Champion Manufacturing D1EB036 user manual

User manual for the device Champion Manufacturing D1EB036

Device: Champion Manufacturing D1EB036
Category: Air Conditioner
Manufacturer: Champion Manufacturing
Size: 0.65 MB
Added : 3/1/2014
Number of pages: 20
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Champion Manufacturing D1EB036. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Champion Manufacturing D1EB036.

For your convenience

If looking through the Champion Manufacturing D1EB036 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Champion Manufacturing D1EB036 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Champion Manufacturing D1EB036 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Champion Manufacturing D1EB036 User manual - Online PDF
Advertisement
« Page 1 of 20 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Champion Manufacturing D1EB036 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Champion Manufacturing D1EB036. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

INSTALLATION
MANUAL - 50 HZ
®
CHAMPION SERIES
SINGLE PACKAGE AIR CONDITIONERS
CONTENTS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
ELECTRIC/ELECTRIC, AIR-COOLED
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
MODELS: D1EB036, 048 DIRECT DRIVE
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
REFERENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
D1EB060 BE

Summary of the content on the page No. 2

173858-YIM-A-0306 TABLE OF CONTENTS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 LIST OF FIGURES INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Fig. # Pg. # REFERENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . . 4 2 TYPICAL FIELD WIRING DIAGRAM . . . . . . . . . . . . . . 7 REPLACEMENT PARTS . . . . . . . . . . . . . . .

Summary of the content on the page No. 3

173858-YIM-A-0306 be made in writing. Refer to Form 50.15-NM for additional GENERAL information. Model D1EB units are factory assembled cooling only air con- ditioners designed for outdoor installation on a rooftop or a REFERENCE slab. Additional information on the design, installation, operation The units are completely assembled on rigid, but easily and service of this equipment is available in the following ref- removable base rails. All piping, refrigerant charge, and elec- erence forms: tri

Summary of the content on the page No. 4

173858-YIM-A-0306 should meet local codes and unit weight. Do not tie the installation. Rig unit with slings placed under the unit. slab to the building foundation. Spreader bars of sufficient length should be used across the top of the unit. 4. For roof top installation, be sure the structure will support the weight of the unit plus any field installed components. BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT Unit must be installed on a level roof curb or appropriate IS DISTRIBUTED EQUALL

Summary of the content on the page No. 5

173858-YIM-A-0306 Duct work should be designed and sized according to the Filters should be checked monthly especially since this unit methods of the Air Conditioning Contractors of America may be used for both heating and cooling. (ACCA), as set forth in their Manual D. CONDENSATE DRAIN A closed return duct system shall be used. This shall not pre- clude use of economizers or ventilation air intake. Flexible A condensate trap is required to be installed in the conden- joints may be used in the

Summary of the content on the page No. 6

173858-YIM-A-0306 TABLE 3: PHYSICAL DATA MODELS COMPONENT DEB036 DEB048 DEB060 NOMINAL TONNAGE 3.0 4.0 5.0 COOLING PERFORMANCE RATING T1 T2 T2 T1 T2 T3 T1 T2 T3 Indoor DB/WB °C 27 / 19 29 / 19 21 / 15 27 / 19 29 / 19 21 / 15 27 / 19 29 / 19 21 / 15 Outdoor DB/WB °C 35 / 24 46 / 24 27 / 19 35 / 24 46 / 24 27 / 19 35 / 24 46 / 24 27 / 19 Total Output (MBH) 36500 30550 34500 47000 40900 45000 58300 50800 54500 Total Output kW (MBH) 125 / 36.5 104 / 30.6 118 / 34.5 160 / 47 140 / 40.9 154 / 45 199 /

Summary of the content on the page No. 7

173858-YIM-A-0306 POWER AND CONTROL WIRING Electrical line must be sized properly to carry the load. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused. Field wiring to the unit must conform to provisions of the cur- rent N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordi- Refer to Figure 2 for typical field wiring and to the appropriate nances. The unit must be electrically grounded in accordance unit wiring diagram for control circuit a

