc. B. Display/Control Unit: A display/control comprised of 16 LEDs and 2 pushbutton switches is located on the front side of the UPS. The display/control unit may be turned 90 degrees clockwise or counterclockwise to acc
Summary of the content on the page No. 9
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 6. The UPS is in fault state; 7. The battery needs to be replaced; 8. The battery capacity/utility voltage LED bar G. Audible Alarms: Using audio signal, the UPS will notify the user about important events. The following is the list of distinct audio alarms: 1. The UPS is on battery; 2. The UPS is on battery and the remaining battery capacity is low; 3. The UPS has shutdown due to low battery capacity; 4. The battery needs
Summary of the content on the page No. 10
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 3.2 SOFTWARE AND CONNECTIVITY A. Network Adaptor: APC SmartSlot Network Management Card shall allow one or more network management systems (NMS) to monitor and manage the UPS in TCP/IP network environments. B. Unattended Shutdown 1. The UPS, in conjunction with a network interface card, shall be capable of gracefully shutting down one or more operating systems during when the UPS is on battery mode. 2. The UPS is also capable of using
Summary of the content on the page No. 11
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 7. TurboLinux v.7.0 and 8.0 8. Novell Netware 6.0 with Support Pack 1 9. Novell Netware 6.5 10. Novell Netware 5.1 with Support Pack 3 or above (using PowerChute Business Edition v6.2.2 agent) 11. Sun Solaris 8 and 9 PART 4 - Part 4 - EXECUTION 4.1 FACTORY ASSISTED START-UP If a factory assisted UPS start-up is requested, factory trained service personnel shall perform the following inspections, test procedures, and on-s
Summary of the content on the page No. 12
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 1. Ensure proper system start-up. 2. Verify proper firmware control functions. 3. Verify proper firmware bypass operation. 4. Verify proper bypass switch operation (where applicable). 5. Verify proper inverter operation and regulation circuits. 6. Simulate utility power failure. 7. Verify proper charger operation. 8. Document, sign, and date all test results. E. On-Site Operational Training: During the factory assisted star
Summary of the content on the page No. 13
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM identification and operation, system controls and adjustment, preventative maintenance, and troubleshooting. End Of Section 16611 CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM