Bard Solid State Dual Unit Lead/Lag Controller MC4000 user manual

User manual for the device Bard Solid State Dual Unit Lead/Lag Controller MC4000

Device: Bard Solid State Dual Unit Lead/Lag Controller MC4000
Category: Air Conditioner
Manufacturer: Bard
Size: 1.31 MB
Added : 4/22/2014
Number of pages: 40
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Bard Solid State Dual Unit Lead/Lag Controller MC4000. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Bard Solid State Dual Unit Lead/Lag Controller MC4000.

For your convenience

If looking through the Bard Solid State Dual Unit Lead/Lag Controller MC4000 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Bard Solid State Dual Unit Lead/Lag Controller MC4000 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Bard Solid State Dual Unit Lead/Lag Controller MC4000 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Bard Solid State Dual Unit Lead/Lag Controller MC4000 User manual - Online PDF
Advertisement
« Page 1 of 40 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Bard Solid State Dual Unit Lead/Lag Controller MC4000 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Bard Solid State Dual Unit Lead/Lag Controller MC4000. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

INSTALLATION INSTRUCTIONS
& REPLACEMENT PARTS LIST
MC4000 SERIES SOLID STATE
DUAL UNIT LEAD/LAG CONTROLLER
Bard Manufacturing Company, Inc. Manual No.: 2100-563C
Bryan, Ohio 43506 Supersedes: 2100-563B
File: Vol. III Tab 19
Since 1914...Moving ahead, just as planned.
Date: 06-25-12
Manual 2100-563C
Page 1 of 40

Summary of the content on the page No. 2

CONTENTS Getting Other Information and Publications 3 Figures MC4000 General Information Figure 1 Controller Connections 1-Stage (WA/WL, W**A/ Shipping Damage .................................................. 4 W**L Series) A/C w/No Economizers ..... 17 General .................................................................. 4 Figure 2 Controller Connections 2-Stage (WA*S/WL*S Theory of Operation ............................................... 4 Series) A/C - No Economizers................ 18

Summary of the content on the page No. 3

Getting Other Information and Publications These publications can help you install the air FOR MORE INFORMATION, CONTACT conditioner or heat pump. You can usually find these at THESE PUBLISHERS: your local library or purchase them directly from the publisher. Be sure to consult current edition of each ACCA Air Conditioning Contractors of America standard. 1712 New Hampshire Avenue, NW Washington, DC 20009 Telephone: (202) 483-9370 Standard for the Installation .............. ANSI/NFPA 90A Fax:

Summary of the content on the page No. 4

The MC4000 controller can be configured for alternative (lead/lag/lead/lag) sequence, which is default setting. It can be changed to non-alternating (lead/lead/lag/lag) ** IMPORTANT ** sequence as required for special applications or user preference. The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. The MC4000 can be equipped with one of two alarm Please read entire manual before proceeding. boards, and these can be factory-ins

Summary of the content on the page No. 5

TEMPERATURE SENSORS SPECIFICATIONS/FEATURES FOR BASIC CONTROLLER The standard (local) temperature sensor has 12" leads and MC4000 Basic Controller comes installed from the factory. •Input power: 18-32 VAC, 60/50Hz, power is supplied from A secondary sensor is located internally on the main A/C #1 and/or A/C #2 controller board and serves as a reference and back-up •Isolation circuitry: no line or low voltage phasing required sensor to the local sensor. Any differential of +/- 12F •Backup power:

Summary of the content on the page No. 6

BASIC MC4000 CONTROLLER SPECIFICATIONS/FEATURES FOR INPUT/OUTPUT SPECIFICATIONS ALARM BOARDS MC4000-A w/Optional Base Alarm Board MC4000 CONTROLLER CONNECTIONS (Inputs/Outputs) Located on Main Controller Board Unit #1 C – 24VAC common NOTE: If this alarm board was not originally factory R – 24VAC hot installed, it can be field-installed at anytime. Bard G – fan (Form A, NO) part number is AB3000-A. st Y1 – 1 -stage cool (Form A, NO) nd Y2 – 2 -stage cool (Form A, NO) Inputs W – heat (Form A, NO

