Powerware FCC 15 user manual

User manual for the device Powerware FCC 15

Device: Powerware FCC 15
Category: Network Card
Manufacturer: Powerware
Size: 0.51 MB
Added : 9/15/2013
Number of pages: 32
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Powerware FCC 15. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Powerware FCC 15.

For your convenience

If looking through the Powerware FCC 15 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Powerware FCC 15 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Powerware FCC 15 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Powerware FCC 15 User manual - Online PDF
Advertisement
« Page 1 of 32 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Powerware FCC 15 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Powerware FCC 15. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

®®
Powerware Modbus Card
User’s Guide

Summary of the content on the page No. 2

ClassAEMCStatements FCCPart15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to rad

Summary of the content on the page No. 3

Table of Contents 1 Introduction ......................................................... 1 2 InstallingtheModbusCard ............................................. 3 InspectingtheEquipment................................................................ 3 Four-WireCommunication ............................................................... 4 InstallingtheModbusCardintoanX-Slot .................................................... 6 3 WiringtheModbusCard ..........................................

Summary of the content on the page No. 4

TABLE OF CONTENTS ® ® ii EATON Powerware Modbus Card User’s Guide S 164201376 Rev C www.powerware.com

Summary of the content on the page No. 5

Chapter 1 Introduction ® ® ® ® The Eaton Powerware Modbus Card is an X-Slot connectivity device that allows you to continuously and reliably monitor the UPSs in your Building Management System (BMS). The card uses the Modbus protocol to integrate data from the UPS into your building management R software, such as Wonderware. The Modbus Card, shown in Figure 1, has the following features: S RS-485 communication through an isolated DB-9 port or isolated terminal strip S Selectable termination and

Summary of the content on the page No. 6

INTRODUCTION BuildingManagementSoftware Ethernet EthernetGateway RS-485Network -270.6 -270.6 PowerMeter UPSwithModbusCard PLC Figure2.UPSIntegratedwithRS-485Network ® ® 2 EATON Powerware Modbus Card User’s Guide S 164201376 Rev C www.powerware.com

Summary of the content on the page No. 7

Chapter 2 Installing the Modbus Card The Modbus Card is available: S as a separate card for use with UPSs that have an X-Slot S factory-installed in a Powerware Expansion Chassis Use the following sequence for installing the Modbus Card: 1. For four-wire networks only, change the jumpers on the Modbus Card (see “Four-Wire Communication” on page 4). 2. If the Modbus Card will be the last device installed in the network chain or the length of the network cable is excessive, termination needs to be

Summary of the content on the page No. 8

INSTALLING THE MODBUS CARD Four-Wire Communication The factory-default setting for the Modbus Card is for two-wire communication. To change the default setting, adjust the jumpers on the Modbus Card. CAUTION Topreventelectrostaticdischarge(ESD),placeonehandonanunpaintedmetalsurfacesuch astheUPSrearpanel. 1. If you are installing the Modbus Card into an X-Slot, complete Step 3 only. If you are installing the Powerware Expansion Chassis with your UPS, complete Steps 2 through 4. 2. Remove the card

Summary of the content on the page No. 9

INSTALLING THE MODBUS CARD 3. Change the J9 and J10 jumpers to the desired setting as shown in Figure 4. Two-Wire (Default) J10 J7 J8 1 1 J10 J9 J9 Four-Wire J10 1 ON 1 S2 J11 123456 1 J9 Figure4.ModbusCardJumpers 4. Reinstall the Modbus Card into the Powerware Expansion Chassis. Align the Modbus Card with the slot guides and slide the card into the slot until it is firmly seated. Secure the Modbus Card with the screws removed in Step 2. ® ® EATON Powerware Modbus Card User’s Guide S 164201376 R

Summary of the content on the page No. 10

INSTALLING THE MODBUS CARD Installing the Modbus Card into an X-Slot CAUTION Topreventelectrostaticdischarge(ESD),placeonehandonanunpaintedmetalsurfacesuch astheUPSrearpanel. 1. Remove the X-Slot cover (or existing X-Slot module) on the UPS rear panel. Retain the screws (see Figure 5). NOTE SomeUPSsmayhaveanotherX-Slotmodulealreadyinstalled(suchasthe Powerware9125UPS).Ifthereisacommunicationcableattachedtothismodule,disconnect thecableandthenremovetheX-Slotmodule. Figure5.RemovingtheSingle-PortM

Summary of the content on the page No. 11

Chapter 3 Wiring the Modbus Card The Modbus Card provides an easy path for integrating a Powerware UPS into an RS-485 Modbus network and also provides isolation of the communication between the UPS and the RS-485 Modbus network. You can use the DB-9 port or terminal strip on the Modbus Card to wire into a two-wire or four-wire network. Two-Wire Networks The Modbus Card’s default configuration is for two-wire, half-duplex, RS-485 networks. Figure 6 shows a detailed view of two-wire connections us

Summary of the content on the page No. 12

WIRING THE MODBUS CARD Four-Wire Networks The Modbus Card also supports four-wire, half-duplex, RS-485 networks. Figure 7 shows a detailed view of four-wire connections using the Modbus Card terminal strip. UPSwith SlaveDevice#1 SlaveDevice#2 ModbusCard TxD+ RxD+ TxD– RxD– R * T R * T Gnd R+ T+ R-- T-- Gnd R+ T+ R-- T-- MasterDevice R * T T-- R-- T+ R+ Gnd R * T *SeeNote Figure7.Four-WireRS-485ModbusNetwork NOTE Belden9842orequivalentcabling(adualtwisted-pairshieldedcablewithground) isrecommende