Summary of the content on the page No. 8

173858-YIM-A-0306 TABLE 4: ELECTRICAL DATA 3 COMPRESSOR OD FAN SUPPLY MAX. FUSE 1 2 SIZE MCA MOCP (EACH) MODEL POWER MOTORS BLOWER SIZE (TONS) (AMPS) (AMPS) (EACH) MOTOR RLA LRA MCC (AMPS) 036 DEB 380/415-3-50 6.7 39.0 9.5 1.0 1.8 11.2 15 15 (3.0) 048 DEB 380/415-3-50 8.7 66.5 12.5 1.0 3.2 15.1 20 20 (4.0) 060 DEB 380/415-3-50 10.4 73.0 13.0 1.0 2.7 15.7 25 25 (5.0) 1. Minimum Circuit Ampacity. 2. Maximum Over Current Protection per standard UL 1995. 3. Fuse or HACR circuit breaker size installe

Summary of the content on the page No. 9

173858-YIM-A-0306 TABLE 5: ADDITIONAL STATIC RESISTANCE Wet Indoor Filter / Frame 1 Size Airflow Economizer Model Coil Kit 3 (Tons) m /s (cfm) Pa (in.wc) Pa (in.wc) Pa (in.wc) 0.42 (900) 12.45 (0.05) 2.49 (0.01) 4.98 (0.02) 0.47 (1000) 14.95 (0.06) 2.49 (0.01) 4.98 (0.02) 0.52 (1100) 17.44 (0.07) 4.98 (0.02) 7.47 (0.03) 036 DEB 0.57 (1200) 17.44 (0.07) 4.98 (0.02) 7.47 (0.03) (3.0) 0.61 (1300) 19.93 (0.08) 7.47 (0.03) 7.47 (0.03) 0.66 (1400) 22.42 (0.09) 9.96 (0.04) 9.96 (0.04) 0.71 (1500) 24.91

Summary of the content on the page No. 10

173858-YIM-A-0306 TABLE 6: D1EB036 SUPERHEAT CHARGING (IMPERIAL) SUPERHEAT AT COMPRESSOR SUCTION (°F) AIRFLOW = 1,300 CFM OUTDOOR TEMPERATURE INDOOR WB TEMPERATURE (°F) (°F) 55 57 59 61 63 65 67 69 71 73 75 65 21.1 21.6 22.1 22.7 23.2 23.8 24.3 25.3 26.4 26.9 27.4 70 19.5 20.0 20.6 21.1 21.7 22.2 22.8 24.0 25.1 25.7 26.3 75 17.9 18.5 19.0 19.6 20.2 20.7 21.3 22.6 23.9 24.6 25.2 80 16.3 16.9 17.5 18.0 18.6 19.2 19.8 21.2 22.7 23.4 24.1 85 14.7 15.3 15.9 16.5 17.1 17.7 18.3 19.9 21.4 22.2 23.0

Summary of the content on the page No. 11

173858-YIM-A-0306 TABLE 8: D1EB048 SUPERHEAT CHARGING (IMPERIAL) SUPERHEAT AT COMPRESSOR SUCTION (°F) AIRFLOW = 1,800 CFM OUTDOOR TEMPERATURE INDOOR WB TEMPERATURE (°F) (°F) 55 57 59 61 63 65 67 69 71 73 75 65 19.9 21.0 22.1 23.3 24.4 25.6 26.7 28.0 29.3 30.0 30.7 70 16.5 17.9 19.2 20.6 22.0 23.4 24.8 26.3 27.8 28.6 29.4 75 13.1 14.7 16.3 18.0 19.6 21.3 22.9 24.6 26.3 27.2 28.1 80 9.7 11.6 13.4 15.3 17.2 19.1 21.0 22.9 24.8 25.8 26.8 85 6.3 8.4 10.5 12.7 14.8 17.0 19.1 21.2 23.3 24.4 25.5 9