Summary of the content on the page No. 7

control to the “R” terminal on the blower control. The LOW VOLTAGE FIELD WIRING electronic blower control will now function as an on-off The MC4000 is powered from the air conditioners that it relay with no off-delay, and the blower motor will stop is controlling, 24 VAC (18-32V) low voltage only. running immediately when the F1-F2 fire suppression Circuitry in the MC4000 isolates the power supplies of circuit is activated (opened). the two air conditioners so that no back feeds or phasing prob

Summary of the content on the page No. 8

GENERAL PROGRAMMING OVERVIEW MC4000 CONTROLLER BUTTONS AND FUNCTION On/Off Button 1. Press and release the On/Off button to turn On controller, 4-character display will illuminate and Lead unit LED will light. 2. Press and release the On/Off button to turn Off controller. Controller will go dark and A/C units will stop. Comfort Button 1. Press and release the Comfort button to change the Cooling Set Point to 72F and the Heating Set Point to 68F for a period of 1 hour. 2. Set Points will return

Summary of the content on the page No. 9

HUMIDITY CONTROL OPTION COOLING OPERATING SEQUENCES FOR ALTERNATING LEAD/LAG/LEAD/LAG Note: This function is not available if controller is CONFIGURATION configured for heat pump. 1. 1-Stage Compressor Units No Economizer The standard air conditioning system can be adapted to st perform dehumidification control by addition of a 1 stage cooling set point is the setting (SP) input into simple humidity controller that closes-on-rise, and is the controller. Factory default is 77F (25C). On a call fo

Summary of the content on the page No. 10

th nd 4 cooling set point is 2F (default setting, user selectable 2 cooling set point is 4F (default setting, user selectable 2- nd 2-3F) warmer than Stage 3. On a call for 4th Stage 6F) warmer than Stage 1. On a call for 2 Stage cooling the cooling the Stage 4 LED comes on solid (no delay), and blower of the lag unit is turned on (if not already on – See the lag unit compressor will switch to compressor Stage 2 Blower Operation), and the Stage 2 LED will blink for 10- full capacity operation. s

Summary of the content on the page No. 11

6. 2-Stage Compressor Units with Newer COOLING OPERATING SEQUENCES FOR ECONWMT Economizers (See Note A) NON-ALTERNATING LEAD/LEAD/LAG/ LAG CONFIGURATION st 1 stage cooling set point is the setting (SP) input into the controller. Factory default is 77F (25C). On a call Note: Heat pumps cannot be operated in Non-Alternating for cooling the blower of the lead unit will come on Lead/Lead/Lag/Lag sequence. Selecting Heat Pump = immediately (if not already on – See Blower Yes will override a Non-Alt

Summary of the content on the page No. 12

rd th 3 cooling set point is 2F (default setting, user selectable 4 cooling set point is 2F (default setting, user selectable rd th 2-3F) warmer than Stage 2. On a call for 3 Stage 2-3F) warmer than Stage 3. On a call for 4 Stage cooling the blower of the lag unit is turned on (if not cooling the lag unit Y2 cooling output turns on already on – See Blower Operation), and the Stage 3 activating the lag unit compressor. If the outdoor LED will blink for 10-seconds before going solid, and temperat

Summary of the content on the page No. 13

5. 2-Stage Compressor Units with Newer HEATING SEQUENCE OF OPERATION ECONWMT Economizers (See Note A) Note: All heating sequences for air conditioners with st 1 stage cooling set point is the setting (SP) input into electric heat or heat pumps will automatically operate in the controller. Factory default is 77F (25C). On a call for Alternating Lead/Lag/Lead/Lag sequence even if cooling the blower of the lead unit will come on controller is set to Non-Alternating for cooling with or immediately

Summary of the content on the page No. 14

For Vista or Windows 7: SPECIFICATIONS FOR OPTIONAL REMOTE COMMUNICATION BOARD 1. Open Control Panel, click Network & Internet. 2. Click Network & Sharing Center. CB4000 COMMUNICATION BOARD 3. Click Local Area Network link. Note: If this communication board was not originally 4. Click Properties. factory installed it can be field-installed at anytime. Bard 5. Highlight Internet Protocol Version 4 (TCP/ part number is CB4000. Either the –A or –B alarm board IPV4) and select Properties. is require

