Bard Mfg. Co.WA361 user manual

User manual for the device Bard Mfg. Co.WA361

Device: Bard Mfg. Co.WA361
Category: Air Conditioner
Manufacturer: Bard
Size: 0.48 MB
Added : 12/21/2013
Number of pages: 19
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Bard Mfg. Co.WA361. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Bard Mfg. Co.WA361.

For your convenience

If looking through the Bard Mfg. Co.WA361 user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Bard Mfg. Co.WA361 on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Bard Mfg. Co.WA361 to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Bard Mfg. Co.WA361 User manual - Online PDF
Advertisement
« Page 1 of 19 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Bard Mfg. Co.WA361 but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Bard Mfg. Co.WA361. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

WALL MOUNTED
PACKAGED
INSTALLATION
AIR CONDITIONER
INSTRUCTIONS
Models: WA301, WA361
MIS-656
Bard Manufacturing Company Manual No.: 2100-192M
Supersedes: 2100-192L
Bryan, Ohio 43506
File: Volume III, Tab 16
Since 1914...Moving ahead just as planned.
Date: 05-13-02
© Copyright 2002

Summary of the content on the page No. 2

Contents Start Up Getting Other Information and Publications For more information, Important Installer Note........................................ 13 Crankcase Heaters .............................................. 13 contact these publishers ........................................ 1 Service Hints ........................................................ 13 Wall Mount General Information Sequence of Operation ........................................ 13 Air Conditioner Wall Mount Model Nomenclat

Summary of the content on the page No. 3

Getting Other Information and Publications These publications can help you install the air FOR MORE INFORMATION, CONTACT conditioner or heat pump. You can usually find these at THESE PUBLISHERS: your local library or purchase them directly from the publisher. Be sure to consult current edition of each ACCA Air Conditioning Contractors of America standard. 1712 New Hampshire Avenue NW Washington, DC 20009 National Electrical Code ....................... ANSI/NFPA 70 Telephone: (202) 483-9370 Fax:

Summary of the content on the page No. 4

WALL MOUNT GENERAL INFORMATION AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE MODEL CONTROL MODULES WA 361– A 10 X XXXXA NUMBER COIL OPTIONS CAPACITY X- Standard 30 - 2 1/2 Ton REVISIONS 36 - 3 Ton 1 - Phenolic Coated Evapora- COLOR OPTIONS tor KW X - Beige (Standard) 2 - Phenolic Coated Con- 1 - White denser 2 - Mesa Brown 3 - Phenolic Coated Evapora- VENTILATION OPTIONS VOLTS & PHASE 4 - Buckeye Gray X - Barometric Fresh Air tor A - 230/208/60/1 5 - Desert Brown and Condenser Damper B - 23

Summary of the content on the page No. 5

Manual 2100-192 Page 3 TABLE 2 DIMENSIONS OF BASIC UNIT (NOMINAL) Sn upply Retur Width Depth Height Model (W) (D) (H) A BCB EF G I J K L M N O P Q R S T WA30 35 8.20013 7.1278 0.5678 .828 7.818 3.820 7.840 0.015 8.523 5.715 7.925 6.725 8.720 9.225 7.029 .735 9.124 2.799 .140 .110 2.0 5.0 WA36 FIGURE 1 UNIT DIMENSIONS FRONT VIEW SIDE VIEW BACK VIEW MIS-1262 * Optional top outlet (factory installed only) for WA30 and WA36 models only.

