A.O. Smith NW 37-670 user manual

User manual for the device A.O. Smith NW 37-670

Device: A.O. Smith NW 37-670
Category: Boiler
Manufacturer: A.O. Smith
Size: 0.27 MB
Added : 5/25/2013
Number of pages: 12
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for A.O. Smith NW 37-670. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with A.O. Smith NW 37-670.

For your convenience

If looking through the A.O. Smith NW 37-670 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual A.O. Smith NW 37-670 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual A.O. Smith NW 37-670 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
A.O. Smith NW 37-670 User manual - Online PDF
Advertisement
« Page 1 of 12 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual A.O. Smith NW 37-670 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to A.O. Smith NW 37-670. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

DURA-POWER MODELS NW 37- 670
COMMERCIAL ELECTRIC WATER BOILERS
• Installation • Operation • Service • Maintenance • Limited Warranty
CAUTION
TEXT PRINTED OR OUTLINED IN RED CONTINS INFORMATION
STANDARD
RELATIVE TO YOUR SAFETY. PLEASE READ THOROUGHLY
BEFORE INSTALLING AND USING THE APPLIANCE.
FLOOD WARNING
IF THE BOILER SHOULD BECOME IMMERSED IN
WATER AT ANY TIME, THE BOILER SHOULD BE
EXAMINED BY A COMPETENT SERVICE PERSON A DIVISION OF A.O. SMITH CORPORATION
RENTON, WASHINGTON
BEFORE

Summary of the content on the page No. 2

DIMENSIONAL DATA SIZES AND DATA 45KW THRU 720KW Model Number Inlet* & Boiler Prefix Gal.Cap. Std.KWInput D E F G** H J K S T U Outlet* Drain NW 37 45K 32 30 12 42 12 1/2 - - 20 4 42 3 1 NW 37 60K 32 30 12 42 12 1/2 - - 20 4 42 3 1 NW 37 75K 32 30 12 42 12 1/2 - - 20 4 42 2 1 NW 37 90K 32 30 12 42 12 1/2 - - 20 4 42 3 1 NW 37 105K 32 30 12 42 12 1/2 - - 20 4 42 3 1 NW 37 120K 32 30 12 42 12 1/2 - - 20 4 42 3 1 NW 37 150K 32 30 12 42 12 1/2 - - 20 4 42 3 1 NW 37 18

Summary of the content on the page No. 3

SIZES AND DATA 780KW THRU 3300KW Model Number Inlet* & Boiler Prefix Gal.Cap. Std.KWInput D E F G** H J K S T Outlet* Drain NW 220 780K 60 50 25 71 21 2 25 1/2 30 5 1/2 5 1 1/2 NW 220 840K 60 50 25 71 21 2 25 1/2 30 5 1/2 5 1 1/2 NW 220 900K 60 50 25 71 21 2 25 1/2 30 5 1/2 5 1 1/2 NW 220 960K 60 50 25 71 21 2 25 1/2 30 5 1/2 5 1 1/2 NW 220 1020K 60 50 25 71 21 2 25 1/2 30 5 1/2 5 1 1/2 NW 220 1080K 60 50 25 71 21 2 25 1/2 30 5 1/2 5 1 1/2 NW 220 1140K 6

Summary of the content on the page No. 4

ELECTRICAL/RECOVERY DATA WATER BOILER SPECIFICATIONS Model Number Gal. Std. KW BTU Output Gal./Hr. Number of Number of Standard Number Amperage 3 Phase Prefix Cap. Input 100°F Rise Elements Steps and KW of Steps 208v 240V 480V 575V NW 37 45K 153,585 180 3 1 1@45 128 108 55 45 NW 37 60K 204,720 240 4 1 1@60 171 144 73 60 NW 37 75K 255,975 300 5 1 1@75 213 180 90 75 NW 37 90K 307,170 369 6 3 3@30 250 217 108 90 NW 37 105K 358,365 430 7 4 3@30+1@15 292 253 126 105 NW 37 120K 409,560 492 8 4 4@

Summary of the content on the page No. 5

FOREWORD APPROVALS INSTALLATION CODE REQUIREMENTS These designs comply with requirements of Underwriters Laboratories In addition to these instructions, the equipment shall be installed in accordance with those installation regulations in force in the local and bear the U.L. label on the cabinet. area where the installation is to be made. These shall be carefully All models are built to the standards of Section lV of the American followed in all cases. Authorities having jurisdiction should be

