Bryant CeilingPAC 502A user manual

User manual for the device Bryant CeilingPAC 502A

Device: Bryant CeilingPAC 502A
Category: Air Conditioner
Manufacturer: Bryant
Size: 0.73 MB
Added : 11/14/2014
Number of pages: 16
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Bryant CeilingPAC 502A. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Bryant CeilingPAC 502A.

For your convenience

If looking through the Bryant CeilingPAC 502A user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Bryant CeilingPAC 502A on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Bryant CeilingPAC 502A to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Bryant CeilingPAC 502A User manual - Online PDF
Advertisement
« Page 1 of 16 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Bryant CeilingPAC 502A but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Bryant CeilingPAC 502A. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

HORIZONTAL INDOOR
Model 502A
SINGLE PACKAGE
CeilingPAC
COOLING UNITS 2 to 5 Tons
Single Package Cooling Units Featuring: challenge by specifying heavy insulation, vibration-resistant
construction and operating components that function at low
• compact design
noise levels, all of which keep system sound at a minimum
 flexibility
level.
 easy maintenance
 high quality and reliability When it comes to maintenance, the
EASY MAINTENANCE —
 quiet and efficient scroll compressor technology 502A un

Summary of the content on the page No. 2

TABLE OF CONTENTS Page Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . 2 ARI Capacity Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Field-Installed Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Base Unit Dimensions . . . . . . . . . . . . . .

Summary of the content on the page No. 3

PHYSICAL DATA UNIT 502A 024 036 048 060 SHIPPING WEIGHT (lb)* 560 590 690 700 OPERATING WEIGHT (lb) Base Unit 450 480 580 590 REFRIGERANT TYPE R-22 Operating Charge (lb)† 5.4 5.5 8.0 7.6 COMPRESSOR — TYPE Scroll Quantity...Model (1)...ZR23 (1)...ZR34 (1)...ZR49 (1)...ZR57 Oil (oz) 24 42 48 54 HPS Setting (psig) Cutout 426 ± 7 Reset 320 ± 20 LPS Setting (psig) Cutout 27 ± 4 Reset 67 ± 7 CONDENSATE DRAIN CONNECTION 3 Size (in.)...Type / ...FPT 4 CONDENSER FAN Centrifugal — Direct Drive Centrifugal

Summary of the content on the page No. 4

FIELD-INSTALLED ACCESSORIES Thermostat and Subbase — Attractive wall-mounted 24-v Condensate Pump — The condensate pump is used when the accessory provides precise temperature control. Automatic and distance and slope to the nearest drain is far enough to prevent Manual changeover models available. A thermostat subbase is the natural drainage of unit. The pump is mounted remotely available that works with Cycle-LOC™ circuitry. If a safety from the unit and includes a signal light (field-installe

Summary of the content on the page No. 5

BASE UNIT DIMENSIONS DIMENSIONS (ft-in.) UNIT ABCD E 502A 5 3 024 2-5 2-1 / 1- 5 / 1-2 1-1 8 4 3 3 036 2-4 / 2-2 1- 5 / 1-2 1-1 4 4 5 7 7 048 2-5 2-3 1-11 / 1-8 / 1-7 / 8 8 8 3 3 5 7 7 060 2-4 / 2-2 / 1-11 / 1-8 / 1-7 / 4 4 8 8 8 Unit Component Locations 5

Summary of the content on the page No. 6

SELECTION PROCEDURE (with example) I DETERMINE COOLING REQUIREMENTS AT DESIGN 67 F ewb will provide a Total Capacity (TC) of 44,200 Btuh and a Sensible Heat Capacity (SHC) of 31,300 Btuh. CONDITIONS. Since the entering air is 80 F edb, an SHC correction is Given: not required. Gross Cooling Capacity III DETERMINE EVAPORATOR FAN PERFORMANCE. Required (TC). . . . . . . . . . . . . . . . . . . . . . . . . 39,000 Btuh Enter Evaporator Fan Performance table at 1200 cfm Sensible Heat Capacity (SHC) .