Summary of the content on the page No. 6

Manual 2100-192 Page 4 TABLE 3 ELECTRIC HEAT TABLE WB A301-A WC A301- WA A301-WB A361- WC A361- WA361- Models21 40V-123 08V-23 40V-23 08V-41 60V-21 40V-23 08V-23 40V-23 08V- 460V- KS WAH MPBS TUAH MPBS TUAH MPBS TUAH MPBS TUAH MPBS TUAH MPBS TUAH MPBS TUAH MPBS TUAH MPBS TUAH MP BTU 58 .025 0.11 7,0610 8.1- 2,80-- - -- - -- - -- - -- - -8 -25 0.11 7,0610 8.1- 2,80-- - -- - -- - -- - -- - -- 83 .030 3.28 7,3025 8.2- 0,47 -- - -- - -- - -- - -- - -3 -30 3.28 7,3025 8.2- 0,47 -- - -- - -- - --

Summary of the content on the page No. 7

Refer to Table 10 for maximum static pressure available SHIPPING DAMAGE for duct design. Upon receipt of equipment, the carton should be Design the duct work according to methods given by the checked for external signs of shipping damage. If Air Conditioning Contractors of America (ACCA). damage is found, the receiving party must contact the When duct runs through unheated spaces, it should be last carrier immediately, preferably in writing, insulated with a minimum of 1 inch of insulation. Use

Summary of the content on the page No. 8

FRESH AIR INTAKE The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper All units are built with fresh air inlet slots punched in shipped with each unit. the service panel. If the unit is equipped with the fresh air damper CONDENSATE DRAIN assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed A plastic drain hose extends from the drain pan at the position. To allow the damper to operate

Summary of the content on the page No. 9

INSTALLATION INSTRUCTIONS 6. Position unit in opening and secure with 5/16 lag WALL MOUNTING INFORMATION bolts; use 7/8 inch diameter flat washers on the lag 1. Two holes, for the supply and return air openings, bolts. must be cut through the wall as shown in Figure 3. 7. Secure rain flashing to wall and caulk across entire 2. On wood-frame walls, the wall construction must be length of top. See Figure 3. strong and rigid enough to carry the weight of the unit without transmitting any unit vibra

Summary of the content on the page No. 10

The electrical data lists fuse and wire sizes (75ºC WIRING — LOW VOLTAGE WIRING copper) for all models, including the most commonly 230/208V, 1 phase and 3 phase equipment dual primary used heater sizes. Also shown are the number of field voltage transformers. All equipment leaves the factory power circuits required for the various models with wired on 240V tap. For 208V operation, reconnect from heaters. 240V to 208V tap. The acceptable operating voltage The unit rating plate lists a “Maximum T

Summary of the content on the page No. 11

FIGURE 3 MOUNTING INSTRUCTIONS 4 9/ 16 MIS-311 NOTE: It is recommended that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of installation. FIGURE 4 ELECTRIC HEAT CLEARANCE WARNING WARNING • A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. • It is important to insure that the 1/4 inch Side section view of minimum spac

Summary of the content on the page No. 12

FIGURE 5 WALL-MOUNTING INSTRUCTIONS SEE FIGURE 3 – MOUNTING INSTRUCTIONS MIS-548 FIGURE 6 WALL-MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS, FIGURE 1, FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DUCT DIMENSIONS MIS-549 Manual 2100-192 Page 10

Summary of the content on the page No. 13

FIGURE 7 COMMON WALL-MOUNTING INSTALLATIONS MIS-550 Manual 2100-192 Page 11

Summary of the content on the page No. 14

FIGURE 8 LOW VOLTAGE WIRING MIS-1373C Manual 2100-192 Page 12

Summary of the content on the page No. 15

START UP COMPRESSOR CONTROL MODULE IMPORTANT INSTALLER NOTE The compressor control module is optional on the For improved start-up performance, wash the indoor models covered by this manual. The compressor control coil with a dishwasher detergent. is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output. CRANKCASE HEATERS Adjustable Delay On Make And Break Timer All units are provided with some form of compressor crankcase heat. On initial power u

Summary of the content on the page No. 16

High Pressure Switch and Lockout Sequence ADJUSTMENTS If the high pressure switch opens, the compressor Adjustable Delay on Make and Delay on Break contactor will de-energize immediately. The lockout Timer timer will go into a soft lockout and stay in soft lockout The potentiometer is used to select Delay on Break time until the high pressure switch closes and the delay on from 30 seconds to 5 minutes. Delay on Make (DOM) break time has expired. If the high pressure switch timing on power-up

