Emerson Rosemount Pressure Transmitter 3051SF user manual

User manual for the device Emerson Rosemount Pressure Transmitter 3051SF

Device: Emerson Rosemount Pressure Transmitter 3051SF
Category: Marine Instruments
Manufacturer: Emerson
Size: 2.61 MB
Added : 3/28/2014
Number of pages: 34
Print the manual

Download

How to use this site?

Our goal is to provide you with a quick access to the content of the user manual for Emerson Rosemount Pressure Transmitter 3051SF. Using the online preview, you can quickly view the contents and go to the page where you will find the solution to your problem with Emerson Rosemount Pressure Transmitter 3051SF.

For your convenience

If looking through the Emerson Rosemount Pressure Transmitter 3051SF user manual directly on this website is not convenient for you, there are two possible solutions:

  • Full Screen Viewing - to easily view the user manual (without downloading it to your computer), you can use full-screen viewing mode. To start viewing the user manual Emerson Rosemount Pressure Transmitter 3051SF on full screen, use the button Fullscreen.
  • Downloading to your computer - You can also download the user manual Emerson Rosemount Pressure Transmitter 3051SF to your computer and keep it in your files. However, if you do not want to take up too much of your disk space, you can always download it in the future from ManualsBase.
Emerson Rosemount Pressure Transmitter 3051SF User manual - Online PDF
Advertisement
« Page 1 of 34 »
Advertisement
Print version

Many people prefer to read the documents not on the screen, but in the printed version. The option to print the manual has also been provided, and you can use it by clicking the link above - Print the manual. You do not have to print the entire manual Emerson Rosemount Pressure Transmitter 3051SF but the selected pages only. paper.

Summaries

Below you will find previews of the content of the user manuals presented on the following pages to Emerson Rosemount Pressure Transmitter 3051SF. If you want to quickly view the content of pages found on the following pages of the manual, you can use them.

Abstracts of contents
Summary of the content on the page No. 1

4801_QIG_RevKB.fm Page 1 Friday, December 3, 2010 1:17 AM
Quick Installation Guide
00825-0100-4801, Rev KB
December 2010
Rosemount 3051S
Rosemount 3051S Series Pressure Transmitter
®
with HART Protocol
Rosemount 3051SF Series Flowmeter Transmitter
®
with HART Protocol
Start
Step 1: Mount the Transmitter
Step 2: Consider Housing Rotation
Step 3: Set Switches and Jumpers
Step 4: Connect Wiring and Power Up
Step 5: Verify Configuration
Step 6: Trim the Transmitter
Safety Instrumented Systems

Summary of the content on the page No. 2

4801_QIG_RevKB.fm Page 2 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB Rosemount 3051S December 2010 © 2010 Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. Rosemount Inc. Emerson Process Management 8200 Market Boulevard GmbH & Co. OHG Chanhassen, MN USA 55317 Argelsrieder Feld 3 T (US) (800) 999-9307 82234 Wessling T (Intnl) (952) 906-8888 Germany F (952)

Summary of the content on the page No. 3

4801_QIG_RevKB.fm Page 3 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S STEP 1: MOUNT THE TRANSMITTER Liquid Flow Applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward. Gas Flow Applications 1. Place taps in the top or side of the line. 2. Mount beside or above the taps. Steam Flow Applications 1. Place taps to the

Summary of the content on the page No. 4

4801_QIG_RevKB.fm Page 4 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB Rosemount 3051S December 2010 STEP 1 CONTINUED... Panel Mount Pipe Mount ™ Coplanar Flange Traditional Flange In-line Housings ™ PlantWeb Junction Box Remote Mount Display 4

Summary of the content on the page No. 5

4801_QIG_RevKB.fm Page 5 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S STEP 1 CONTINUED... Bolting Considerations If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 1 ill

Summary of the content on the page No. 6

4801_QIG_RevKB.fm Page 6 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB Rosemount 3051S December 2010 STEP 1 CONTINUED... Figure 2. Torque values for the flange and flange adapter bolts Bolt Material Head Markings Initial Torque Final Torque Carbon Steel (CS) 300 in.-lbs. 650 in.-lbs. B7M Stainless Steel (SST) 150 in.-lbs. 300 in.-lbs. 316 B8M 316 STM SW 316 316 316 R O-rings with Flange Adapters WARNING Failure to install proper flange adapter O-rings may