Summary of the content on the page No. 7

PERFORMANCE DATA (cont) GROSS COOLING CAPACITIES (cont) 502A048 502A060 Evaporator Air Quantity Cfm/BF Evaporator Air Quantity — Cfm/BF Temp Temp 1200/0.06 1600/0.08 2000/0.10 1500/0.06 2000/0.09 2250/0.10 Air Ent Air Ent Condenser Condenser Evaporator Air Ewb Temp (F) Evaporator Air Ewb Temp (F) (F) (F) 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 72 67 62 72 67 62 TC 56.0 52.1 47.9 44.4 57.7 54.5 50.6 49.6 59.4 56.0 52.7 52.3 TC 64.8 58.5 52.9 68.0 61.5 56.3 68.9 62.5 58.0 85 SHC 27.8 34.8 41

Summary of the content on the page No. 8

PERFORMANCE DATA (cont) BELT DRIVE EVAPORATOR FAN PERFORMANCE (Special Order Only, Pricing and ordering on related price pages.) UNIT SIZE — 502A CFM 048 060 ESP Fan kW ESP Fan kW 1800 ———— 1850 ———— 1900 ———— 1950 .81 1.03 —— 2000 .72 1.05 —— 2050 .63 1.07 —— 2100 .55 1.08 1.02 1.17 2150 .47 1.11 .93 1.21 2200 .42 1.14 .84 1.24 2250 .34 1.17 .75 1.27 LEGEND ESP — External Static Pressure (in. wg) kW — Total Fan Power Motor Input (kilowatts) NOTE: Pulley setting must be adjusted to limit cfm to

Summary of the content on the page No. 9

CONTROLS OPERATING SEQUENCE 2. When room thermostat is satisfied, the evaporator fan, com- pressor, and condenser fan shut off. Cooling The thermostat can be set for Continuous Fan Operation — 1. Thermostat calls for cooling. continuous operation by setting the fan switch to ON. a. Indoor (evaporator) fan relay is energized and starts evaporator fan. b. Compressor contactor is energized to start compressor and condenser fan (up to a 5-minute delay on single- phase units). ELECTRICAL DATA FAN MO

Summary of the content on the page No. 10

ELECTRICAL DATA (cont) ELECTRIC HEATER STATIC PRESSURE DROP (in. wg) UNIT CFM ELECTRIC HEATER UNIT MIN UNIT 88EN 502A CFM 600 800 1000 1200 1400 1600 1800 2000 2200 0050CA01 400 .02 .04 .06 .10 ————— 024, 036 510 .03 .06 .10 .16 ————— 0075CA01 1-stage 0115CA01 620 heat 0075EA01 320 .04 .08 .13 .19 ————— 1150EA01 720 0100EA01 970 ——— .04 .06 .08 .12 .15 .17 0150EA01 1240 0200EA01 1350 1220 ——— .08 .11 .14 .18 .22 .26 0300EA01 048, 060 0300CA01 1220 2-stage heat 0100FA01 1130 ——— .04 .06 .08 .12 .

Summary of the content on the page No. 11

TYPICAL WIRING SCHEMATICS (cont) LEGEND AHA — Adjustable Heat Anticipator TH — Thermostat-Heating NOTES: C — Contactor Compressor TRAN — Transformer 1. Neutral for 240/416 v supply (Canada only). CAP — Capacitor 2. If any original wires furnished must be replaced, it should be Marked Wire CB — Circuit Breaker replaced with 90 C or its equivalent. CC — Cooling Compensator 3. Numbers indicate the line location of used contacts. A bracket Denotes connection point between CDT — Compressor Discharge

