American Power Conversion POWERCELL user manual

User manual for the device American Power Conversion POWERCELL

Device: American Power Conversion POWERCELL
Category: Power Supply
Manufacturer: American Power Conversion
Size: 0.28 MB
Added : 3/12/2014
Number of pages: 36
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for American Power Conversion POWERCELL. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with American Power Conversion POWERCELL.

For your convenience

If looking through the American Power Conversion POWERCELL user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual American Power Conversion POWERCELL on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual American Power Conversion POWERCELL to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
American Power Conversion POWERCELL User manual - Online PDF
Advertisement
« Page 1 of 36 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual American Power Conversion POWERCELL but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to American Power Conversion POWERCELL. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

®
POWERCELL
Models
Network
Professional
Personal
User's
Manual

Summary of the content on the page No. 2

Important safety instructions! Please read this manual! Veuillez lire ce manuel! ¡Se ruega leer este manual de instrucciones! Thank you for selecting this American Power Conversion Uninterruptible Power System (UPS). It has been designed for many years of reliable, maintenance free service. American Power Conversion is dedicated to the development of high performance electrical conversion and control products and we hope that you will find this UPS a valuable, convenient addition to your compu

Summary of the content on the page No. 3

Table of contents 1.0 Introduction ........................................................... 2 2.0 Safety! ................................................................... 5 Sécurité! (Françias)....................................................................................... 6 Seguridad! (Español) ................................................................................... 7 3.0 Installation.............................................................8 4.0 Principles of operati

Summary of the content on the page No. 4

This page intentionally left blank. Page 2

Summary of the content on the page No. 5

1.0 Introduction 1.1 Overview Your PowerCell is a high performance standby uninterruptible power system designed to protect computers and peripheral devices such as monitors, mo- dems, tape drives, etc. from utility line failures which could result in the loss or corruption of valuable data. In the event of a utility failure such as a blackout, brownout or sag, the PowerCell rapidly transfers loads (computer equipment) to an alternative power source. This alternative power is derived from a ba

Summary of the content on the page No. 6

1.0 Introduction 1.4 Surge suppression and EMI/RFI filtering Your PowerCell provides high performance surge suppression and EMI/RFI (electromagnetic and radio frequency interference) filtering. The UPS sup- presses surges defined by the ANSI C62.41 (formerly IEEE 587) Category A and B standard to levels well below that which is compatible with your computer. 1.5 Remote interface - Network model A remote computer interface port capable of signalling utility failure and low battery conditions is

Summary of the content on the page No. 7

ENGLISH 2.0 Safety ! Caution! CAUTION ! ■ To reduce the risk of electric shock, disconnect the Uninterruptible Power Source from the mains before installing a computer interface signal cable (when used). Reconnect the power cord only after all signalling interconnections have been made. ■ Connect the Uninterruptible Power Source to a two-pole, three-wire ground- ing mains receptacle. The receptacle must be connected to appropriate branch protection (fuse or circuit breaker). Connection

Summary of the content on the page No. 8

FRANÇAIS 2.0 Sécurité ! Attention! ATTENTION! ■ Pour réduire le risque d’électrocution, débranchez la prise principale de la source d’alimentation permanente (Uninterruptible Power Source), avant d’installer le câble d’interface allant à l’ordinateur (si utilisé). Ne rebranchez le bloc d’alimentation qu’après avoir effectué toutes les connections. ■ Branchez la source d’alimentation permanente (UPS) dans une prise de courant à 3 dérivations (deux pôles et la terre). Cette prise doit être m

Summary of the content on the page No. 9

ESPAÑOL 2.0 ¡ Seguridad ! ¡Atencion! ¡ATENCION! ■ Para reducir el riesgo de descarga eléctrica, desconecte de la red la Fuente de energía ininterrumpible antes de instalar el cable de señalización de interfaz de la computadora (si se usa). Vuelva a conectar el conductor flexible de alimentación solamente una vez efectuadas todas las interconexiones de señalización. ■ Conecte la Fuente de energía ininterrumpible a un tomacorriente bipolar y trifilar con neutro de puesta a tierra. El tomacor

Summary of the content on the page No. 10

3.0 Installation 3.1 Receiving inspection Once your PowerCell has been removed from its shipping container, it should be inspected for damage that may have occurred while in transit. Immediately notify the carrier and place of purchase if any damage is found. The packing materials are made from recyclable materials and should be saved for reuse or disposed of properly. 3.2 Placement Your PowerCell may be installed in any protected environment. The location should provide adequate air flow aro

Summary of the content on the page No. 11

3.0 Installation 3.4 Connecting to the utility Your PowerCell is furnished with a 6 foot line cord terminated with a standard NEMA 5-15P three pronged plug. The UPS must be plugged into a 2 pole, 3 wire grounding receptacle. If an extension cord must be used between the UPS and the nearest wall outlet, use a 3 wire grounding type rated for at least 10 Amps. Your PowerCell is provided with a rear SITE WIRING FAULT indicator. Once loads are connected, the indicator illuminates when the UPS i