Summary of the content on the page No. 7

4801_QIG_RevKB.fm Page 7 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S STEP 1 CONTINUED... Inline Gage Transmitter Orientation The low side pressure port (atmospheric reference) on the inline gage transmitter is located under the sensor module neck label. (See Figure 3.) Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so that any contaminants c

Summary of the content on the page No. 8

4801_QIG_RevKB.fm Page 8 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB Rosemount 3051S December 2010 STEP 4: CONNECT WIRING AND POWER UP Use the following steps to wire the transmitter: 1. Remove the housing cover labeled “Field Terminals.” 2. Connect the positive lead to the “+” terminal, and the negative lead to the “–” terminal. NOTE Do not connect the power across the test terminals. Power could damage the test diode in the test connection. Twisted p

Summary of the content on the page No. 9

4801_QIG_RevKB.fm Page 9 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S STEP 4 CONTINUED... Signal Wiring Grounding Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Grounding terminations are provided on the sensor module and inside the Terminal Compartment. These grounds are used when transient protect terminal blocks are installed or to fulfill local regulations. See S

Summary of the content on the page No. 10

4801_QIG_RevKB.fm Page 10 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB Rosemount 3051S December 2010 STEP 4 CONTINUED... Remote Display Wiring and Power Up The Remote Mount Display and Interface system consists of a local transmitter and a remote mount LCD display assembly. The local 3051S transmitter assembly includes a Junction Box housing with a three position terminal block integrally mounted to a sensor module. The remote mount LCD display assembl

Summary of the content on the page No. 11

4801_QIG_RevKB.fm Page 11 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S STEP 4 CONTINUED... Intrinsic Safety Consideration: The transmitter assembly with remote display has been approved with Belden 3084A DeviceNet cable. Alternate cable may be used as long as the transmitter with remote display and cable is configured according to the installation control drawing or certificate. Refer to appropriate approval certificate or

Summary of the content on the page No. 12

4801_QIG_RevKB.fm Page 12 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB Rosemount 3051S December 2010 STEP 4 CONTINUED... NOTE Wire colors provided on page 11 are per Belden 3084A DeviceNet cable. Wire color may vary depending on cable selected. Belden 3084A DeviceNet cable includes a ground shield. This shield must be connected to earth ground at either the sensor module or the Remote Display, but not both. Quick Connect Wiring As standard, the 3051S Qu

Summary of the content on the page No. 13

4801_QIG_RevKB.fm Page 13 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S STEP 4 CONTINUED... Conduit Electrical Connector Wiring (Option GE or GM) For 3051S transmitters with conduit electrical connectors GE or GM, refer to the cordset manufacturer’s installation instructions for wiring details. For FM Intrinsically Safe, non-incendive or FM FISCO Intrinsically Safe hazardous locations, install in accordance with Rosemount dr

Summary of the content on the page No. 14

4801_QIG_RevKB.fm Page 14 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB Rosemount 3051S December 2010 STEP 5: VERIFY CONFIGURATION Use any HART-compliant master to communicate with and verify configuration of the 3051S. For the HART Diagnostics transmitter (option code DA1), DD revision 3051S HDT Dev. 1 Rev. 1 is required. Field Communicator User Interface The Traditional Interface - Device Revision 6 or 7 and DD Revision 7 Fast Key Sequence can be foun

Summary of the content on the page No. 15

4801_QIG_RevKB.fm Page 15 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S A check () indicates the basic configuration parameters. At a minimum, these parameters should be verified as part of the configuration and startup procedure. Table 1. Traditional Interface - Device Revision 6 or 7 and DD Revision 7 Fast Key Sequence Function Fast Key Sequence Alarm Level Configuration 1, 4, 2, 7, 7 Alarm and Saturation Levels 1, 4, 2, 7