Summary of the content on the page No. 17

TROUBLESHOOTING FAN BLADE SETTING DIMENSIONS TABLE 8 SUCTION LINE TEMPERATURES Shown in the drawing below are the correct fan blade setting dimensions for proper air delivery across the Rated 95°F 82°F Model Airflow OD Temp. OD Temp. outdoor coil. W0 A30117 ,1056 5 - 5 64 - 6 Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions W0 A36119 ,1054 7 - 5 62 - 6 below be checked and blade adjusted in or out on the motor shaft accordingly. The s

Summary of the content on the page No. 18

TABLE 11 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY Mt odelFt rontOutle Top Outle Low High Low High KW Speed Speed Speed Speed A00 .50 .50 .50 .50 A05 .50 .50 .45 .50 A08 .50 .50 --- --- A10 .45 .50 .35 .50 A15 .35 .40 --- --- B00 .50 .50 .50 .50 B06 .40 .50 --- --- B09 .50 .50 .40 .45 B15 .30 .45 --- --- C00 .50 .50 .50 .50 C06 .50 .50 --- --- C09 .40 .50 .40 .45 C15 .35 .45 --- --- TABLE 12 COOLING PRESSURE – OUTDOOR TEMPERATURE °F Return Air ModelTe emperatureP5 ressur 708580959015 010 01

Summary of the content on the page No. 19

TABLE 13 OPTIONAL ACCESSORIES MN ODEL DESCRIPTIO EHWA03-A05 XX Heater Packages 1 EHWA03-A08 Heater Packages 1 XX EHWA03-A10 Heater Packages 1 XX EHWA03-A15 Heater Packages 1 XX EHWA03-B06 Heater Packages 1 XX EHWA03-B09 XX Heater Packages 1 EHWA03-B15 Heater Packages 1 XX EHWA03-C06 Heater Packages 1 XX EHWA03-C09 Heater Packages 1 XX EHWA03-C12 Heater Packages 1 X EHWA03-C15 XX Heater Packages 1 Be OP-3 Blank OffPlat XXXXXX Br FAD-3 Barometric FreshAir Dampe XXXXXX Mr FAD-3 Motorized FreshAir


Alternative user manuals
# User manual Category Download
1 Bard Mfg. Co.P1136A1 User manual Air Conditioner 24
2 Bard Mfg. Co.W17A User manual Air Conditioner 5
3 Bard Mfg. Co.HA4S3KA User manual Air Conditioner 3
4 Bard Mfg. Co.HL5S2KA User manual Air Conditioner 4
5 Bard 357-93-E User manual Air Conditioner 4
6 Bard Mfg. Co.W12A1 User manual Air Conditioner 2
7 Bard Mfg. Co.w17a2 User manual Air Conditioner 14
8 Bard Mfg. Co.P1130A1 User manual Air Conditioner 0
9 Bard Mfg. Co.HL4S2KA User manual Air Conditioner 1
10 Bard Mfg. Co.W18L1 User manual Air Conditioner 0
11 Bard Mfg. Co.W30L1 User manual Air Conditioner 1
12 Bard Mfg. Co.W42A1 User manual Air Conditioner 4
13 Bard Mfg. Co.W24L1 User manual Air Conditioner 1
14 Bard Mfg. Co.W24A1 User manual Air Conditioner 3
15 Bard Mfg. Co.W42L2 User manual Air Conditioner 0
16 Sony SU-PW2 User manual Air Conditioner 12
17 Sony CV-P12PX User manual Air Conditioner 3
18 Sony MULTI CHANNEL AV RECEIVER STR-DG710 User manual Air Conditioner 31
19 Sony VGN-BX500 User manual Air Conditioner 1
20 Philips 190S5 User manual Air Conditioner 21