Summary of the content on the page No. 1
30GX-4SB
30GX080-265
AIR-COOLED LIQUID CHILLER
— PERFORMANCE DATA
— CERTIFIED DIMENSION PRINT
— FIELD WIRING DIAGRAM
R 1997 Carrier Corporation • Syracuse, New York 13221
Form 30GX-4SB Supersedes 30GX-3SB Printed in U.S.A. 12-97 Catalog No. 513-450
Summary of the content on the page No. 2
Date: Supersedes: 30GX080-265 Rev.: 30GX AIR-COOLED LIQUID CHILLER -4SB JOB NAME: LOCATION: BUYER: BUYER P.O. # CARRIER # UNIT NUMBER: MODEL NUMBER: PERFORMANCE DATACERTIFIED BY: DATE: DESCRIPTION Packaged air-cooled liquid chiller factory wired, piped, and charged with HFC-134a. Upward discharge airflow minimizes directional sound and dissipates heat away from surrounding areas. FEATURES Cooler is mechanically cleanable ‘‘flooded’’ shell-and-tube type Condenser fan motors are totally enclosed 3-p
Summary of the content on the page No. 3
3 CUTALONG DOTTED LINE CUTALONG DOTTED LINE ---------------------------------------------------------------------------------------- CERTIFIED DIMENSION PRINT
Summary of the content on the page No. 4
4 CERTIFIED DIMENSION PRINT
Summary of the content on the page No. 5
5 CUTALONG DOTTED LINE CUTALONG DOTTED LINE ---------------------------------------------------------------------------------------- CERTIFIED DIMENSION PRINT
Summary of the content on the page No. 6
6 CERTIFIED DIMENSION PRINT
Summary of the content on the page No. 7
7 CUTALONG DOTTED LINE CUTALONG DOTTED LINE ---------------------------------------------------------------------------------------- CERTIFIED DIMENSION PRINT
Summary of the content on the page No. 8
8 CERTIFIED DIMENSION PRINT TOTAL OPERATING TOTAL OPERATING WEIGHT WEIGHT UNIT 30GX Aluminum Fin Copper Fin lb kg lb kg 205 12,184 5,538 13,569 6,168 225 12,364 5,620 13,749 6,250 NOTES: 1. Unit must have clearances for air flow as follows: Top — Do not restrict in any way Ends — (1524 mm) 5 ft (from solid surface) Sides — (1829 mm) 6 ft 2. Unit with sound hoods requires clearances for air flow as follows: Top — Do not restrict in any way Ends — (1829 mm) 6 ft Sides — (2134 mm) 7 ft 3. Centerofgra
Summary of the content on the page No. 9
9 CUTALONG DOTTED LINE CUTALONG DOTTED LINE ---------------------------------------------------------------------------------------- CERTIFIED DIMENSION PRINT TOTAL OPERATING TOTAL OPERATING WEIGHT WEIGHT UNIT 30GX Aluminum Fin Copper Fin lb kg lb kg 206 12,794 5,815 14,462 6,574 226 12,974 5,897 14,642 6,655 250 13,194 5,997 14,862 6,755 NOTES: 1. Unit must have clearances for air flow as follows: Top — Do not restrict in any way Ends — (1524 mm) 5 ft (from solid surface) Sides — (1829 mm) 6 ft
Summary of the content on the page No. 10
10 CERTIFIED DIMENSION PRINT TOTAL OPERATING TOTAL OPERATING WEIGHT WEIGHT UNIT 30GX Aluminum Fin Copper Fin lb kg lb kg 251 13,774 6,621 15,549 7,068 265 13,829 6.286 15,604 7,093 NOTES: 1. Unit must have clearances for air flow as follows: Top — Do not restrict in any way Ends — (1524 mm) 5 ft (from solid surface) Sides — (1829 mm) 6 ft 2. Unitwithsoundhoodsrequiresclearancesforairflow as follows: Top — Do not restrict in any way Ends — (1829 mm) 6 ft Sides — (2134 mm) 7 ft 3. Center of gravity
Summary of the content on the page No. 11
11 CUTALONG DOTTED LINE CUTALONG DOTTED LINE ---------------------------------------------------------------------------------------- FIELD WIRING DIAGRAM NOTES: LEGEND 1. Factory wiring is in accordance with National Electrical Code (NEC). Field modifica- CCN — Carrier Comfort Network tions or additions must be in compliance with all applicable codes. CWFS — Chilled Water Flow Switch 2. Wiring for main field power supply must be rated 75° C minimum. Use copper for all CWP — Chilled Water Pump uni
Summary of the content on the page No. 12
12 FIELD WIRING DIAGRAM NOTES: LEGEND 1. Factory wiring is in accordance with National Electrical Code (NEC). Field modifi- CCN — Carrier Comfort Network TB — Terminal Block cations or additions must be in compliance with all applicable codes. CWFS — Chilled Water Flow Switch Field Power Wiring 2. Wiring for main field power supply must be rated 75° C minimum. Use copper for CWP — Chilled Water Pump all units. Maximum incoming wire size for each terminal block is 500 kcmil. Field Control Wiring CW