Summary of the content on the page No. 12

173858-YIM-A-0306 TABLE 10: D1EB060 SUPERHEAT CHARGING (IMPERIAL) SUPERHEAT AT COMPRESSOR SUCTION (°F) AIRFLOW = 2,000 CFM OUTDOOR TEMPERATURE INDOOR WB TEMPERATURE (°F) (°F) 55 57 59 61 63 65 67 69 71 73 75 65 21.9 23.8 25.7 27.6 29.4 31.3 33.2 34.2 35.1 35.6 36.1 70 16.0 18.4 20.7 23.0 25.3 27.6 30.0 31.3 32.7 33.4 34.0 75 10.1 12.9 15.7 18.4 21.2 23.9 26.7 28.5 30.2 31.1 32.0 80 - 7.5 10.7 13.9 17.1 20.3 23.5 25.6 27.8 28.9 29.9 85 - - 5.6 9.3 12.9 16.6 20.2 22.8 25.3 26.6 27.9 90 - - -

Summary of the content on the page No. 13

173858-YIM-A-0306 FIGURE 5 - UNIT DIMENSIONS Unitary Products Group 13

Summary of the content on the page No. 14

173858-YIM-A-0306 SECURE OWNER'S APPROVAL SEQUENCE OF OPERATION When the system is functioning properly, secure the owner's COOLING approval. Show the owner the location of all disconnect switches and the thermostat. Teach the owner how to start The following sequences of operation are based on using a and stop the unit and how to adjust temperature settings standard single-stage cooling thermostat. within the limitations of the system. WITH POWER TO UNIT AND THERMOSTAT IN COOLING MAINTENANCE MO

Summary of the content on the page No. 15

173858-YIM-A-0306 FIGURE 3 - TYPICAL WIRING DIAGRAM 3 & 4 TON (380/415-3-50 POWER SUPPLY) Unitary Products Group 15

Summary of the content on the page No. 16

173858-YIM-A-0306 FIGURE 4 - TYPICAL WIRING DIAGRAM 5 TON (380/415-3-50 POWER SUPPLY) 16 Unitary Products Group

Summary of the content on the page No. 17

173858-YIM-A-0306 FIGURE 5 - TYPICAL WIRING DIAGRAM LEGEND 1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT. 2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SER- VICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DAN- GEROUS OPERATION. IF ANY OF THE WIRE AS SUPPLIED WITH THIS UNIT MUST BE REM

Summary of the content on the page No. 18

173858-YIM-A-0306 18 Unitary Products Group

Summary of the content on the page No. 19

173858-YIM-A-0306 Unitary Products Group 19

Summary of the content on the page No. 20

Subject to change without notice. Printed in U.S.A. 173858-YIM-A-0306 Copyright © 2006 by Unitary Products Group. All rights reserved. Supersedes: Nothing Unitary 5005 Norman Products York OK Group Drive 73069


Alternative user manuals
# User manual Category Download
1 Champion Manufacturing 24 User manual Air Conditioner 10
2 Champion Manufacturing 48 User manual Air Conditioner 3
3 Champion Manufacturing 36 User manual Air Conditioner 1
4 Champion Manufacturing 60 User manual Air Conditioner 0
5 Champion Manufacturing D1EB060 User manual Air Conditioner 1
6 Champion Manufacturing 30 User manual Air Conditioner 0
7 Champion Manufacturing 42 User manual Air Conditioner 1
8 Champion Manufacturing DNH: 018 User manual Air Conditioner 2
9 Sony SU-PW2 User manual Air Conditioner 12
10 Sony CV-P12PX User manual Air Conditioner 3
11 Sony MULTI CHANNEL AV RECEIVER STR-DG710 User manual Air Conditioner 31
12 Sony VGN-BX500 User manual Air Conditioner 1
13 Philips 190S5 User manual Air Conditioner 21
14 Philips Comfort-Cire AMC 45 User manual Air Conditioner 7
15 Philips Comfort-Cire AMC 30 User manual Air Conditioner 2