Summary of the content on the page No. 6

IMPORTANT LOCATING THE BOILER IT IS RECOMMENDED THAT A QUALIFIED SERVICE TECHNICIAN For the best installation, the boiler should be located: PERFORM THE INITIAL FIRING OF THE BOILER. AT THIS TIME 1. On a level surface. THE USER SHOULD NOT HESITATE TO ASK THE TECHNICIAN ANY QUESTIONS WHICH THEY MAY HAVE IN REGARD TO THE • Shim the channel type skid base as necessary if leveling OPERATION AND MAINTENANCE OF THE BOILER. is required. BEFORE FILLING THE SYSTEM FOR OPERATION the hot water 2. Near a f

Summary of the content on the page No. 7

Calculating Amperage/Overcurrent Protection Portion of Table 310-16 Portion of Table 310-16 Allowable Ampacities of Allowable Ampacities of Insulated The boiler is factory wired for connection to three wire single-phase Insulated Aluminum and Copper- Copper Conductors or three and four wire three-phase branch circuits. In addition, a Clad AluminumConductors Not more than three conductors in ground conductor may be required. raceway or cable or direct burial Not more than three conductors (based

Summary of the content on the page No. 8

ELECTRICAL CONFIGURATION TABLE Boiler Type Voltage Between Control Elements Nameplate of Boiler Terminal Circuit Quantity Element Markings Service Lugs Voltage Per Operating Voltage Phase (1 Phase) Contractor Voltage 1 L1 L2 N G 120 1 208 208 120 208 L1 L2 L3 N G 3 Delta 208 208 (With 120 1 208 208 Neutral) 120 L1 L2 G 1 120 1 240 240 240 L1 L2 L3 G 240 240

Summary of the content on the page No. 9

WIRING DIAGRAM 480V THREE-PHASE (WYE) SYSTEM CLEANING OPERATION The hot water system should be internally cleaned and flushed to remove contaminants which may have accumulated during installation. GENERAL System cleaning provides chemical stability necessary for component life and system performance. Never operate the heating elements without being certain the boiler is filled with water and a pressure relief valve is installed in the relief Failure to clean the system may cause: valve opening p

Summary of the content on the page No. 10

4. Close the vent as water starts to flow from the opening. Place the Tank flushing and circulating pump lubrication should be performed make-up water valve in the desired position. The boiler is now in accordance with the above schedule. Tank sediment removal and ready for START UP and TEMPERATURE REGULATION if being element lime scale removal must be performed when needed as determined by period inspections. Following are the instructions for placed in operation for the first time. perform

Summary of the content on the page No. 11

• Use a twisting, pulling action to remove elements scaled 3. If the water was excessively hot, and is now cold, the high beyond the size of the tank opening. temperature cutoff may have operated (manual reset equipped models). • Brush loose scale from elements. • To reset, turn off electricity and remove the back panel and push the reset button. • Silicates, sulfates and aluminates must be removed by • Repeated operation of the high temperature cutoff should scraping or other mechanical means.

Summary of the content on the page No. 12

NW-37 THRU NW-670 ELECTRIC HOT WATER BOILER LIMITED WARRANTY A.O. Smith Corporation, the warrantor, extends the following LIMITED WARRANTY to the owner of this boiler. 1. THE TANK If the tank in this boiler shall prove upon examination by the warrantor to have leaked due to natural corrosion from water therein, during the FIRST year after initial installation, the warrantor will at its option, repair it or provide a replacement tank less elements a n d controls of equivalent size and then curren


Alternative user manuals
# User manual Category Download
1 A.O. Smith 200 User manual Boiler 2
2 A.O. Smith 201 User manual Boiler 7
3 A.O. Smith 750 & 1000 User manual Boiler 6
4 A.O. Smith GB/GW-400 User manual Boiler 10
5 A.O. Smith DB/DW-720-1810 User manual Boiler 1
6 A.O. Smith DB-720 thru 1810 User manual Boiler 0
7 A.O. Smith GB/GW-650 User manual Boiler 3
8 A.O. Smith GB/GW-500 User manual Boiler 5
9 A.O. Smith GB/GW-200 User manual Boiler 2
10 A.O. Smith ACGSS02307 User manual Boiler 0
11 A.O. Smith 3400 User manual Boiler 0
12 A.O. Smith 1700 User manual Boiler 1
13 A.O. Smith 2000 User manual Boiler 3
14 A.O. Smith GB/GW-750 User manual Boiler 3
15 A.O. Smith DW-1810 User manual Boiler 1
16 Sony HDV 1080I HVR-M15N/M15P User manual Boiler 67
17 Sony HDV 1080I HVR-M25N/M25P User manual Boiler 50
18 A.O. Smith 200 User manual Boiler 2
19 A.O. Smith 201 User manual Boiler 7
20 A.O. Smith 750 & 1000 User manual Boiler 6