Summary of the content on the page No. 12

TYPICAL WIRING SCHEMATICS (cont) LEGEND NOTES: AHA — Adjustable Heat Anticipator 2. If any original wires furnished must be replaced, it should be Marked Wire C — Contactor Compressor replaced with 90 C or its equivalent. CAP — Capacitor 3. Numbers indicate the line location of used contacts. A bracket Denotes connection point between CB — Circuit Breaker subbase and thermostat over 2 numbers signifies a single-pole double-throw contact. An CC — Cooling Compensator underlined number signifies a

Summary of the content on the page No. 13

TYPICAL WIRING SCHEMATICS (cont) LEGEND AHA — Adjustable Heat Anticipator Denotes connection point between NOTES: BKR W/AT — Breaks with Amp Turns subbase and thermostat C — Contactor Compressor 1. Compressor and fan motors are thermally protected, three-phase CC — Cooling Compensator motors protected against primary single-phase conditions. Terminal (Marked) CLO — Compressor Lockout 2. If any original wires furnished must be replaced, it should be COMP — Compressor Motor Terminal (Unmarked) rep

Summary of the content on the page No. 14

TYPICAL PIPING AND WIRING LEGEND NEC — National Electrical Code NOTES: 3. All piping must follow standard refrigerant piping techniques. 1. Wiring and piping shown are not intended for or to include all 4. For other installation details refer to Installation Instructions. details for specific installation. 5. If unit sections are field split, 8 threaded support rods are required. 2. All wiring must comply with applicable local and national codes. 6. Ensure condenser air recirculation is minimize

Summary of the content on the page No. 15

GUIDE SPECIFICATIONS INDOOR PACKAGED UNIT C. Fans: HVAC GUIDE SPECIFICATIONS — SECTION 15787 1. Evaporator: SIZE RANGE: 2 TO 5 TONS, NOMINAL a. Blower shall be of the forward-curved, centrifugal, direct-drive type or belt drive (4 and 5 tons only). BRYANT MODEL NUMBER: 502A b. Motor shall have permanently lubricated PART 1 — GENERAL bearings. 1.01 SYSTEM DESCRIPTION c. Unit sizes 048, 060 shall be available with an Indoor mounted, electrically controlled packaged horizon- optional 1.5 hp fan mot

Summary of the content on the page No. 16

GUIDE SPECIFICATIONS (cont) 3. Compressor Cycle Delay: 6. Vibration Isolation Package: Prevents compressor from restarting for a minimum Shall provide 4 spring hangers for ceiling mounted of 5 minutes after shutdown. unit to damper vibration that may be transmitted to building structure. * 4. Condensate Pump: 7. Time Guard® II Device: Unit shall be equipped with remotely located con- densate pump. A field-installed light shall illuminate Time Guard II device (024,048,060 single-phase when reserv


Alternative user manuals
# User manual Category Download
1 Bryant 113A User manual Air Conditioner 365
2 Bryant 24B User manual Air Conditioner 61
3 Bryant 187B User manual Air Conditioner 39
4 Bryant 342S User manual Air Conditioner 17
5 Bryant 39479D8 User manual Air Conditioner 31
6 Bryant 342 User manual Air Conditioner 15
7 Bryant 165A User manual Air Conditioner 22
8 Bryant 450D User manual Air Conditioner 21
9 Bryant 451P User manual Air Conditioner 7
10 Bryant 451 User manual Air Conditioner 7
11 Bryant 36-453 User manual Air Conditioner 10
12 Bryant 452W User manual Air Conditioner 6
13 Bryant 452 User manual Air Conditioner 3
14 Bryant 454 User manual Air Conditioner 112
15 Bryant 463AAC008BA User manual Air Conditioner 17
16 Sony SU-PW2 User manual Air Conditioner 12
17 Sony CV-P12PX User manual Air Conditioner 3
18 Sony MULTI CHANNEL AV RECEIVER STR-DG710 User manual Air Conditioner 31
19 Sony VGN-BX500 User manual Air Conditioner 1
20 Philips 190S5 User manual Air Conditioner 21