Summary of the content on the page No. 1
InRoom™
Precision Air Conditioner
Technical Data
ACPDX21-86, ACPCW40-150
Summary of the content on the page No. 2
American Power Conversion Legal Disclaimer The information presented in this manual is not warranted by the American Power Conversion Corporation to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan. Therefore, American Power Conversion Corporation assumes no liability for damages, violations of codes, improper installation, system failures, or any other problems that could arise based on
Summary of the content on the page No. 3
Contents Overview ..................................................................................................... 1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Scalable Solution for Critical Environments . . . . . . . . . . . . . . . . . . . . . . . . .2 Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Optional Features. . . . . . . . . . . . . . . . . .
Summary of the content on the page No. 4
InRoom Nomenclature Product Range Cooling System Model Size Number of Refrigeration Circuits Airflow Pattern D - Downflow, U - Upflow 0, 1, 2 A: Air-cooled DX: 21, 31, 45, 61, 86 CW: 40, 66, 90, 110, 150 G: Glycol-cooled ACW: Air-cooled with MultiCool P = Perimeter unit GCW: Glycol-cooled with MultiCool GE: Glycol-cooled with Economizer CW: Chilled Water Voltage Phase/Hertz Reheat Humidification Mains Input Selection 0 - Standard Disconnect, 1 - Dual Power with ATS *, 2 - Dual Power without
Summary of the content on the page No. 5
Overview General The InRoom product family is an Room Air Distribution Standard Features assemble to order (ATO) line of The InRoom downflow system 1. Insulated Cabinet perimeter air conditioning draws warm exhaust air in 2. Direct Drive Fans systems that provide precision through the top of the unit and 3. Electrical Panel cooling for data centers and cools it. The cool air is distributed server rooms. 4. Main Power Disconnect back into the room through a Switch Precision environmenta
Summary of the content on the page No. 6
Scalable Solution for Critical Environments Temperature and Humidity Low Humidity APC InRoom - Design Conditions The Right Solution Low humidity greatly increases the possibility of static electric Maintenance of temperature and The APC InRoom cooling unit discharges. Static discharges can humidity design conditions is provides the maximum amount of corrupt data and damage critical to the smooth operation of precision cooling in a compact hardware. a technology room. Based on foot
Summary of the content on the page No. 7
Standard Features Insulated Panels Refrigeration System and Evaporative Freeze Compressor Protection The frame is constructed of 16 gauge steel sheet metal for The refrigeration system operates Suction pressure is actively maximum strength. All exterior under a master controller for monitored by two individual panels and corner posts on the greater efficiency and accuracy. sensors and controlled by the frame are powder coated for Suction and discharge pressures microprocessor controller
Summary of the content on the page No. 8