Summary of the content on the page No. 16

4801_QIG_RevKB.fm Page 16 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB Rosemount 3051S December 2010 Table 2. Device Dashboard - Device Revision 7 and DD Revision 9 Fast Key Sequence Function Fast Key Sequence Alarm and Saturation Levels 2,2,1,7 Burst Mode Control 2,2,4,2 Burst Option 2,2,4,3 Custom Display Configuration 2,1,3  Damping 2,2,1,5 Date 2,2,5,4 Descriptor 2,2,5,5 Digital to Analog Trim (4 - 20 mA Output) 3,4,2 Disable Zero & Span Adjustment

Summary of the content on the page No. 17

4801_QIG_RevKB.fm Page 17 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S STEP 6: TRIM THE TRANSMITTER Transmitters are shipped fully calibrated per request or by the factory default of full scale (lower range value = zero, upper range value = upper range limit). Zero Trim A zero trim is a single-point adjustment used for compensating mounting position and line pressure effects. When performing a zero trim, ensure that the equ

Summary of the content on the page No. 18

4801_QIG_RevKB.fm Page 18 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB Rosemount 3051S December 2010 SAFETY INSTRUMENTED SYSTEMS Additional Safety Instrumented Systems information is available in the Rosemount 3051S reference manual (document number 00809-0100-4801). The manual is available electronically on www.rosemount.com or by contacting an Emerson Process Management representative. 3051S Safety-Certified Identification All 3051S transmitters must

Summary of the content on the page No. 19

4801_QIG_RevKB.fm Page 19 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S NOTES 1. Transmitter output is not safety-rated during the following: configuration changes, multidrop, loop test. Alternative means should be used to ensure process safety during transmitter configuration and maintenance activities. 2. DCS or safety logic solver should be configured to match transmitter configuration. Figure 15 identifies the three alar

Summary of the content on the page No. 20

4801_QIG_RevKB.fm Page 20 Friday, December 3, 2010 1:17 AM Quick Installation Guide 00825-0100-4801, Rev KB Rosemount 3051S December 2010 Operation and Maintenance Proof Test and Inspection The following proof tests are recommended. Proof test results and corrective actions taken must be documented at http://rosemount.d1asia.ph/rosemount/safety/ReportAFailure_newweb.asp in the event that an error is found in the safety functionality. Use the fast key sequences in Table 1 on page 15 or Ta


Alternative user manuals
# User manual Category Download
1 Emerson Digital Controller Valves 788 DVC User manual Marine Instruments 31
2 Emerson Four-electrode Conductivity Sensor 410VP User manual Marine Instruments 0
3 Emerson FCL with 1050 Analyzer 1056 User manual Marine Instruments 149
4 Emerson Four-electrode Conductivity Sensor PN 51A-410VP User manual Marine Instruments 0
5 Emerson ENDURANCE Conductivity Sensor 404 User manual Marine Instruments 1
6 Emerson ENDURANCE Conductivity Sensor PN 51A-404 User manual Marine Instruments 1
7 Emerson FCL with 1050 Analyzer PN 51-FCL-1056 User manual Marine Instruments 12
8 Emerson Mass Flow Transmitter 3095 User manual Marine Instruments 34
9 Emerson Multiport Flow Selector I-0168 User manual Marine Instruments 6
10 Emerson pH/ORP Analyzer/Controller 54e User manual Marine Instruments 3
11 Emerson pH/ORP Analyzer/Controller PN 51A-54epH User manual Marine Instruments 3
12 Emerson Mass Flow Transmitter 00825-0100-4716 User manual Marine Instruments 2
13 Emerson Rosemount Pressure Transmitter 3051S User manual Marine Instruments 58
14 Emerson pH/ORP Analyzer/Controller 54e pH User manual Marine Instruments 18
15 Emerson Tank Contents Transmitter MAS 2600 User manual Marine Instruments 115
16 Sony SSM-930 User manual Marine Instruments 3
17 Sony SSM-175A User manual Marine Instruments 0
18 Attwood 8M004689 User manual Marine Instruments 0
19 Attwood 99515-1 User manual Marine Instruments 0
20 Attwood 99510-1 User manual Marine Instruments 0