Summary of the content on the page No. 13

WIRING THE MODBUS CARD Forfour-wirenetworks. All four RS-485 network signals including TxD(+), RxD(+), TxD(–), and RxD(–) must be connected to the terminal strip as illustrated in Table 1. Verify that the Modbus Card J9 and J10 jumpers are set to the four-wire option (see “Four-Wire Communication” on page 4). TxD+ RxD+ TxD– RxD– GND 12345 Figure8.RS-485TerminalStrip Table1.RS-485TerminalStripPinAssignments RS-485NetworkSignals PinNumber ModbusCardSignalName MasterSignalName 1 TxD(+) RxD(+) 2 RxD

Summary of the content on the page No. 14

WIRING THE MODBUS CARD 5 4 3 2 1 9 8 7 6 Figure9.RS-485DB-9PinNumbers Table2.RS-485DB-9PinAssignments RS-485NetworkSignals PinNumber ModbusCardSignalName MasterSignalName 1 RxD(+) TxD(+) 2 TxD(+) RxD(+) 3 Signalcommon Signalcommon 4 Reserved — 5 Reserved — 6 RxD(–) TxD(–) 7 TxD(–) RxD(–) 8 Reserved — 9 Reserved — Termination CAUTION TerminationresistorsshouldbeplacedonlyattheextremeendsoftheRS-485network.No morethantwoterminationpointsshouldbeusedintheRS-485network. Termination is not required u

Summary of the content on the page No. 15

WIRING THE MODBUS CARD Four-Wire Two-Wire ON *OFF *Factory-default=OFF J7J8 12 3 4 5 6 J10 TxD(–)PullDown(620Ω) J9 TxD(+)PullUp(620Ω) TxDTerminator(120 Ω) 1 S2 J11 RxDTerminator(120 Ω) RxD(+)PullUp(620 Ω) RxD(–)PullDown(620 Ω) Figure10.S2TerminationConfiguration If a value other than the on-board 120 ohm termination is required, then S2-3 and S2-4 should be set to the OFF position. The Modbus Card terminal strip provides easy access to attach external termination resistors across the TxD(+), TxD

Summary of the content on the page No. 16

WIRING THE MODBUS CARD RS-232 Modbus Port It is also possible to use the RS-232 Modbus port for connecting to your network. 5 4 3 2 1 9 8 7 6 Figure11.RS-232DB-9PinNumbers Table3.RS-232DB-9PinAssignments PinNumber Function DirectionfromtheModbusCard 1 Noconnection — 2 RS-232transmitdata Out 3 RS-232receivedata In 4 Noconnection — 5 Signalcommon — 6 Noconnection — 7 Noconnection — 8 Noconnection — 9 Noconnection — ® ® 12 EATON Powerware Modbus Card User’s Guide S 164201376 Rev C www.powerware.com

Summary of the content on the page No. 17

Chapter 4 Modbus Card Configuration The Modbus Card has an RS-232 configuration port that you can access with a terminal or a computer equipped with a terminal emulation program. To use the configuration screens for the Modbus Card, you need: S A serial communication cable (supplied). S A terminal with a serial communication port, or a computer with a R terminal emulation program such as HyperTerminal . The serial line should be set to 9600 baud, No parity, 8 data bits, 1 stop bit, and no hardwa

Summary of the content on the page No. 18

MODBUS CARD CONFIGURATION 2. Press [Enter]. The Configuration screen appears (see Figure 13). Powerware Modbus Card Version 1.00 (1-16-02) Current Configuration: Baud Rate: 9600 Slave Address: 29 ----------------------------------------------------------------------------- Valid Commands: AD Change Slave Address, usage AD n, where n is the new slave address for the card (1 - 247 valid). BD Change Modbus Baud Rate, usage BD n, where n is the new baud rate (1200, 2400, 4800, 9600, 19200). SA Save

Summary of the content on the page No. 19

MODBUS CARD CONFIGURATION 4. To configure the slave address, type AD followed by a space and node (1 through 247) and press [Enter]. The default is 29. This setting affects both RS-232 and RS-485 Modbus connections. 5. To save and exit, type SA and press [Enter] to permanently save the new configuration changes. 6. The card is now configured. Shut down the terminal emulation program and disconnect the serial cable from the Modbus Card. 7. Continue to Chapter 5, “Integrating the UPS” on page 17.

Summary of the content on the page No. 20

MODBUS CARD CONFIGURATION ® ® 16 EATON Powerware Modbus Card User’s Guide S 164201376 Rev C www.powerware.com


Alternative user manuals
# User manual Category Download
1 Powerware 3110 User manual Network Card 18
2 Powerware 5115 User manual Network Card 69
3 Powerware 5125 User manual Network Card 57
4 Powerware 700 3000 VA User manual Network Card 0
5 Powerware 700 VA User manual Network Card 0
6 Powerware 5115 RM User manual Network Card 2
7 Powerware IPK-0320 User manual Network Card 0
8 Powerware BestLink IPK-0319 User manual Network Card 0
9 Powerware IPK-0318 User manual Network Card 0
10 Powerware E.T.N 1500 VA - 60kVa User manual Network Card 3
11 Powerware 5119 User manual Network Card 39
12 Powerware 9315 User manual Network Card 14
13 Powerware Uninterruptible Power Supply SOLA 4000 User manual Network Card 0
14 Powerware UPS Sidecar9390 User manual Network Card 160
15 Powerware 300 VA User manual Network Card 0
16 Sony BTA-NW1A User manual Network Card 2
17 Sony BKMW-E3000 User manual Network Card 2
18 Sony AC-SQ950D User manual Network Card 0
19 Sony BBV RX100 User manual Network Card 3
20 Sony CLIE A-AVZ-100-11 User manual Network Card 1