Optional Features Humidifier Hot Gas Bypass Valve Plenums The humidifier utilizes a pure The hot gas bypass valve Discharge plenums are available steam generator specifically (HGBV) adjusts the flow of on upflow configurations. This designed for precision compressor discharge gas to the application is recommended in environmental close control. The evaporator coil at low load rooms where raised floors are not pure steam eliminates conditions to protect the coil from available for air distrib
Summary of the content on the page No. 9
Condensate Pump 50 Hz 60 Hz Model # ACAC75107 ACAC75107 ACAC76106 Hz 60 60 50 Height mm (in) 259 (10 1/8) 259 (10 1/8) 210 (8 1/4) Width mm (in) 152 (6) 152 (6) 132 (5 1/4) Length 304 (12) 304 (12) 295 (11 1/2) Outlet mm (in) 13 (1/2) 13 (1/2) 6 (1/4) Volts 230 460 400 Amps 1.9 0.8 0.125 Watts 360 360 30 Weight Kg (Lb) Ea 5.8 (13) 5.8 (13) 3 (6.6) HP (motor only) 1/5 1/5 1/20 Tank Capacity Ltr (Gal) 3.785 (1) 3.785 (1) 1.4 (1/3) Liters (Gallons) per hour at 60 Hz/Rated Voltage Model Flow rate pe
Summary of the content on the page No. 10
Upflow Discharge Plenums for 50 Hz and 60 Hz InRoom Cooling Units Upflow discharge plenums Width Depth Height Cabinet size SKU mm (in) mm (in) mm (in) 1 ACPL75100 1000 (39.37) 2 ACPL75101 1400 (55.11) 3 ACPL75102 1750 (68.90) 900 (35) 500 (19.7) 4 ACPL75103 2150 (84.65) 5 ACPL75104 2550 (100.39) Note: Plenums are delivered completely assembled. 6 InRoom Precision AC Tech Data Manual na2874a
Summary of the content on the page No. 11
Downflow Discharge Plenums for 50 Hz InRoom Cooling Units Width Depth Height Cabinet size SKU mm (in) mm (in) mm (in) Unit Sub Base Plenum with no Grills 1 ACSB76100 960 (37.8) 2 ACSB76101 1360 (53.5) 3 ACSB76102 1710 (67.3) 865 (34) 450 (17.7) 4 ACSB76103 2110 (83.1) 5 ACSB76104 2510 (98.8) Unit Sub Base Plenum with Grills 1 ACSB76110 960 (37.8) 2 ACSB76111 1360 (53.5) 3 ACSB76112 1710 (67.3) 865 (34) 450 (17.7) 4 ACSB76113 2110 (83.1) 5 ACSB76114 2510 (98.8) Unit Sub Base Plenum with Dam
Summary of the content on the page No. 12
Standard Floorstands for InRoom 60Hz Cooling Units Cabinet Height Width Depth size Model mm (in) mm (in) mm (in) ACFS76000 254 (10) 960 (37.8) 864 (34) ACFS76001 305 (12) 1 ACFS76002 381 (15) ACFS76003 457 (18) ACFS76004 609 (24) ACFS76005 254 (10) 1359 (53.5) 864 (34) ACFS76006 305 (12) 2 ACFS76007 381 (15) ACFS76008 457 (18) ACFS76009 609 (24) ACFS76010 254 (10) 1712 (67.4) 864 (34) ACFS76011 305 (12) 3 ACFS76012 381 (15) ACFS76013 457 (18) ACFS76014 609 (24) ACFS76015 254 (10) 2108 (83.0) 864
Summary of the content on the page No. 13
Bowling Alley Floorstands for InRoom 60Hz Cooling Units Cabinet Height Width Depth size Model mm (in) mm (in) mm (in) ACFS76033 305 (12) ACFS76032 381 (15) 1 960 (37.8) 864 (34) ACFS76031 457 (18) ACFS76030 609 (24) ACFS76037 305 (12) ACFS76036 381 (15) 2 1359 (53.5) 864 (34) ACFS76035 457 (18) ACFS76034 609 (24) ACFS76041 305 (12) ACFS76040 381 (15) 3 1712 (67.4) 864 (34) ACFS76039 457 (18) ACFS76038 609 (24) ACFS76045 305 (12) ACFS76044 381 (15) 4 2108 (83.0) 864 (34) ACFS76043 457 (18) ACFS76
Summary of the content on the page No. 14
Floorstands for InRoom 50 HzCooling Units Cabinet Height Width Depth size Model mm (in) mm (in) mm (in) 1 ACFS76025 250-500 (10-20) 960 (37.8) 864 (34) 2 ACFS76026 250-500 (10-20) 1359 (53.5) 864 (34) 3 ACFS76027 250-500 (10-20) 1712 (67.4) 864 (34) 4 ACFS76028 250-500 (10-20) 2108 (83.0) 864 (34) 5 ACFS76029 250-500 (10-20) 2512 (98.9) 864 (34) 10 InRoom Precision AC Tech Data Manual na3087a