Summary of the content on the page No. 12

3.0 Installation 3.6 Connecting equipment to the PowerCell To ensure that your computer equipment will be protected during a utility failure and that you receive expected run time, it is important that you determine the total power needs of the equipment you wish to protect with the PowerCell. The power requirements of your equipment should be less than or equal to the capacity of the PowerCell. The capacity rating of your PowerCell, in both Volt- Amperes (VA) and Watts (W), is given in the Sp

Summary of the content on the page No. 13

3.0 Installation 3.6 Connecting equipment to the PowerCell (continued) requirement of your equipment is 50% greater than the capacity of the UPS! 3.6.5 Once all power requirement figures have been converted to VA units and added together, simply determine whether the power requirements of your equipment is less than or equal to the capacity of your PowerCell. If this is not the case, then it must be decided which equipment should be left unprotected by the UPS. Many times, the system printer m

Summary of the content on the page No. 14

3.0 Installation 3.6 Connecting equipment to the PowerCell (continued) 3.6.7 Once you have determined that your equipment and the UPS are compat- ible, plug your equipment into the UPS’s rear panel output receptacles. Note: Do not plug laser printers into your PowerCell! The power requirements of a typical laser printer are much larger than the requirements of other computer peripherals and may trip the UPS’s rear panel circuit breaker. Plug laser printers into an APC ® SurgeArrest surge suppr

Summary of the content on the page No. 15

3.0 Installation 3.7 Test for proper operation (continued) following section covering Overloads if abnormal operation is encountered. The power I/0 control switches power to your equipment. If you leave your equipment power switches on, the I/0 power control can be used as a master on/ off switch! 3.8 Overloads If the total power requirement of your equipment is much greater than the capacity of your PowerCell, its rear panel circuit breaker may trip. This is called an overload situation. Onc

Summary of the content on the page No. 16

4.0 Principles of operation Below is a block diagram showing the major components of your PowerCell UPS. These blocks are described on the following pages. Block diagram showing all major components of your UPS. Page 14

Summary of the content on the page No. 17

4.0 Principles of operation 4.1 Noise and surge suppression Your PowerCell contains high performance EMI/RFI (Electro-Magnetic and Radio Frequency Interference) noise and surge suppression circuitry to protect your computer equipment. The PowerCell provides this suppression continu- ously, whether or not it is turned on. Normally, your PowerCell suppresses noise and surges without your notice; that is, the UPS doesn’t transfer your load to its internal power source. Instead, the suppression c

Summary of the content on the page No. 18

4.0 Principles of operation 4.2 Load transfer switch The load transfer switch is actually an electro-dynamic relay which serves to rapidly transfer your computer equipment (load) from the utility to the PowerCell’s alternate power source in the event of a utility failure. When the utility is restored to within safe limits, the switch acts to re-transfer the load to the utility. Except for the user control switches, the transfer switch is the only moving part in the PowerCell. The time require

Summary of the content on the page No. 19

4.0 Principles of operation 4.6 Transformer The PowerCell’s transformer is an electrical component which “steps up” the output voltage of the inverter to the normal utility line voltage (115 Vac). In addition, it serves to isolate the PowerCell from equipment failures. 4.7 Monitoring and control electronics This block is the “brain” of the PowerCell. The monitoring and control circuitry detects utility failures such as blackouts, sags and brownouts; synchronizes the inverter’s output frequency

Summary of the content on the page No. 20

4.0 Principles of operation 4.8 Operation during a utility failure (continued) of the battery (the battery could be charged faster, but wouldn’t last as long). Utility voltage sags are temporary amplitude reductions of the normal 120 Vac line. Utility voltage sags can be caused by local high power demand equipment such as elevators, air conditioners, shop tools and electric heaters. Brownouts, defined as long lasting utility voltage reductions, are sometimes initiated by the power company itse


Alternative user manuals
# User manual Category Download
1 American Power Conversion 100 User manual Power Supply 0
2 American Power Conversion 120 User manual Power Supply 0
3 American Power Conversion 110, 120, 230 User manual Power Supply 0
4 American Power Conversion 10000 VA User manual Power Supply 1
5 American Power Conversion 1000, 1100, 1400 User manual Power Supply 2
6 American Power Conversion 110Vac User manual Power Supply 0
7 American Power Conversion 1400XLT User manual Power Supply 0
8 American Power Conversion 1050 User manual Power Supply 0
9 American Power Conversion 10-40kW 208/480V User manual Power Supply 0
10 American Power Conversion 2200 VA User manual Power Supply 0
11 American Power Conversion 2200XLT User manual Power Supply 0
12 American Power Conversion 208/220 User manual Power Supply 0
13 American Power Conversion 20000 VA User manual Power Supply 3
14 American Power Conversion 2200VA 3U User manual Power Supply 0
15 American Power Conversion 230 VAC User manual Power Supply 0
16 Sony AC U50A User manual Power Supply 5
17 Sony AC LS1 User manual Power Supply 2
18 Sony NP-FM30 User manual Power Supply 35
19 Sony NP FX101 User manual Power Supply 1
20 Sony NH-AAA-DA User manual Power Supply 2