Summary of the content on the page No. 15

  USER PAGE 4. General Alarm Status: a. Fire/Smoke, Clear or Alarm 1. The designated Admin person can assign up to 9 b. Low Temp, Clear or Alarm additional users and set-up as Admin, Write or c. High Temp #1, Clear or Alarm Read authority. d. High Temp #2, Clear or Alarm 2. User Name and password must be assigned, each e. Controller Failure, Clear or Alarm must be at least 3 characters long, and are case sensitive. SETPOINTS PAGE (Note: “Read” level authority 3. Only “Admin” can add, change or

Summary of the content on the page No. 16

CONTROLLER WIRING GENERATOR RUN FEATURE The MC4000 can be used for controlling two (2) air If desired, the MC4000 controller can be signaled from a conditioners with or without economizers. It can also be standby generator system to lockout (disable operation) configured for two (2) heat pumps without economizers. of the lag air conditioning system. This is sometimes Units with economizers will connect differently than mandated if the generator size is not sufficient to handle units without ec

Summary of the content on the page No. 17

TABLE 1 HOOK-UP DIAGRAM SELECTION TABLE — REFERENCE FIGURE 1 SHOWN Newer Older EIFM Newer Older EIFM ECONWMT MC4000-A or MC4000-B Economizer ECONWMT System Model No Economizer — No Economizer with Communication with CB4000 Economizer — No Type Series Economizer Communication with CB4000 Board – No Economizer Communication Communication Board Communication Board Board Board A/C with 1-Stage WA / WL 13 5 7 9 11 Compressor W**A / W**L A/C with 2-Stage W2 A*S / WL*S 4 6 8 12 0 1 Compressor WH / W**

Summary of the content on the page No. 18

FIGURE 2 CONTROLLER CONNECTIONS 2-STAGE (WA*S/WL*S SERIES) AIR CONDITIONERS – NO ECONOMIZERS Manual 2100-563C Page 18 of 40

Summary of the content on the page No. 19

FIGURE 3 CONTROLLER CONNECTIONS 1-STAGE (WA/WL, W**A/W**L SERIES) AIR CONDITIONERS – NO ECONOMIZER WITH ALARM BOARD & CB4000 COMMUNICATION BOARD Manual 2100-563C Page 19 of 40

Summary of the content on the page No. 20

FIGURE 4 CONTROLLER CONNECTIONS 2-STAGE (WA*S/WL*S SERIES) AIR CONDITIONERS – NO ECONOMIZERS WITH ALARM BOARD & CB4000 COMMUNICATION BOARD Manual 2100-563C Page 20 of 40


Alternative user manuals
# User manual Category Download
1 Bard Mfg. Co.P1136A1 User manual Air Conditioner 24
2 Bard Mfg. Co.W17A User manual Air Conditioner 5
3 Bard Mfg. Co.HA4S3KA User manual Air Conditioner 3
4 Bard Mfg. Co.HL5S2KA User manual Air Conditioner 4
5 Bard 357-93-E User manual Air Conditioner 4
6 Bard Mfg. Co.W12A1 User manual Air Conditioner 2
7 Bard Mfg. Co.w17a2 User manual Air Conditioner 14
8 Bard Mfg. Co.P1130A1 User manual Air Conditioner 0
9 Bard Mfg. Co.HL4S2KA User manual Air Conditioner 1
10 Bard Mfg. Co.W18L1 User manual Air Conditioner 0
11 Bard Mfg. Co.W30L1 User manual Air Conditioner 1
12 Bard Mfg. Co.W42A1 User manual Air Conditioner 4
13 Bard Mfg. Co.W24L1 User manual Air Conditioner 1
14 Bard Mfg. Co.W24A1 User manual Air Conditioner 3
15 Bard Mfg. Co.W42L2 User manual Air Conditioner 0
16 Sony SU-PW2 User manual Air Conditioner 12
17 Sony CV-P12PX User manual Air Conditioner 3
18 Sony MULTI CHANNEL AV RECEIVER STR-DG710 User manual Air Conditioner 31
19 Sony VGN-BX500 User manual Air Conditioner 1
20 Philips 190S5 User manual Air Conditioner 21