Summary of the content on the page No. 15
Condensers Air cooled condensers are designed to reject heat from refrigerant based cooling equipment and are designed to be installed outdoors. The condensers are self-contained in a lighweight aluminum cabinet designed for mounting to a horizontal surface. The cabinet houses condenser coils and fan assemblies. Each condenser coil is a copper turb, aluminum finned coil. The capacity of the condenser is based on the rated capacity of the coil. In the case of dual circuit units, the model nu
Summary of the content on the page No. 16
InRoom Standard Condensers - 60 Hz InRoom Remote Outdoor Condenser Data, 95°F ambient, 120°F condensation - R407C InRoom Cabinet Size 1 2 3 4 5 Total Heat Rejection 96.219 165.496 225.435 279.262 380.436 (THR) BTU/h CFM 8,394 19,325 18,609 17,604 27,963 Fan Diameter - in 19.69 24.80 24.80 24.80 24.80 Voltage Options 208-230/3/60 ACCD76000 ACCD76004 ACCD76008 ACCD76012 ACCD76016 Number of Fans 2 2 2 2 3 Fan RPM (Qty) 1490 1585(1), 1500(1) 1585(1), 1500(1) 1585(1), 1500(1) 1585(2), 1500(1) Motor
Summary of the content on the page No. 17
InRoom Low Temperature (-30ºF) Condensers - 60 Hz InRoom Remote Outdoor Condenser Data, 95°F ambient, 120°F condensation - R407C InRoom Cabinet Size 1 2 3 4 5 Total Heat Rejection 96.219 165.496 225.435 279.262 380.436 (THR) BTU/h CFM 8,394 19,325 18,609 17,604 27,963 Fan Diameter - in 19.69 24.80 24.80 24.80 24.80 Voltage Options 208-230/3/60 ACCD76032 ACCD76033 ACCD76034 ACCD76035 ACCD76036 Number of Fans 2 2 2 2 3 Fan RPM (Qty) 1490 1585(1), 1500(1) 1585(1), 1500(1) 1585(1), 1500(1) 1585(2),
Summary of the content on the page No. 18
InRoom High Temperature Condensers - 60 Hz InRoom Remote Outdoor Condenser Data, 105°F ambient, 125°F condensation - R407C InRoom Cabinet Size 1 2 3 4 5 Total Heat Rejection 154,105 247,501 331,845 448,600 331,845 (2) (THR) BTU/h CFM 19,325 17,604 27,791 25,227 27,791 (2) Fan Diameter - in 25.60 25.60 25.60 25.60 25.60 Voltage Options 208-230/3/60 ACCD76004 ACCD76006 ACCD76016 ACCD76014 ACCD76020(2) Number of Fans 2 2 3 3 3 Fan RPM (Qty) 1585(1), 1500(1) 1585(1), 1500(1) 1585(2), 1500(1) 1585
Summary of the content on the page No. 19
InRoom Condensers - 50 Hz 50 Hz InRoom Remote Outdoor Condenser Data, 97°F ambient, 120°F condensation - R407C InRoom Cabinet Size 1 2 3 4 5 Condenser Model (Qty) ACCD76002 ACCD76003 ACCD76002 (2) ACCD76003 (2) ACCD76011(2) Voltage 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Number of Fans 2 2 3 3 3 3 Airflow m /h (cfm) 13600 (8024) 13000 (7670) 13600 (8024) each 13000 (7670) each 16800 (9912) each 2 x 0.69 2 x 0.69 2 x 0.69 2 x 0.69 3 x 0.69 Motor kW (HP) - (2 x 0.92) (2 x 0.92) (2 x 0.92) (2
Summary of the content on the page No. 20
Receivers Conformance. Each receiver conforms to UL, CSA or ASME requirements for 450 psi maximum working pressure. Models with an internal diameter under six inches are UL listed. All larger models are made according to ASME code and labeled appropriately. Pumpdown and refrigerant charge. All pumpdowns are calculated at 80% capacity of liquid. Approximately 10% of pumpdown capacity is required to operate the receiver properly. Pumpdown = (overall length – length correction) x (pumpdown per i